Front Interface of the Relay

(For CSENEX-I 201 Model)

 

R

I

CSEN

EX

TRIP

PICKUP

L

1

L 2

L 3

BLOCK

E

BF/TCS

F1

CLOSE

OPEN

C
O
N
T
R
O
L

U R R E N T 

C

R O T E C T I O N

P

E L A Y

R

Key operation 
indication LEDs

Scroll / Edit key

Power On LED

(Relay  ready  for  operation)
* It must glow otherwise check
the trouble shooting tips on last
page

LCD

Assignable function key
F1: (DO1...DO4) DO Reset

CLOSE: CB Close key
            on assigned DO  

OPEN: CB Open key
           on assigned DO  

Intelligent  Key  for 
direct  access  to 
fault status, pickup
status, DI status &
DO status

Scroll / Edit key

Enter key

BLOCK: indicates 
protection blocking
based on DI

BF/TCS:  indicates the
Circuit Breaker failure
or Trip Circuit failure

E: indicates the

fault in earth

L3: indicates the 
fault in L3 phase

L1: indicates the 
fault in L1 phase

L2: indicates the 
fault in L2 phase

TRIP: trip on fault

PICKUP: pickup
               in fault

LED

USB  for  Front 
Communication
with Laptop/PC

Fault Reset key

(For CSENEX-I 202 Model)

Front Interface of the Relay

 

R

I

CSEN

EX

TRIP

PICKUP

L

1

L 2

L 3

AR

E

BF/TCS

F1

CLOSE

OPEN

C
O
N
T
R
O
L

U R R E N T 

C

R O T E C T I O N

P

E L A Y

R

USB  for  Front 
Communication
with Laptop/PC

Key operation 
indication LEDs

Scroll / Edit key

Fault Reset key

Power On LED

(Relay  ready  for  operation)
* It must glow otherwise check
the trouble shooting tips on last
page

LCD

Assignable function key
F1: (DO1...DO4) DO Reset

CLOSE: CB Close key
            on assigned DO  

OPEN: CB Open key
           on assigned DO  

BF/TCS:  indicates the
Circuit Breaker failure
or Trip Circuit failure

E: indicates the 
fault in earth

L3: indicates the 
fault in L3 phase

L1: indicates the 
fault in L1 phase

L2: indicates the 
fault in L2 phase

TRIP: trip on fault

LED

AR:  indicates  the
Auto Recloser status

PICKUP: pickup
               in fault

Intelligent  Key  for 
direct  access  to 
fault status, pickup
status, DI status &
DO status

Scroll / Edit key

Enter key

 

R

U R R E N T 

C

R O T E C T I O N

P

E L A Y

R

I

F1

CLOSE

OPEN

TRIP

PICKUP

L

1

L 2

L 3

BLOCK

E

C
O
N
T
R
O
L

BF/TCS

CSEN

EX-

I

Dimension Details

Side View

Front View

158.5

112.0

Panel cutout 

Dimensions

145.0

125.0

154.0

CSENEX-I  relay is available in a plastic case for panel or flush mounting
Weight :  Approx. 1.0 Kg (without cables) (All the dim. are in mm)

Connection Diagram

of 201 model

A1 

Auxiliary Supply Earth

A2-A3 

Auxiliary Supply - (A3) , + (A2)

A4-A5 

RS-485 Modbus N1(A4), P1(A5)

A9-A10 

Potential free Digital Output 4

A11-A12 

Potential free Digital Output 3

A13-A14-A15 

Potential free Digital Output 2

A16 -A17- A18 

Potential free Digital Output 1

D2-D3 

Potential Digital Input 1

D5-D6 

Potential Digital Input 2

D7-D8 

Potential Digital Input 3

D9-D10 

Potential Digital Input 4

E1-E6 

CT Terminal for Phase current input

 

 

L1(E1-E2), L2(E3-E4),L3(E5-E6)

E7-E8 

CT Terminal for Earth current input

Terminal Name

Terminal Description

L1

L2

L3

Power Supply

A3

A2

-

+

A1

Earth

RS-485

A4

A5

N1

P1

DI 2

D0 1

D0 4

DI 1

D

IG

IT

A

L

 I

N

P

U

T

D

IG

IT

A

L

 O

U

T

P

U

T

D2

D3

D6

D5

DI 3

D8

D7

DI 4

D10

D9

P2

S1

S2

IL1

E1

E2

P1

P2

S1

S2

IL3

IE

P1

P2

S1

IL2

E3

E4

E5

E7

E8

E6

A10
A9

D0 2

A14

A15

A13

A17

A18

A16

D0 3

A12
A11

NO
C

NC

NO

C

NO

NC

C

NO
C

S2

Connection Diagram

of  202 model

P1

Introduction

CSENEX Series offers a compact Multi-functional Over-current protection solution for 
Feeder, Generator, Motor & Transformer segment.

