Cantec Systems CHFC-1 Скачать руководство пользователя страница 9

 

 

 

 

 General

 

Description 

Symbol 

Test Condition 

Value and/or 

Range 

Unit 

Operating range of temperature 

from -20 to 

+50 

°C 

Maximum relative humidity 

RH 

90% 

Switching frequency 

f

c

 

50 ± 5% 

kHz 

Efficiency 

η 

At each operation 
condition 

> 85% 

Maximum size 

a×b×c 

Without connecting cable 

300×160×80 

mm 

Weight 

Without connecting cable 

2,2 

kg 

Enclosure class 

IP20 

 

Protection and Safety

 

Description 

Symbol 

Test Condition 

Value and/or 

Range 

Unit 

Insulation 

Mains to Battery side 

1250 

V

AC

 

Insulation 

Mains side to Earth 

500 

V

DC

 

Insulation 

Battery side to Earth 

500 

V

DC

 

Leakage current 

I

L

 

Supplied equipment 

< 3 

mA 

Input fuse 

F1 

Inside the equipment 

20 

Output fuse 

F2 

Inside the equipment 

40

Minimum output voltage of operation 
(Battery Detector) 

Equipment turn on 

1,5 

V/cell 

Maximum output voltage 

Um 

Phase 3 (IUIa - IUIUo) 

See curve 

Reverse output polarity 

At the connection to the 
Battery 

Protection 

provided by 

fuse F2 

Thermal protection of semiconductors 
(Temperature of Thermal Alarm) 

- Ta=55°C 

100 

°C 

Safety Requirements (Rules) 

EN60335-1, EN60335-2-29

 

- - 

EMC Requirements (Rules) 

EN55014-1, EN61000-3-3 
EN55014-2, EN61000-4-2 
EN61000-4-4, EN61000-4-5 
EN61000-4-6, EN61000-4-11 

- - 

 

Battery charger CHFC-1 

  

Your Power Solutions Specialists

OTTAWA

Tel: 613-725-3704

Fax:  613-725-0490

TORONTO:

Tel: 613-725-3704

Fax:  613-725-0490

VANCOUVER:

Tel: 604-736-4922

Fax:  604-736-1074

A DIVISION OF CANTEC REPRESENTATIVES

1573 LAPERRIERE AVENUE OTTAWA ON  1Z 7T3

Содержание CHFC-1

Страница 1: ...Installation and User Manual Your Power Solutions Specialists CHFC 1 HIGH FREQUENCY BATTERY CHARGER...

Страница 2: ...presence of uninsulated dangerous voltage within the equipment s enclosure that may be of sufficient magnitude to constitute a risk of electric shock to persons The exclamation point within an equilat...

Страница 3: ...adapter to defeat the earthing To avoid damaging the power cord do not put anything on it or place it where it will be walked on If the cord becomes damaged or frayed replace it immediately If you ar...

Страница 4: ...tion for the SMPS Switching Mode Power Supply at high power This solution gives a good performance for minimum costs and physical dimensions using switches more faster and powerful modern technology T...

Страница 5: ...ttery capacity Audible message RED YELLOW flash Battery Current Loss of output Current control Failure of the control logic Audible message RED GREEN flash Battery Voltage Loss of output Voltage contr...

Страница 6: ...of elements The number of elements is calculated by dividing the nominal tension of the battery for the tension of each single element in the table Capacity It is the quantity of electric charge that...

Страница 7: ...Mechanical dimensions N B All dimensions are expressed in mm Drilling details UP Advised Installation N B All dimensions are expressed in mm 275 300 9 155 16 80 6 3 160 78 245 300 Battery charger CHFC...

Страница 8: ...max 1 kW Battery side Description Symbol Test Condition Value and or Range Unit Output current I See curve Maximum output current I1 Phase 1 See curve A Output current ripple I I1 5 Absorbed current I...

Страница 9: ...Inside the equipment 20 A Output fuse F2 Inside the equipment 40 A Minimum output voltage of operation Battery Detector Equipment turn on 1 5 V cell Maximum output voltage Um Phase 3 IUIa IUIUo See cu...

Отзывы: