# GROUP SELECT #
ACTIVE-GRP :
GRP1
←
BACK
On selecting GROUP SELECT by pressing ENTER
key, user can change the active group by using
ENTER and then scroll key.
Press Enter and If the user selects the YES option
then it will ask to enter the correct password or else to
go to the previous menu by selecting the other
options by pressing ENTER key.
From Menu-1:
From Menu-1:
# PROTECTION #
CTRatio
: 0001 : CT Ratio for primary current display
Frequency : 50Hz : Frequency characteristic
PhaseCh : DEFT : Phase over-current trip characteristic
EarthCh
: DEFT : Earth over-current trip characteristic
l>
: 0.20xIn : Over-current Pickup
ti>
: 0.01
: TMS Over-current Setting
t>
: 0.1s
: DEFT Trip Time
l>>
: 0.5xIn : Short Circuit Protection
t>>
: 0.03 : DEFT Trip timing for SC Protection
Ie>
: 0.05xIn : Earth Over-current Pickup
tie>
: 0.01
: Inverse Trip Time
te>
: 0.05s : DEFT Trip Time
Ie>>
: 0.01xIn : Earth High-set Pickup
te>>
: 0.05 : DEFT Trip timing Earth High
SOFTpk
: DISABLE : SOTF pickup setting
Unbalnc
: 5%
: Unbalance
tUnblnc
: 0.50s : Unbalance DEFT Trip Time
CBFP
: YES
: CBFP Supervision Time
tCBFP
: 0.15s : CBFP Supervision Time
td_TCS
: 2.00s : TCS Trip Time
←
BACK
O n s e l e c t i n g
P R O T E C T I O N b y
pressing ENTER key.
User can see the list of all
the protection setting
parameter by using the
scroll keys.
Press ENTER to select
the desired Parameter &
use SCROLL keys to
Edit the selected one.
If the user change any of
the setting, It is required
to save the changes by
pressing ENTER key
and than selecting YES
option, after that entering
the correct password to
save the setting or else
to go to the previous
menu by selecting the
o t h e r o p t i o n s & b y
pressing ENTER key.
12