Page 21 of 32
Installation Manual
September 2020 • Rev. 1.5
Note 2:
6 Amp Relay Rating
Maximum current that can be switched reliably when connected to a ‘non-inductive load’ up to
30VDC. Electric strikes and magnetic locks are considered ‘inductive loads’. It is important to
have diode or MOV attached at the locking device to remove the CEMF pulse that is generated
when switching an ‘inductive load’. It is advisable to use a 50% switch factor or 3 amps as the
maximum switching current for longer relay life. An external relay should be used on larger
voltage and current requirements
.
MAP2 SYSTEM INDICATORS
12VDC POWER LED
: ON indicates 12 volts DC is connected.
First Access Mode
:
Mode indicator: MAP2 emits 1 beep after powered up.
CloudACS Mode
:
Mode indicator: MAP2 emits 3 beeps after powered up.
BD STAT LED
: Flashing RED – IOM (Input Output Module) is in normal operation.
STAT LED
:
Flashing GREEN – PLM (Panel Logic Module) is waiting for a connection from
the host via Ethernet.
Steady GREEN – PLM (Panel Logic Module) is connected to a host via
Ethernet.
IMPORTANT:
In some jurisdictions, the use of a UL approved power supply and
connection to the fire alarm system for emergency release may be required. Installers
should contact the local authority having jurisdiction to verify the specific
requirements. Also, a building permit may be required in some jurisdictions for the
installation of magnetic locks.
Содержание MAP2
Страница 1: ...MAP2 Controller INSTALLATION MANUAL September 2020...
Страница 7: ...MAP2 Page 7 of 32 Installation Manual September 2020 Rev 1 5 MAP2 Controller Layout Figure 1...
Страница 19: ...MAP2 Page 19 of 32 Installation Manual September 2020 Rev 1 5 Output Wiring Figure 14...
Страница 32: ...MAP2 Page 32 of 32 Installation Manual September 2020 Rev 1 5...