CSENEX-I Family of protective relays are numeric relays that provides multi protection 
and monitoring with reliable and fast protection solution in a single unit.
In this family  of  CSENEX series,  the  CSENEX-I is an  advanced  feeder  protection 
solution which has fast, sensitive and secure protection for feeder internal & external 
faults. CSENEX-I offers different model based features to cover the wide range of user.

L1

L2

L3

D

IG

IT

A

L

 I

N

P

U

T

DI 4

DI 3

D6

D5

DI 1

DI 2

DI 5

D8

D7

DI 6

D10

D9

(D2  IS  COMMON 
FOR DI1, DI2 & DI3)

D3

D4

D1

D2

A17

A18

A16

D0 1

D0 4

D

IG

IT

A

L

 O

U

T

P

U

T

A10
A9

D0 2

A14

A15

A13

D0 3

A12
A11

NO
C

NC

NO

C

NO

NC

C

NO
C

P1

P2

S1

S2

IL1

E1

E2

P1

P2

S1

S2

IL3

IE

P1

P2

S1

S2

IL2

E3

E4

E5

E7

E8

E6

RS-485

A4

A5

N1

P1

l

 

1A & 5A rated CT input (programmable)

l

 

Draw out with self CT shorting

l

 

Programmable auto-reclosing by selecting number of cycles for a particular fault *

l

 

Event record / Fault record

l

 

DI/DO programmable matrix *

l

 

Communication (Local & Remote)

Features

Protections

l

 

Three phase time over current protection (51)

l

 

Three phase instantaneous protection (50)

l

 

Earth time over-current (51N)

l

 

Earth instantaneous over-current (50N)

l

 

Current unbalance (46)

l

 

Broken conductor (46BC) *

l

 

Residual over-voltage (Neutral displacement) *

l

 

Circuit breaker failure protection (50BF)

l

 

Trip Circuit supervision (74TC) *

l

 

Negative Phase Sequence *

l

 

Digital Signal Processor based numeric design

l

 

Measures true RMS with DFT filter

l

 

4 Current analog inputs for phase & earth fault current

l

 

Max. 6 Digital Inputs / 4 Digital Outputs

l

 

16 x 4 Alpha-numeric LCD

l

 

8 LEDs at pickup and trip on fault + 3 LEDs with special function of 3 control keys

l

 

RS-485 & USB communication

Hardware

* Model dependent

05

06

07

08

01

02

03

04

Power Supply

A3

A2

-

+

A1

Earth

The disposal of our products and possible recycling of their components after 
decommissiong has to be carried out by an accredited recycling company or 
the products/components must be taken to applicable collection points. Such 
disposal  activities  must  comply  with  all  local  laws,  guidelines  and 
environmental specifications of the country in which the disposal is done.

Our products and batteries must not be disposed of as household waste. For disposing 
batteries it is necessary to observe the local national/international directives.

According to national legislation, penalties may be charged for incorrect disposal 
of such waste.

By disposing of these products correctly you will help to save valuable resources and 
prevent any potential negative effects on human health and the environment.

Disposal

Introduction

CSENEX Series offers a compact Multi-functional Over-current protection solution for 
Feeder, Generator, Motor & Transformer segment.

