background image

Trouble Shooting Points

F u n c t i o n a l   Te s t 
doesn't executing

No Fault pickup

or

Wrong Fault pickup

Accuracy  not  within 
band

Battery  voltage  not 
available
          or 
B a t t e r y   s e a l   n o t 
removed
           or
Voltage  too  low  or 
fault existing.

Sensor  wires  not 
screwed properly  
        .
         or

Setting not as per the 
current

Pickup  not  working 
as per defined band

1)  Try  reinserting  the 
battery  by  opening  the 
front cover and check. if 
not  solved,  replace  the 
battery.
2)  Check  whether  fault  
current exists, if so, It will 
prevent  the  functional 
test.
3)  Remove  the  battery 
seal before installing the 
product.

1)  Check  the  pickup/ 
response time setting.

2) Check the sensor wire 
connection  to  the  FPI 
indication unit.

3)  Check  the  sensor 
f i t t i n g   w i t h   c a b l e s . 
Locking screw should be 
tighten on cable.

4) Check the cable dia as 
per the sensor chosen.

1)  Fixing  Screw  of  the 
clamp  of    sensor  not 
tighten properly.

2) Check the cable dia as 
per the sensor chosen.

3) S.No.of sensor should 
match  with  the  S.No.  of 
indicator.

Cause of Problem

Problem

Remedy

15

Содержание CSFPI-C13

Страница 1: ...0191 CSFPI C13 Short Circuit Earth Fault Passage Indicator This QRG will help you step by step installation operation and programming procedure Please go through all the instructions carefully prior t...

Страница 2: ...that the current sensor is installed at earth potential on the HV cable system Ensure that the current sensor is installed on screened part of the cable system Sensor should be installed on shielded...

Страница 3: ...Sensor must be mounted on screened cable and can be retrofitted on the cable l Programmable Short circuit pickup level wide range 100A to 1200A l Programmable Earth fault pickup level wide range 10A t...

Страница 4: ...y Screw BATTERY L3 E L2 RST FN CHK BATT CHK L1 CSFPI Battery 3 DIP Switches for Programmed Parameter settings Accessible only after opening the Front Plate Dip Switch 1 Dip Switch 2 Dip Switch 3 Screw...

Страница 5: ...ON 3 5 ON ON OFF 4 ON ON ON 5 x Don t Care Not in Use ON 1 2 3 4 ON ON 1 1 3 3 2 2 6 6 5 5 4 4 Short Circuit Pickup Amp Earth Fault Pickup Amp Short Circuit Response Time s OFF OFF OFF 10 OFF OFF ON 2...

Страница 6: ...eight 45 0 mm Dimension Details FRONT VIEW OF PHASE EARTH FAULT INDICATOR TOP VIEW All the dimensions are in mm Gen Tol 1 0mm BATTERY L3 E L2 RST FN CHK BATT CHK SHORT EARTH FAULT INDICATOR L1 CSFPI 5...

Страница 7: ...Side Back View of the Relay SIDE VIEW BACK VIEW 43 5 mm 51 0 mm 12 13 14 15 16 17 18 9 10 11 VOLTAGE RESET 8 7 6 5 4 3 2 1 E L3 L2 L1 DO REMOTE RESET 97 8 mm 07...

Страница 8: ...Connection Diagram CSFPI E B x CSFPI E C x RESET 230VAC RESET 230VAC L N L N CAUTION Remote Reset Signal requires 200msec pulse Continuous signal can reduce battery life 08...

Страница 9: ...gram CSFPI E D x CSFPI E G x RESET 230VAC REMOTE RESET Potential Free RESET 230VAC REMOTE RESET Potential Free L N L N CAUTION Remote Reset Signal requires 200msec pulse Continuous signal can reduce b...

Страница 10: ...tion on the cable by locking the screw on the back of the steel bracket in case of short circuit sensor or by clamping it with the help of a cable tie for earth sensor The FPI indicator unit is for pa...

Страница 11: ...Locking Screw Short Circuit Sensor Earth Sensor Fixing Screw Fixing Screw Cable Tie Terminal Connector 12 13 14 15 16 17 18 9 10 11 VOLTAGE RESET 8 7 6 5 4 3 2 1 E L3 L2 L1 DO REMOTE RESET 11...

Страница 12: ...for panel installation Indication of a Short Circuit a One Red LED for each Phase b Earth Fault b One Red LED for Earth Fault c Battery c One Yellow LED for Battery Status Reset of the Indicator a Ma...

Страница 13: ...Max Switching Voltage 220V DC 250V AC Short Circuit Sensor CT Three Short Circuit SensorsType CS x PS x x forThree Core Cable One Sensor for each core Diameter various option available Based on orderi...

Страница 14: ...Short Circuit Sensor Type CS x PS x x Earth Fault Sensor Type CS x ES x x d Sensor cable length will be based on Sensor ordering information Refer catalogue d d 14...

Страница 15: ...k if not solved replace the battery 2 Check whether fault current exists if so It will prevent the functional test 3 Remove the battery seal before installing the product 1 Check the pickup response t...

Страница 16: ...to change the design or specification contained in this catalog without prior notice content C 60 Wing A Phase II Noida 201 305 Dist Gautam Budh Nagar U P INDIA Phone 91 120 38748 00 01 C S Electric...