10. CONFIGURATION PARAMETERS
To access and set the following parameters, see chapters 8 and 11.
10.1 Basic parameters
Parameter
UM
range
def
note
A0 Operating mode
0 = On/Off mode from auxiliary card probe input
1 = Proportional mode from auxiliary probe input
2 = Humidity probe mode from auxiliary card probe input
3 = if the temperature and humidity probe TH is present, the humidity is read and adjusted; otherwise On/
Off mode from contact on main board. Parameter A2 is not used.
4 = Dew point control mode by reading the temperature and humidity probe TH
-
0...4
3
A1 Unit of measure 0 = International system; 1 = Imperial system
-
0...1
0
A2 Type of external sensor (optional card) (0 = On/Off ; 1 = 0-10V; 2 = 2-10V; 3 = 0-20 mA; 4 = 4-20 mA)
-
0...4
1
P0
Maximum production
%
Pn...100
100
P1
Proportional control hysteresis for mode A0=1
%
2...20
2
Pn Produzione minima
%
5...P0
10
SP
Humidity Setpoint / dew point temperature
(1)
%rH
20...95
50
only if terminal connected, other-
wise values set by dipswitch
°C
(°F)
-16…35
(3…95)
10
(50)
only editable on the terminal
SL
Humidity limit set point / dew point temperature
%rH
0…100
70
°C
(°F)
-16…35
(3…95)
15
(59)
bP Proportional band for control with probe
%rH
2…20
10
°C
(°F)
1…10
(2…20)
3
(5)
bL Proportional band for humidity / dew point temperature limit
%rH
2…20
10
°C
(°F)
1…10
(2…20)
3
(5)
C0 Default display (Terminal)
0 = Probe reading/control signal; 1 = Hour counter
-
0...1
0
Tab. 10.a
10.2 Advanced parameters
Parameter
UM
range
def
note
A3
Probe minimum
%rH
0…100
0
A4
Probe maximum
%rH
0…100
100
A5
Probe offset
%rH
-99…100
0
A6
Fan off delay time
min
0…15
5
A7
Fan speed
%
40…100
100
A8
Maximum evaporation time for reduced production alarm
min
0…200
30
A9
Minimum evaporation time for reduced production alarm
min
0…A8
1
AA
Waiting time for retry
min
1…60
10
Ab
Percentage of A8 to carry out level test
%
50…90
70
AC
Maximum time to measure level when refilling
s
1…60
10
Ad
Maximum time to measure high level
s
1…60
10
AE
Restart fan time in standby for TH probe reading
min
0…120
0
AF
Piezoelectric transducer working life
h
0...9999
9999 with demineralised water
b0
Operating options (see table for parameter b0)
-
0…255
7
b1
Time between two washing cycles
min/h
0…120
60
b2
Inactivity time for washing
h
1…240
24
b3
Washing time (fill + drain)
min
0…10
1
b4
Start delay time
s
0…120
10
b5
Operating hours for CL alarm
h
0…9999(*)
5000
b6
Time to display new CL alarm after reset from keypad (without resetting hour counter)
min
0…240
60
b7
Transducer modulating control period
s
0…10
1
b8
Probe disconnected delay
s
0…200
10
b9
OFF delay from TAM
s
0…60
2
bA
Maximum fill time
min
0…30
2
bb
Water refill time in production
s
0…120
5
bC
Maximum drain time
s
0…1500
60
bd
Drain opening time to completely empty tank
s
0…1500
30
bE
Delay time after measuring low level for refilling
s
1…20
10
bF
Drain activation delay in standby (if drain solenoid valve in standby = OPEN)
min
0…60
0
bH
Enable TH probe as humidity limit (bH=1) or as dew point limit (bH=2)
-
0…2
0
can be set to 1 or 2 only in
modes A0 = 0, 1, 2
bL
Proportional band for humidity / dew point temperature
%rH
2…20
10
°C
(°F)
1…10
(2…20)
3
(5)
bn
Disable alarm buzzer 0 = enabled; 1 = disabled
-
0…1
0
bP
Proportional band for control with probe
%rH
2…20
10
°C
(°F)
1…10
(2…20)
3
(5)
P1
Proportional control hysteresis for mode A0=1
%
2…20
2
P2
Low humidity alarm threshold
%rH
0…100
20
P3
High humidity alarm threshold
%rH
0…100
80
Tab. 10.b
(1)
To be able to modify the value on the terminal, the corresponding dipswitches must all be Off. To be able to use the value set by the dipswitches again, set one of the dipswitches to
On and power off. When powering on again, the controller will use the values set by the dipswitches..
(*)
after 999 the display shows
to indicate the 1000s (the three digits are displayed with a dot at the top between the first and second digit).
Setting the value of parameter b0 in the range from 0 to 255 (default 7) changes the humidifier operating options as regards the following preferences:
1.
Unit of measure of parameter b1 (time between two periodical washing cycles): M = minutes; H = hours;
2.
Backup: ON = if two humiSonic units, the secondary unit becomes the backup unit for the main unit, i.e. it starts production only if the main unit has shut down due to an
alarm; OFF = backup function disabled;
3.
Position of the drain solenoid valve in standby: OPEN = standby empty, the NO valve is not powered and the humidifier tank is emptied; CLOSED = standby full, the NO
valve remains powered, keeping the humidifier tank full during standby;