CSENEX-I Family of protective relays are numeric relays that provides multi protection 
and monitoring with reliable and fast protection solution in a single unit.
In this family  of  CSENEX series,  the  CSENEX-I is an  advanced  feeder  protection 
solution which has fast, sensitive and secure protection for feeder internal & external 
faults. CSENEX-I offers different model based features to cover the wide range of user.

l

 

1A & 5A rated CT input (programmable)

l

 

Draw out with self CT shorting

l

 

Programmable auto-reclosing by selecting number of cycles for a particular fault *

l

 

Event record / Fault record

l

 

DI/DO programmable matrix *

l

 

Communication (Local & Remote)

Features

Protections

l

 

Three phase time over current protection (51)

l

 

Three phase instantaneous protection (50)

l

 

Earth time over-current (51N)

l

 

Earth instantaneous over-current (50N)

l

 

Current unbalance (46)

l

 

Broken conductor (46BC) *

l

 

Residual over-voltage (Neutral displacement) *

l

 

Circuit breaker failure protection (50BF)

l

 

Trip Circuit supervision (74TC) *

l

 

Negative Phase Sequence *

* Model dependent

The disposal of our products and possible recycling of their components after 
decommissioning has to be carried out by an accredited recycling company 
or the products/components must be taken to applicable collection points. 
Such  disposal  activities  must  comply  with  all  local  laws,  guidelines  and 
environmental specifications of the country in which the disposal is done.

Our products and batteries must not be disposed of as household waste. For disposing 
batteries it is necessary to observe the local national/international directives.

According to national legislation, penalties may be charged for incorrect disposal 
of such waste.

By disposing of these products correctly you will help to save valuable resources and 
prevent any potential negative effects on human health and the environment.

Disposal

02

Содержание CSENEX-I

Страница 1: ...you step by step installation operation and programming procedure Please go through all the instructions carefully prior to implementing Current Protection Monitoring Solution CSENEX I Quick Reference...

Страница 2: ...tion 50 l Earth time over current 51N l Earth instantaneous over current 50N l Current unbalance 46 l Broken conductor 46BC l Residual over voltage Neutral displacement l Circuit breaker failure prote...

Страница 3: ...atus Scroll Edit key Enter key BLOCK indicates protection blocking based on DI BF TCS indicates the Circuit Breaker failure or Trip Circuit failure E indicates the fault in earth L3 indicates the faul...

Страница 4: ...rouble shooting tips on last page LCD Assignable function key F1 DO1 DO4 DO Reset CLOSE CB Close key on assigned DO OPEN CB Open key on assigned DO BF TCS indicates the Circuit Breaker failure or Trip...

Страница 5: ...L1 L2 L3 BLOCK E C O N T R O L BF TCS CSENEX I Dimension Details Side View Front View 158 5 112 0 Panel cutout Dimensions 145 0 125 0 154 0 CSENEX I relay is available in a plastic case for panel or f...

Страница 6: ...A1 Auxiliary Supply Earth A2 A3 Auxiliary Supply A4 A5 RS 485 Modbus N1 A4 P1 A5 A9 A10 Potential free Digital Output 4 A11 A12 Potential free Digital Output 3 A13 A14 A15 Potential free Digital Outp...

Страница 7: ...2 A3 Auxiliary Supply A4 A5 RS 485 Modbus N1 A4 P1 A5 A9 A10 Potential free Digital Output 4 A11 A12 Potential free Digital Output 3 A13 A14 A15 Potential free Digital Output 2 A16 A17 A18 Potential f...

Страница 8: ...38400 57600 bps Parity Selection programmable Even Odd None Stop Bit 1 Bit Data Bit 8 Bit data Remote Address programmable 1 to 247 Cable required for Interface Two wire twisted shielded cable Front U...

Страница 9: ...25W inductive L R 40ms Durability Loaded contact 10 000 operation minimum Trip Contact Rating Rated Data Rated Current Ip 1A or 5A Rated Frequency Fn 50 Hz 60Hz Drop out to pickup ratio 96 Power cons...

Страница 10: ...TC Harmonic blocking 50H Broken conductor 46BC x Auto Re closer 79 x Digital input 4 6 Digital output 4 4 Fault record 10 10 Event record 50 50 Selection of 1 5A Site selectable Site selectable Enclos...

Страница 11: ...serted in the enclosure properly Draw out the unit reinsert it properly so hat front BLUE LED should be steady ON 2 Check the VA Burden of primary CT It should closely match with the VA Burden of Rela...

Страница 12: ...to change the design or specification contained in this catalog without prior notice content C 60 Wing A Phase II Noida 201 305 Dist Gautam Budh Nagar U P INDIA Phone 91 120 38748 00 01 C S Electric...

Отзывы: