Carel EASY FREEZE Скачать руководство пользователя страница 2

+050004122 - rel. 1.0 - 19.10.2009

 CAREL INDUSTRIES HQs

Via dell’Industria, 11 - 35020 Brugine - Padova (Italy)
Tel. (+39) 0499716611  –   Fax (+39) 0499716600   –   http://www.carel.com   –   e-mail: [email protected]

CAREL reserves the right to modify the features of its products without prior notice.

Disposal of the product

The appliance (or the product) must be disposed of separately in accordance with the local waste disposal 
legislation in force.

WARNING:

 separate as much as possible the probe and digital input signal cables from the cables carrying 

inductive loads and power cables to avoid possible electromagnetic disturbance. Never run power cables 
(including the electrical panel wiring) and signal cables in the same conduits.

NO POWER 

& SIGNAL 

CABLES 

TOGETHER

READ CAREFULLY IN THE TEXT!

Table of parameters

Parameter

Min. Max. Def. UOM

PS

PASSWORD

0

200

22

-

/

PROBE PARAMETERS

/5

Select °C / °F ( 0 = °C; 1 = °F)

0

1

0

-

/6

Disable decimal point (1 disabled)

0

1

0

-

/C1 Probe calibration

-50.0 50.0 0.0

°C/°F

/C2 Probe 2 calibration

-50.0 50.0 0.0

°C/°F

r

CONTROL PARAMETERS

St

Control temperature

-50.0 90.0 -18.0 °C/°F

rd

Control differential (hysteresis)

0.0

19.0

2.0

°C/°F

c

COMPRESSOR PARAMETERS

c0

Comp. and fan start delay after start-up

0

100

0

min

c1

Min. time between successive comp. starts

0

100

1

min

c4

Compressor safety (duty setting)

0

100

15

min

d

DEFROST PARAMETERS

d0

Type of defrost (0= heater; 1= hot gas; 2= heater by time; 
3= hot gas by time; 4= heater by time with temp. cont.)

0

4

0

-

dI

Interval between two defrosts

0

199

6

h/min

dt

End defrost temperature

50.0 130.0 8

°C/°F

dP

Max. or effective defrost duration

1

199

25

min/s

d4

Defrost when the instrument is switched on (1= activated)

0

1

0

-

d6

Disable temperature display during defrost (1= display disabled)

0

1

1

-

dd

Dripping time after defrost

0

15

1

min

d/

Defrost probe reading

-

-

-

°C/°F

A

ALARM PARAMETERS

A0

Alarm and fan differential

-20.0 20.0

-2.0

°C/°F

AL

Low temperature alarm threshold/deviation (AL= 0; alarm 
disabled)

-50.0 250.0 -50

°C/°F

AH

High temperature alarm threshold/deviation (AH= 0; alarm 
disabled)

-50.0 250.0 50

°C/°F

Ad

Low and high temperature alarm delay

0

199

0

min

F

FAN PARAMETERS 

F0

Fan management: 0= fans on excluding specifi c phases; 
1= fans on according to parameter F1 excluding specifi c phases 

0

1

1

-

F1

Fans shutdown temperature 

50.0 130.0 2

°C/°F

F3

Fans status during defrost: 0= fan ON;  1= fan OFF

0

1

1

-

H

OTHER SETTINGS

H2

Enable keypad
0= keypad disabled
1= keypad enabled
2= keypad enabled except for ON/OFF function

0

2

1

-

EZY restore the Default settings

0

1

0

-

Table of alarms

Alarm 
code

buzzer and 
alarm relay

LED

Description

Parameters involved

E0

active

ON

probe 1 error= control

-

E1

inactive

ON

probe 2 error= defrost

[d0 = 0 / 1]

LO

active

ON

low temperature alarm

[AL] [Ad]

HI

active

ON

high temperature alarm

[AH] [Ad]

EE

inactive

ON

unit parameter error

-

EF

inactive

ON

operating parameter error

-

Ed

inactive

ON

defrost ended by timeout

[dP] [dt] [d4] [A8]

dF

inactive

OFF

defrost running

[d6=0]

How to restore the Default settings (refer to table of parame-
ters in this sheet)

1) Access parameter EZY (entering password 22 and scroll parameter list).
2) Select the desired confi guration:

• EZY = 0         

¼

 No changes;

• EZY = 1         

¼

 Restore of default settings (refer to Table of parameters in this sheet);

3) Exit the setting procedure (holding SET button for more than 3 sec).
4) Power off the device and then power it on again while holding SET button.
5) The display shows “CE” to indicate that the confi guration has been restored.

