background image

 

  Cooling system faults.

 

  How to diagnose faults: 

 

It should take approximate 3 hours to reach the lowest setting temperature of 5

  for an empty unit (assuming ambient 

temp of 32 degrees centigrade and continuous operation). If not, check the compressor, cooling fans, controller, and sensors. 

If all these are working normally, there is probably a cooling system

s fault.

 

 

  How to repair the defualt

 

1. Check the compressor 

Turn on the unit and check there is electricity current flowing to the compressor using a caliper type Amp meter, the 

current should be within 0.6 to 2 Amps.  If the readings are not in this range, turn  off and cut off the pipes 

(See Fig.20 

showing  G)

  and the seal pliers

 (See  Fig.20showing E.) 

from the  compressor, then turn the unit on  again (

in  this  case 

only  run  the  compressor  for  a  few  minuets,  so  as  to  avoid  the  compressor  absorb  moist  air

)  and  recheck  the 

current  and  if  there  is  pressure  at  the  outlet  pipe.  If  the  current  reading  is  still  out  of  range  specified  above  and  no 

pressure from the compressor outlet, replace the whole compressor. 

 

2.

 Check the cooling system pipe work: 

Carefully  check  the  cooling  system  after  verifying  the  compressor  is  working  normally.  Then  follow  the  procedure 

below. 

1>.

  Then  cut  off  process  pipe  and  check  the  refrigerant.  If  there  is  not  enough  refrigerant,  the  defualt  of  the  refrigerant 

system should be caused by the leaking. If the refrigerant is sufficient., it is probably jamed in the capillary.   

 

2>.If the default is concentrated on the cooling system, the checking procedure is as below. 

A. Cut off the vent pipe of the compressor, and infuse 0.8-1MP nitrogen by 

process pipe

, and please put the hand close 

to the cut kerf of the vent pipe. If there is a little gas leak form the terminal, it means normal, or it is jamed. 

 

B.  Make  sure  the  capilary  is  working  normally,  when  the  drainpipe  is  connetced  again,  and  infuse  0.8-1MP nitrogen 

then  test  the  leakage  if  the  cooling  system  of  the  soldering  point  with  the  soap  water.  Check  from  the  the  soldering 

point arround the  compressor

(Fig.20& Fig.21, Fig.21.1)

, and if  everything is ok, remove  the  air-duct board and 

chech the soldering point around evaporator. please see the remove method and the procedure as below

(

4

)

.

 

C. If all the soldering point in B is not leaking, there are two possibility, one is leakage in the inner condenser, another 

is the damage on the parts

such as evaporator,condenser and so on

  in the cooling system. If it is the inner damage, it 

can not be repaired, and if the damage on the parts, replace them. 

3>. Make sure that there is not leakage in the cooling system, refill the refrigerant. 

 

3. Refill the refrigerant: 

1>. Using the vacuum pump form a vacuum in the system, via the joint of the low-pressure process pipe on the compressor , 

the high-pressure pipeline is on the process pipe of the filter. Apply the vacuum pump for approximately 20 minutes. Until 

the  vacuum  is  lower  than  100Pa.  Then  solder  the  compressor  process  pipe  of  the  filter.  Keep  the  vacuum  running  while 

soldering this joint 

2>.

Fill  Cooling  system  with  refrigerant  via  the  process  pipe.  (The  refrigerant  is  R134a.  Regarding  refrigerant  quantity 

Please  refer  to  the  instruction  at  back  label  of  wine  cellar).  Then  solder  the  compressor  process  pipe  after  the  system  is 

charged with refrigerant. 

 

 

4. Running test: 

 

Replace all the components after the procedures above and turn the unit on. To verify the effectiveness of the repair, monitor   

Содержание WI6128WH

Страница 1: ...WI6128WH Caple 60cm 2 zone wine cabinet Caple 60cm 2 zone wine cabinet Technical information...

Страница 2: ......

Страница 3: ...r 1 20 DG13 198 Senser cover 2 21 DG22 421 Upper panel for middle airway board 1 22 DG7 3 1 BH Evaporator fan1 1 23 DG7 3 1 BH Evaporator fan2 1 24 DG18 76 Foam 1 25 DG22 303 Lower panel for middle ai...

Страница 4: ...G12 91 Condenser 1 44 DG12 6 1 Air circulating pipe 1 45 DG22 80 Compressor bracket 1 46 DG14 56 Bracket of fan pair 1 47 DG13 1 Water tank 1 48 DG11 45 Drier 1 A DG14 190 SL Top left hinge 1 B DG14 2...

Страница 5: ......

Страница 6: ...WI6128WH Caple dual zone wine cabinet Caple dual zone wine cabinet Service Manual...

Страница 7: ...e attempting any cleaning or maintenance this unit MUST be disconnected from the electrical supply to prevent electrical shock Preparation before maintenance Tools 1 Pliers 2 Phillips head screwdriver...

