MAP2 

Page 21 of 32 

 

Installation Manual 

September 2020 • Rev. 1.5 

Note 2:

 

6 Amp Relay Rating 

 

Maximum current that can be switched reliably when connected to a ‘non-inductive load’ up to 
30VDC. Electric strikes and magnetic locks are considered ‘inductive loads’. It is important to 
have diode or MOV attached at the locking device to remove the CEMF pulse that is generated 
when switching an ‘inductive load’. It is advisable to use a 50% switch factor or 3 amps as the 
maximum switching current for longer relay life. An external relay should be used on larger 
voltage and current requirements

 

 

MAP2 SYSTEM INDICATORS 

 

12VDC POWER LED

: ON indicates 12 volts DC is connected. 

First Access Mode

 

Mode indicator: MAP2 emits 1 beep after powered up. 

CloudACS Mode

 

Mode indicator: MAP2 emits 3 beeps after powered up. 

BD STAT LED

: Flashing RED – IOM (Input Output Module) is in normal operation.  

STAT LED

:   

 

Flashing GREEN – PLM (Panel Logic Module) is waiting for a connection from 
the host via Ethernet.   

 

Steady GREEN – PLM (Panel Logic Module) is connected to a host via 
Ethernet. 
 
 

IMPORTANT:

 In some jurisdictions, the use of a UL approved power supply and 

connection to the fire alarm system for emergency release may be required. Installers 
should contact the local authority having jurisdiction to verify the specific 
requirements. Also, a building permit may be required in some jurisdictions for the 
installation of magnetic locks.

 

Содержание MAP2

Страница 1: ...MAP2 Controller INSTALLATION MANUAL September 2020...

Страница 2: ...Contact Wiring 12 Lock Output and Multi Function Relay Wiring 15 Input and Output Point Wiring 17 Appendix 20 MAP2 System Indicators 21 Power Connector 22 SHDN Shutdown Button 23 IP Address Reset and...

Страница 3: ...ty of the general purpose Input and Output points depends on the number of doors provisioned for the controller The MAP2 controller also supports elevator configurations The MAP2 allows for 100 000 in...

Страница 4: ...ity readers with 100 mA each 12VDC 1 5A Temperature Range Operating 0 C to 60 C Storage without lithium battery 40 C to 105 C Relative Humidity Operating 20 to 80 Auto Resettable Fuses MAP2 Main 12V D...

Страница 5: ...ax Length NOTE Consult reader specifications as 12 gauge wire may be required for power Dimensions Weight MAP2 Controller 7 L x 7 W 18 cm L x 18 cm W MAP2 Enclosure 13 W x 19 H x 3 5 8 D 33 cm W x 48...

Страница 6: ...lines creating misreads This Wiegand misread issue is more evident on longer Wiegand reader cables The reader cable may have to be replaced with the correct type of Wiegand reader cable to improve sys...

Страница 7: ...MAP2 Page 7 of 32 Installation Manual September 2020 Rev 1 5 MAP2 Controller Layout Figure 1...

Страница 8: ...output points c 6 door configuration 6 lock relays 6 multi function relays 6 REX RET 6 door contacts DPS 2 general purpose input points and 2 general purpose output points d 8 door configuration 8 lo...

Страница 9: ...ler is set to acquire an IP address automatically DHCP However it can be optionally set to a static IP address or reset if necessary See Appendix section for more information Mechanical Information 1...

Страница 10: ...ontroller and a separate power supply which can be sized to supply the amount of current that the attached high current devices locks will require Figure 5 Mode Indicator After a complete power up the...

Страница 11: ...1 of 32 Installation Manual September 2020 Rev 1 5 ENTRY READER WIRING The following diagram shows entry reader wiring only For entry and optional exit reader wiring diagram proceed to the next sectio...

Страница 12: ...4 uses Input 7 Door Contact DPS and Input 8 RTE REX Reader 5 uses Input 9 Door Contact DPS and Input 10 RTE REX Reader 6 uses Input 11 Door Contact DPS and Input 12 RTE REX Reader 7 uses Input 13 Door...

