Capstone Turbine Corporation
Model C65 Hybrid UPS User’s Manual
Page
56 of 66
400027 Rev A (July 2010)
Capstone reserves the right to change or modify, without notice, the design, specifications, and/or contents of this document without
incurring any obligation either with respect to equipment previously sold or in the process of construction.
Scheduled Maintenance
Table 6 details the preventive maintenance schedules of the C65 Hybrid UPS systems
under normal environmental conditions. This information is provided for your reference.
Only Authorized Service Providers are permitted to access MicroTurbine components and
perform these maintenance tasks.
Table 6. C65 Hybrid UPS package – Gaseous Fuels
Maintenance
Interval
3
Component
Maintenance
Action
Comments
24 months
UCB Battery
Replace
5 years
Electronic
Components: ECM,
LCM & BCM Power
Boards, BCM & ECM
Fan Filters, Fans, EMI
Filter, Frame PM
Replace
Per Mfg
Instructions
External Energy
Storage
Replace
Refer to manufacturer’s requirements for the
energy storage system being used
4,000 hours
Engine Air Filter
Inspect
Replace if required - see Note 1
Electronics Air Filter
Inspect
Clean if necessary - see Note 1
Fuel Filter Element
(External)
Inspect
Replace if required - see Note 1
Fuel System
Leak Check
Refer to "Gaseous Fuel Fittings and
Components" section below for
recommended procedure
8,000 hours
Engine Air Filter
Replace
See Note 1
Electronics Air Filter
Clean
Fuel Filter Element
(External)
Replace
See Note 1
Igniter
Replace
See Note 2
ICHP Actuator
Replace
20,000 hours
Injector Assemblies
Replace
TET Thermocouple
Replace
40,000 hours
Engine
Replace
Use Reman or New Engine Replacement
NOTE 1
Filters may require more frequent attention based upon environment,
installation, and/or air/fuel quality. Inspect new installations frequently to
determine best inspection/ replacement periods for air and fuel filters.
NOTE 2
Load profiles with frequent onloads and offloads may require more frequent
igniter replacement due to igniter operation during injector switching.
NOTE 3
Months and Years are elapsed time. Hours are “Engine Hours,” as recorded by
each Hybrid UPS system.