6-10KVA Rack-mount UPS User Manual Production Specification and Performance
9
3. Operating Environment
Temperature
Humidity
Altitude
Storage temperature
0
°
C-40
°
C <95%
<1000m 0
°
C-70
°
C
NOTE
:
If the UPS is installed or used in a place where the altitude is above than 1000m, the
output power must be derated in use, please refer to the following:
Altitude (M)
1000
1500
2000
2500
3000
3500
4000
4500
5000
Derating Power 100% 95%
91%
86%
82%
78%
74%
70%
67%
±
1% 0.9
lag
±
0.1% of
normal
THD<1%
Full load
(Linear
Load)
110% load: transfers to
Bypass mode after 10
minutes
130% load: transfers to
Bypass mode after 1 min.
150% load :transfers to
Bypass mode after 30
seconds and shutdown the
output after 1 minute
3:1
maximum