For more information, refer to user manual (cod.+0300083EN) before
installing this product. It is available in the documentation download
area at www.carel.com. Before commissioning, set the fi rst confi guration
parameters, as shown below and highlighted with a dark background in
the parameter table.
First confi guration parameter table
Cod. Description
/P
B1-B3 type
/A2 B2 confi guration
/A3 B3 confi guration
/P4 B4 type
/A4 B4 confi guration
/P5 B5 type
/A5 B5 confi guration
St
Set point
rd
Diff erential
c1
Minimum time between successive compressor starts
c2
Minimum compressor off time
c3
Minimum comp. on time
d0
Type of defrost
dt1 End defrost temperature, main evaporator
dP1 Maximum defrost duration
dd
Dripping time after defrost
A5
Digital input 2 confi g. (DI2)
A9
Digital input 3 confi g. (DI3)
F3
Evaporator fans during defrost 0/1=on/off
Fd
Post-dripping time
c12 Compressor safety time for door switch
d8d Compressor restart time for door switch
A3
Door switch disabling
tLi
Light on with door open
A4
Light management
Remove the bottom
faceplate and connect
the UltraCella Service to
the controller
If the UltraCella controller has never been confi gured, as soon
as the UltraCella Service is connected, the wizard is shown au-
tomatically. The Wizard menu can also be accessed to repe-
at the guided commissioning procedure at another time.
1
2
1
2
B: the commissioning procedure can be repeated by accessing
the Wizard menu.
1.Switch the controller OFF (press DOWN and select the On/Off icon;
press Set twice and then UP to switch the controller OFF; press Esc
twice to exit)
SET
PRG
ESC
M
E
N
U
H
E
L
P
03/12/13 Setpoint
17:52:30 0.0°C
36.8 °C
OFF
2.0 °C
2. To enter programming mode: Press Prg and enter the password:
1234
SET
PRG
ESC
M
E
N
U
H
E
L
P
Parameters Modification
Password: 1234
3. Press DOWN until reaching the “Wizard” menu
SET
PRG
ESC
M
E
N
U
H
E
L
P
Parameters Categ. 1/2
1-Probes
2-Control
3-Compressor
4. Confi rm by selecting Set
SET
PRG
ESC
M
E
N
U
H
E
L
P
Parameters Categ. 12/12
10-Door/Light
11-Recipes
12-Wizard
5. Press Up and SET to enter the guided commissioning procedure
SET
PRG
ESC
M
E
N
U
H
E
L
P
YES
Param.Cat Wizard
Do you want to use the
Wizard to configure
the cold room ?
USB memory key
The USB fl ash drive can be used to:
•
Download the list of parameter in the fl ash drive
•
Upload the list of parameters from the fl ash drive
•
Download log of stored temperatures
•
Download log of stored alarms
Preliminary operations:
1. remove the lower frame and insert the USB memory key;
2. set the control to OFF.
1
2
1
2
USB key
Access to multifunction menu
by pressing together PRG and
SET; select with UP / DOWN the
message “USb”.
Procedure:
Press two times Set:
the following commands will
appear by scrolling UP/DOWN:
•
EXt: press Set to exit;
•
dnL: press Set, the control saves
inside the key the 10 parameters
set: r01…r10;
•
uPd: press Set, the control loads
from the key the 10 parameters
set: r01…r10;
Note:
the parameters are saved in a text fi le type. txt, which can be
viewed on the computer
1
2
3
4
1
2
1
2
1
2
1
2
1
2
1
2
1
2
3
4
1
2
1
2
1
2
1
2
1
2
1
2
1
2
3
4
1
2
1
2
1
2
1
2
1
2
1
2
1
2
1
2
1
2
3
4
1
2
1
2
1
2
1
2
1
2
1
2
1
2
1
2
1
2
1
2
Note:
the fi gures refer to the screens on models with single row di-
splay, P/Ns WB000S*. In models with two rows, P/Ns WB000D*, as well
as the message indicated, during navigation the display shows the
scrolling message “recipes in USB device” on the second row
UltraCella SINGLE DIGIT MODELS COMMISSIONING
(cod. WB000S*)
SET
PRG
ESC
M
E
N
U
H
E
L
P
MENU
HELP
Multifunction menu
HACCP
Multifunction menu
HACCP
UltraCella with SINGLE DIGIT display
COMMISSIONING with ULTRACELLA SERVICE
(cod. PGDEWB0FZ0)
+
UltraCella Service
(accessory)
SET
PRG
ESC
M
E
N
U
H
E
L
P
MENU
HELP
Multifunction menu
HACCP
Multifunction menu
HACCP
SET
PRG
ESC
M
E
N
U
H
E
L
P
MENU
HELP
Multifunction menu
HACCP
Multifunction menu
HACCP
1
2
1
2
1
2
1
2
1. First switch the controller OFF (press ON/OFF).
1
2
1
2
1
2
1
2
2. Press Prg for 2 sec: the pas-
sword prompt is displayed
(PAS).
3. Press UP and enter the password:
22.
1
2
1
2
1
2
1
2
4. Press Set: the fi rst category is
displayed: Pro (Probes).
5. Press Set: the fi rst parameter is
displayed: /21.
1
2
1
2
1
2
1
2
6. Press repeatedly UP to reach
the parameter /P
7. Press Set to display the value of
the parameter (see settings in the
parameter table)
1
2
1
2
1
2
1
2
8. Press UP to modify the value.
9. Press Set to confi rm and return
to the parameter code. The new
value has now been saved on the
controller.
1
2
1
2
1
2
1
2
10. Press UP to move to para-
meters /A2.../ A5; make any
required settings
11. Press Prg to return to the para-
meter categories
1
2
1
2
12. Press UP to move to category
CtL and follow the previous steps
to set St and the following parame-
ters highlighted below and in the
parameter table.
UltraCella
with LED display
UltraCella DOUBLE DIGIT DISPLAY COMMISSIONING
(cod. WB000D*)
UltraCella with DOUBLE DIGIT display
1. First switch the controller OFF (press ON/OFF).
2. Press Prg for 2 sec: the password prompt is displayed
3. Press UP and enter the pas-
sword: 22.
4. Press Set: the second row of
the display will scroll the name of
the fi rst category of parameters:
Probes.
5. Press Set: the second row of
the display will scroll the code
and description of the fi rst para-
meter in the category: /21 – Pro-
be1 meas. stab.; the fi rst row of
the display will show the current
value of the parameter
6. Press UP repeatedly until rea-
ching parameter /P. The second
row of the display will scroll the
code and description of the para-
meter: /P – type B1 to B3; the fi rst
row of the display will show the
current value of the parameter
7. Press Set and UP/DOWN to set
the desired value of the para-
meter.
8. Press Set to confi rm. The new
value entered is now saved on the
controller
9. Press UP to move to parame-
ters /A2…/A5; make any required
settings
10. Press Prg to return to the cate-
gories of parameters
11. Press UP to move to category
CtL (the second row scrolls the
name of the second category of
parameters: Control) and follow
the previous steps to set St and
the subsequent parameters, as
shown in the previous table and in
the parameter table
A: First start-up
When starting for the fi rst time, once the UltraCella Service is con-
nected, the wizard is shown automatically
Set “Yes” to change the set point and then answer the questions to set
the other parameters.
SET
PRG
ESC
M
E
N
U
H
E
L
P
YES
Param.Cat Wizard
Do you want to modify
the main set point ?