Setting list
MRN3
Project:
CSPC Job No.:
Function group: =
Location: +
Relay code:
Relay functions:
Password:
Setting of the parameters
System parameter
Relay type
Default
Actual
settings
settings
Function
Unit
MRN3-1 MRN3-2
Set1/Set2
Set1/Set2
Uprim/Usek Voltage transformer ratio
X
X
SEK
Δ
/Y
Input voltage correction dependent
X
X
Y
connection of the input transformer
f
N
Rated frequency
Hz
X
X
v = 50 Hz
LED Flash
Display of theactivation storage
X
X
FLSH
P2
2 parameter sets/ext. Trigger for FR
X
X
SET1
Protection parameter
Function
Unit
Default
Actual
settings
settings
U<
pickup value for undervoltage element (low set)
V
90/210/360*
t
U
<
tripping delay for undervoltage element
s
0.04
U<<
pickup value for undervoltage element (high set)
V
80/190/320*
t
U
<<
tripping delay for undervoltage element
s
0.04
U>
pickup value for overvoltage element (low set)
V
110/250/440*
t
U
>
tripping delay for overvoltage element
s
0.04
U>>
pickup value for overvoltage element (high set)
V
120/270/480*
t
U
>>
tripping delay for overvoltage element
s
0.04
T
frequency measuring repetition in periods
cycles
4
f
1
pickup value for frequency element 1
Hz
4800
t
f1
tripping delay for frequency element 1
s
0.1
f
2
pickup value for frequency element 2
Hz
4900
t
f2
tripping delay for frequency element 2
s
0.1
f
3
pickup value for frequency element 3
Hz
5100
t
f3
tripping delay for frequency element 3
s
0.1
df
pickup value for rate of frequency (dt/dt) in
Hz/s
EXIT
dt
measuring repetition for df/dt
periods
2
1/3
vector surge tripping logic
1PH
ΔΘ
pickup value for vector surge
°
2.0
U
B
<
voltage threshold value for frequency and vector
V
10/23/40*
surge measuring (or df/dt)
RS
Slave address of the serial interface
1
RS**
Baud-Rate
9600
RS**
Parity-Check
even
* thresholds dependent on rated voltage 100 V / 230 V / 400 V
** only Modbus