Страница 8: ...porator freezing problems Page 15 Unstable internal Temperature Page 16 Control system problems Fault finding by the self check mode Page 16 Sensor fault Page 17 How to replace the sensor Page 17 LED...

Страница 9: ...ogen by process pipe and please put the hand close to the cut kerf of the vent pipe If there is a little gas leak form the terminal it means normal or it is jamed B Make sure the capilary is working n...

Страница 10: ...is empty How to remove the air duct board 1 Remove the shelves firstly and there is two method below a Remove the shelves some models have Phillips head screws to hold other models have no screws Fig...

Страница 11: ...3 Fig 3 1 d Pull the shelves to the bottom circumvolve any side of the right and left and let the setter of the shelve go out of the channel and then draw out the shelves Fig 4 Fig 4 2 How to remove t...

Страница 12: ...ard If there is any similar situation use the same method Fig 5 b Pull out electric box to expose the control panel as per the direction of arrowhead then unplug all the connectors from the control pa...

Страница 13: ...nt F1 red 4 To the sensor of the freezing compartment X1 yellow 5 To the sensor of the refrigeration compartment X10 White 6 To the sensor of the evaporator X11 Red 7 To the power supply L N 8 To the...

Страница 14: ...g 9 Fig 9 The new structure electrical removement a Remove the shelves then remove the fixing screws 2 3 The right diagram shows the box for clarity only See Fig 10 Fig 10 b Remove the the upper cover...

Страница 15: ...movement in this version PCB board is devide into 2 blocks one is power PCB the other is control PCB a Remove the shelves then remove the fixing screws 1 2 3 4 Fig 13 Fig 13 b Remove the the upper cov...

Страница 16: ...rtment Yellow 10 To the fan of the freezing compartment Red c Remove the fixing screws 5 6 then pull out electric box C to expose the air duct board Fig 16 Fig 16 3 How to remove the air duct board A...

Страница 17: ...d 1 2 3 4 5 6 then pull out air duct board A See Fig 18 Fig 18 4 For a View of the internal configuration after removal of the air duct board see Fig 1 Front side joints location See Fig 19 A Capillar...

Страница 18: ...1 Fig 21 1 B Dry filter process pipe soldered joint C Dry filter soldered joint D Capillary soldered joint E Process pipe soldered joint F Suction pipe soldered joint G Discharge pipe soldered joint H...

Страница 19: ...f wine cellar compressor noise 1 The working of motor and piston motion will cause noise when compressor working So if noise is steady and not exceeds 42 dB it s normal If noise is not steady or very...

Страница 20: ...4 and remove the air cycling fan and replace with a new one Fig 23 Fig 23 3 Regarding the old version eletrical box remove middle air duct board lower cover Fig 9 and remove the screw 1 2 3 4 replace...

Страница 21: ...l the fan installing position are different but the replace methods almost same Fig 26 4 Remove the 4 fixing screw of the fans with the Phillips head screwdrivers 3 4 5 6 replace the fan Fig 26 1 Fig...

Страница 22: ...e capillary Caused by Compressor oil flowing into the cooling system pipe work because of wine cooler lean during transportation and the jetting oil in the capillary cause noise Solutions Clean the co...

Страница 23: ...s and the RUN indicator light are on all the time d If the cooler has condenser and evaporator fans they should work at full speed Heater and air cycling fans should work for 30 seconds alternately e...

Страница 24: ...nsors 1 Evaporator sensor there are two different position a and b of the evaporator sensor a One is that the evaporator sensor is plugged into the fin of evaporator Remove the air duct board to acces...

Страница 25: ...r remove the air duct board page 6 and take off the fixing screw 1 and take off the sensor and unplug another terminal s from socket X1 Fig 7 in the PCB board and replace the sensor with the same mode...

Страница 26: ...he transformer Fig 7 model 2 PCB board divide into 2 blocks the main PCB board is in the electrical box Fig 15 the other power PCB board is in the left of the compressor s box with the transformer Fig...

Страница 27: ...aw the PCB board and draw off the PCB board C replace it with the same model s PCB board Fig 33 c Remove two fixing screw of the transformer take off the tranformer D for replacement Fig 33 d How to r...

Страница 28: ...e connector press the 4 studs 3 one by one Updraw the control PCB board and draw off the PCB board replace it with the same model s PCB board Fig 34 Fig 34 B How to replace the power PCB and transform...

Страница 29: ...ter fan connector Red 3 To control PCB White 4 Compressor connecter 5 Connectors of the power N 6 Connector of power L 7 Transformer secondary connector 8 Transformer primary connector How to replace...

Страница 30: ...place the LED light A How to replace the LED light in upper zone Fig 39 a Remove the shelves Fig 1 b Remove the screws 7 fixing light cover B c Remove the screw 8 in the center of the light cover disc...

Страница 31: ...ght upward replace it Fig 34 How to replace the decorative frame Remove the screw 1 2 3 pull the decorative frame according to the arrowhead that view K show then remove the screw 4 5 6 from the gap b...

Отзывы: