24
ENG
“optiMist” +0300065EN- rel. 1.1 - 29/01/2013
W=760 mm
W=608 mm
W= 456 mm
moduli i
n
H
5
4
3
4
5
H= 456
mm
H= 608 mm
H= 760
mm
moduli in W
Fig. 5.c
The following table shows the height and width dimensions available
and the combinations in installable modules
Separators are diff erentiated by:
•
Width
•
Height
They are available in the following heights and widths and number of
standard modules:
WIDTH “W”
MODULES
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
mm
514
666
818
974
1126
1278
1430
1582
1736
1888 2040
2192
2344
2498 2650
2802
2954
3106
no. separators 1
1
1
2
2
2
2
2
3
3
3
3
3
4
4
4
4
4
type separators 1x3
1x4
1x5
2x3
1x3+1x4 2x4
1x4+1x5 2x5
1x3+2x4 3x4
1x3+2x5 1x4+2x5 3x5
4x4
1x5+3x4 3x5+1x3 3x5+1x4 4x5
Tab. 5.a
HIGHT
“W”
MODULES
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
mm
527 679
831 1022 1174
1326
1478
1630
1820
1972
2124
2276
2428
2618
2770
2922
3074
3226
no. separators
1
1
1
2
2
2
2
2
3
3
3
3
3
4
4
4
4
4
type separators
3
4
5
3 + 3 3 + 4
4 + 4
5 + 4
5 + 5 4 + 4 + 3
4 + 4
+ 4
5 + 4 + 4 5 + 5 + 4 5 + 5
+ 5
4 + 4 +
4 +4
5 + 4 + 4
+ 4
5 + 5 + 5
+ 3
5 + 5 + 5
+ 4
5 + 5 + 5
+ 5
Tab. 5.b
There are 324 possible combinations identifi ed by the following coding:
Example: ECDS000710
•
width: 07 (mm1126).
•
height: 10 (mm1630).
Fig. 5.d
Fig. 5.e
In cases where the droplet separator does not exactly cover the section
of the AHU, the free spaces must be closed to prevent the air from
bypassing the droplet separator itself. The necessary plugging materials
is not supplied by Carel.
Flexible or stainless steel pipes are also supplied to connection the
pumping station to the rack.
Please note that the installation of a properly drained droplet collection
tray is always necessary for the rack, the droplet evaporation chamber
and the droplet separator.
The tray is not supplied by CAREL.