A file named SysInf.txt is also present. This file contains critical information if
debugging is required. If this file is not present it is recommended that the
controller be updated with the latest firmware.
DEFAULT FACTORY STATIC IP CONFIGURATION
If you don’t have a USB flash drive then follow the steps below to temporary set the
controller to the default factory static IP address of 10.0.0.101
1.
Temporarily remove tamper jumper, TAMPER = OPEN.
2.
Press and hold the IP RESET PB2 button.
3.
After approximately 3-5 seconds the Webster 64 controller will emit a continuous
beep. Release the IP RESET PB2 button.
4.
The Webster 64 controller will be reset and reboot with a default factory static IP
address of 10.0.0.101.
5.
Insert the tamper jumper, TAMPER = SHORTED.
Note
:
If this is not done, on the
next IP reset the controller will always return to the default factory static IP address of
10.0.0.101
.
6.
Insert one end of your Ethernet cable (RJ45) to your computer and the other end of
the cable to the Webster 64 controller.
7.
Right click on the network icon from the Notifications Area at the bottom right
corner of your screen and select Open Network & Internet settings
Содержание Webster 64
Страница 1: ...Webster 64 Controller INSTALLATION MANUAL September 2023...
Страница 13: ...Webster 64 Page 13 of 32 Installation Manual February 2024 Rev 1 1 Figure 6 Non Supervised...
Страница 14: ...Webster 64 Page 14 of 32 Installation Manual February 2024 Rev 1 1 Figure 7 Supervised...
Страница 32: ...Webster 64 Page 32 of 32 Installation Manual February 2024 Rev 1 1...