2. Preparing for assembly
The blower must be mounted or on the wall and connected to the humidifier via the steam hose.
The maximum length of the steam hose is 4 m.
Note:
observe the minimum distances shown in the following figures to prevent the flow of
humidified air from coming into contact with people, electrical equipment, false-ceilings and cold
surfaces before the steam is totally absorbed by the atmosphere.
Fig.2.a
Mounting (all dimensions in m[ft])
Ref.
Wall
A
>5[16.4]
B
≥2[6.5]
C + E
≥ 2.1[6.8]
D
>0.5[1.6]
E
≤4[13.1]
Tab.2.a
Notes:
l
dimension C+E can be lower if it is not possible to transit in front of the blower unit;
l
see the humidifier manual for details on positioning.
2.1
Requirements
2.1.1 Steam hose
Follow these instructions when installing the steam hose:
l
only use hoses supplied by CAREL; hoses made from other materials may adversely affect operation of
the system;
l
the steam hose must be secured by supports (clamps, brackets) so that it does not bend and does not
weigh on the humidifier. A hot hose is more likely to bend;
l
the minimum radius of curvature of the steam hose is 5 times the inside diameter;
l
the steam hose must have a minimum slope in order to drain condensate back to the humidifier; in
any case, always install a condensate drain at the lowest point on the steam hose;
l
minimise the length of the steam hose so as to reduce heat loss. Avoid the formation of pockets or
traps where condensate may accumulate;
l
choking (due to bends or twisting of the hose) can cause excessive back-pressure in the humidifier
cylinder when the unit is operating and consequently sudden steam outlet.
Important:
l
do not install a stop valve in the steam hose;
l
when installation is complete, flush the steam line to remove any contaminants and processing
10
| 2. Preparing for assembly
VRDX030222195 rel. 1.2 – 22.03.2019