Cabling

Use 4 core, 0.2 mm

2

 (AWG 24) cabling with a maximum, nominal capacitance of

120 pf/m.

Maximum distance between the URI and the Prox 125 reader with this type of cable is
200m (650ft).

Note: You need a special cable terminating tool to connect the building cabling to

the Prox 125. The tool has a head (Part No. C861145) and  handle (Part No.
C861115).

Removing the Facia

To remove the facia from the Prox 125 base you need a T10 Torx driver.

Use the driver to loosen the screw at the bottom of the facia.

Remove the screw.

Gently pull the lower end of the facia away from the base and then slide the facia down
and off the base.

Mounting Distance Between Proximity Readers

The distance between any 2 proximity readers must be greater than 200mm in all
directions.

Note: Please note that 200mm in all directions includes the distance through walls.

200mm

200mm

Содержание Prox 125

Страница 1: ...e equipment are earthed before beginning any servicing Before you Begin Unpack the Prox 125 reader and check the shipment contains the following items 1 x Prox 125 base with printed circuit board PCB...

Страница 2: ...No C861145 and handle Part No C861115 Removing the Facia To remove the facia from the Prox 125 base you need a T10 Torx driver Use the driver to loosen the screw at the bottom of the facia Remove the...

Страница 3: ...ed mounting height for the Prox 125 reader is 1100 mm from floor level to the centre of the reader unit However this may vary in some countries and you should check local regulations for variations to...

Страница 4: ...Ltd REV A B C 22825V2 Assy 22826 5V 12V GND GND IN6 IN5 IN4 OUTPUTS OUTPUTS 5 12V 5 12V DET DET COMMS COMMS GND GND COM COM NO NO NC NC GND GND IN3 IN2 IN1 COMMS P4 Balanced Inputs pin 1 Input1 pin 2...

Страница 5: ...GND BPR LED DET 1 CK 0 DT 5 12V Plug P4 Exit or P5 Entry Universal Reader Interface Red White Blue Black Note Refer to Cardax IV URI Settings later in this Installation Note for the location of the C...

Страница 6: ...o lock as soon as the door is opened Note If you are installing the Prox 125 reader to control a turnstile you should consult the turnstile manufacturer for details of the locking mechanism used Push...

Страница 7: ...F ON OFF Switch On Off 1 1 2 2 3 4 Unit 4 8 Address 5 16 6 32 7 Initialise Normal 8 see note below Switch On Off 1 2 Card Format 3 4 5 6 Validated Exit Normal 7 see note below 8 Keypad No Keypad Depen...

Страница 8: ...cross both pins of connector J2 Connect the Prox 125 reader to the URI Entry Plug P5 Note If you are using two entry readers 2 door software you must connect the second entry reader to URI Plug P4 to...

Страница 9: ...his is a continuous sequence while the URI is unitialised and indicates it is processing The red LED D8 should flash if polls are received from the Commander Note A URI can be initialised without bein...

Страница 10: ...hat interference will not occur in a particularinstallation If this equipment does cause harmful interference to radio or television reception which can be determined by turning the equipment off and...

Отзывы: