8
EM24 M1/M2 use
EM24 M1/M2 - Instruction manual | CARLO GAVAZZI Controls SpA
Step
Action
Button
6
In the
EnE PrES
page, set
YES
7
Confirm operation
Setting a parameter
Example procedure: how to set
P int. ti
=30 and save changes.
Step
Action
Button
1
Power on the energy analyzer
2
Press the joystick for at least 3 seconds
3
In the
PASS?
page, select the correct password (default 0)
4
Confirm operation
5
Scroll pages until
P int. ti
6
Enter the editing mode
7
Select 30
8
Confirm operation
9
Scroll pages until
End
to exit