Switching the device ON/OFF

Press UP for more than 3 s. The control and defrost algorithms are now disabled and the instru-
ment displays the message “OFF” alternating with the temperature read by the set probe.

Manual defrost

Press DOWN for more than 3 s (the defrost starts only if the temperature conditions are valid).

Continuous cycle

Press UP and DOWN together for more than 3 s.

Technical specifi cations

power supply 

230 Vac +10 /-15% 50/60 Hz;

rated power

3,5 VA

inputs NTC 

probes 

relay outputs

16 A relay   UL: 12 A Res. 5 FLA 30 LRA - 240 Vac C300, 
 

    EN60730-1: 12(2) A NO/NC, 10(4) A up to 60 °C NO,  

                   2(2) A CO - 250 Vac
8 A relay      UL: 8 A Res. 2 FLA 12 LRA - 240 Vac C300, 
 

    EN60730-1: 8(4) A NO, 6(4) A NC, 2(2) A CO - 250 Vac

type of probe 

Std CAREL NTC 10 K

Ω

 at 25 °C

connections 

Screw terminals for cables with cross-sect. from 0.5 mm2 to 1.5 mm2
Rated maximum current per terminal 12 A

assembly 

Terminal: using screws from the front panel or with rear brackets 
Interface: wall mounting, 4 screws, spacing 101x151 mm

display

3 digit LED display with sign (-199 to 999) and decimal point; six status LEDs

operating conditions

-10T50 °C - humidity <90% rH non-condensing

storage conditions

-20T70 °C - humidity <90% rH non-condensing

range of measurement

-50T90 °C (-58T194 °F) - resolution 0.1 °C/°F

front panel index of protection

panel installation with IP65 type 1 gasket

case

plastic terminal, 81x36x65 mm

classifi cation according to protection 
against electric shock

Class II when suitably integrated

environmental pollution

normal

PTI of the insulating material

250 V

period of stress across the insulating parts long
category of resistance to heat and fi re

category D (UL94 - V0)

immunity against voltage surges

category 1

type of action and disconnection

1C relay contacts

no. of relay automatic operating cycles 

EN60730-1:  100,000 operations
UL: 

      30,000 operations (250 Vac)

software class and structure

Class A

cleaning the instrument

Only use neutral detergents and water.

cable max. lenght

serial: 1 km
probes: 30 m
relay: 10 m

Note: 

do not run the power cable less than 3 cm from the bottom part of the device or from the 

probes; 

for the connections only use copper wires

Safety standards

compliant with the relevant European standards. Installation precautions:

the connection cables must guarantee insulation up to 90 °C;

• 

for 12 Vac versions use Class II transformers. To ensure compliance with the immunity standards 

• 

(surge), the transformer must be one of the models specifi ed (see the CAREL price list). For the 12 
Vac/dc versions, as double insulation cannot be guaranteed between the power supply and the 
relay outputs, only use safety low voltage loads (up to 42 V effective rated value);
ensure a space of at least 10 mm between the case and the nearby conductive parts;

• 

digital and analogue input connections less than 30 m away; adopt suitable measures for separa-

• 

ting the cables so as to ensure compliance with the immunity standards;

Secure the connection cables of the outputs so as to avoid contact with very low voltage parts.

IMPORTANT WARNINGS

The CAREL product is a state-of-the-art device, whose operation is specifi ed in the technical documentation sup-
plied with the product or can be downloaded, even prior to purchase, from the website www.carel.com.
The customer (manufacturer, developer or installer of the fi nal equipment) accepts all liability and risk relating to 
the confi guration of the product in order to reach the expected results in relation to the specifi c fi nal installation 
and/or equipment. The failure to complete such phase, which is required/indicated in the user manual, may cause 
the fi nal product to malfunction; CAREL accepts no liability in such cases. The customer must use the product 
only in the manner described in the documentation relating to the product. The liability of CAREL in relation to its 
products is specifi ed in the CAREL general contract conditions, available on the website www.carel.com and/or by 
specifi c agreements with customers.