Display shows incorrect number and arrow
•
Settings for DIP switch D2 and D3 on the display is not correct
•
Wrong programming of the CPM GP3482 9091 724
•
Wrong addressing of the sensors GP62x0 22xx
•
L2 bus is not working correctly
No communication from Parking Guidance System software to sensors
•
Check DIP switch address in the local GP3496 0005 to which the sensors are
connected
•
Check TCP-IP on the moxa
•
Check if port address on the moxa is open for incoming and outgoing signals
•
Use the moxa configuration unit which is downloadable from www�car-park�dk
•
Check power on the moxa, CPM (Carpark M, DMM (Dupline
®
Master Module) and
the sensors
Tips
•
Use 1�5 mm
2
(14-16AWG) single core wires in a system for the sensors and LED
indicators� If installer uses multi-core or stranded, the wires must be mounted with
ferrules because of the push connectors in the sensor�
•
To avoid large voltage drops at the far end of the sensors, be sure to have min 28 V
DC power to the GP34960005700�
•
If the system requires an enlargement which contains the repeater D3892 0000
xxx, please contact your closest Carlo Gavazzi sales company�
•
If two or more slave CPMs has the same ID number, the sensors will not be shown
correctly� The sensors will have the same addresses which will cause a conflict�
•
Use the Parking Guidance System Configuration unit GP7380 0080 in GTU8 mode
to simulate the presence of sensors during installation or troubleshooting�
•
If the two wires on the X, Y on the GP6589 0000 are reversed, the LED will light
with the wrong color� Red for available and green for occupied