Model 90200A and G Microprocessor Temperature Controls — Data sheet

Mounting – 

90200A and G controls mount to any standard well. 

Mount the 90200A & G directly to a well (new or existing) with 

hardware supplied in the separate well mounting kit.

Well Kits – 

Wells for 90200A and G sensors are available in the 

sizes shown below. Well kits include sensor mounting hard-

ware designed to hold sensor securely in position. 

Sensors – 

Sensors are available separately for the 90200A and G. 

Configurations

Error Codes

3"

4

3

/

8

"

4

3

/

4

"

Error Code

Reason

01

Primary (K2) relay is welded on. 

Note: 

If the control is reset 

from error code 01, the red LED will flash every 5 seconds 

indicating the control must be replaced.

02

Primary & Safety relays (K1 and K2) on. The control cannot 

be reset from error code 02 and must be replaced.

03

Primary & Safety relays (K1 and K2) are off. 

Note:

 If this 

error is detected, the control will show error code 

03

 and 

enter soft lockout two times to try and resolve the issue. If 

the problem persists the control will enter hard lockout.

05

Simulated High Temp lockout

06

Temp is above set high temp but below thermistor high 

(250°F)

Error Code

Reason

20

Temp sensor 1 out of range failure

21

Temp sensor 2 out of range failure

22

High limit temp sensor out of range failure

23

Temp sensor 1 pin is open

24

Temp sensor 2 pin is open

25

High limit temp sensor is open

10

,

  1 1

,

 12

,

 13

,

 14

,

 15

Internal hardware safety failure – unit should be replaced. Contact customer service for additional informa-

tion. 1-800-989-2275