Страница 13: ...MAP2 Page 13 of 32 Installation Manual September 2020 Rev 1 5 Figure 8 Non Supervised The RTE REX can be set to Normally Open or Normally Closed from the host software...

Страница 14: ...MAP2 Page 14 of 32 Installation Manual September 2020 Rev 1 5 Figure 9 Supervised The RTE REX can be set to Normally Open or Normally Closed from the host software...

Страница 15: ...one of the following options Alarm Shunt factory default Shunt the alarm system before opening lock Door Held Open Door has been left open Forced Entry Door opened without access granted or exit butt...

Страница 16: ...sdiction to verify the specific requirements Also a building permit may be required in some jurisdictions for the installation of magnetic locks Figure 11 See Note 2 in Appendix section for 6 Amp rela...

Страница 17: ...Manual September 2020 Rev 1 5 INPUT AND OUTPUT POINT WIRING General Layout The MAP2 can be provisioned for all I O which allows for 16 input points and 16 output points to be used There is no door pro...

Страница 18: ...uire a Cansec CA EOL resistor pack to be placed at the device being monitored Supervised input points will inform the host of 4 supervised states Alarm Secure Trouble High and Trouble Low These are th...

Страница 19: ...MAP2 Page 19 of 32 Installation Manual September 2020 Rev 1 5 Output Wiring Figure 14...

Страница 20: ...AH batteries 13 5 x 13 x 3 25 342 9mm x 330 2mm x 82 55mm 6 65 lbs 3 02 kg 12 24 VDC selectable output 6 Amp Enclosure Style Power Supply with Backup Battery Charger Eight individual Class 2 rated pow...

Страница 21: ...NDICATORS 12VDC POWER LED ON indicates 12 volts DC is connected First Access Mode Mode indicator MAP2 emits 1 beep after powered up CloudACS Mode Mode indicator MAP2 emits 3 beeps after powered up BD...

Страница 22: ...CTOR Connections TAMPER allows for the connection of an Enclosure Tamper Switch Figure 15 Factory default The Tamper jumper is set to disabled To activate the Panel Tamper move jumper to the top 2 pin...

Страница 23: ...not occur try the procedure again If it still does not respond correctly as described above a system fault has occurred It will be necessary to unplug the power connector and re insert it after 10 se...

Страница 24: ...ng green along with a short series of beeps 1 or 3 beeps to indicate its respective provisioned mode First Access or CloudACS 4 Plug the MAP2 to the network with a DHCP server available 5 Install and...

Страница 25: ...Host IP see Figure 21 instructs the panel to accept data connection only from the host computer where the First Access software is installed Other connections for diagnosis and updating are not limite...

Страница 26: ...ON TOOL 1 If the MAP2 controller is already powered off then proceed to step 3 Otherwise press and hold the SHDN button until the STAT LED on the module begins flashing rapidly then release the shutdo...

Страница 27: ...l emit a series of beeps 1 beep or 3 beeps to indicate its provisioned mode First Access or CloudACS respectively 5 Remove the USB flash drive from the MAP2 controller 6 Insert the flash drive into a...

Страница 28: ...omputer is connected to SrvPort 5000 Factory default server port You may change it or leave it as default DiagPort 5001 Factory default diagnostic port You may change it or leave it as default UpdateP...

Страница 29: ...ly Remove the line USB INIT DONE and save the file before removing it from your computer 9 Repeat from step 1 to step 6 then proceed to step 10 10 Insert the flash drive into a USB port on a computer...

Страница 30: ...it button event A message will be transmitted to the host software if the panel is online DOOR HELD OPEN OUTPUT The MF multifunction relay when configured as Door Held Open will be activated if the lo...

Страница 31: ...ARDS ONLY The MF multifunction relay when configured as Door Operator_HC will only be activated by cards designated as handicap and by exit button press The lock relay will be activated first followed...

Страница 32: ...MAP2 Page 32 of 32 Installation Manual September 2020 Rev 1 5...

Отзывы: