Technical Specification

Model No.

IMC

Operating time characteristic

Inverse/Definite time

Current range (A)

0.125~60A (One device)

Time Setting(s)

Inverse time

1~60sec/1sec (Class)

Definite time

D-Time

1~200sec/1sec

O-Time

1~60sec/1sec

Auto returning time (R-T)

1~20min/1min, OFF (Manual returning) 

Control Power 

Voltage

AC 110V or AC 220V (+15%)

Frequency

50/60Hz

Power Consumption

Under 6W

Output Contact (9Nos) Capacity

5A/250VAC

Construction

Digital contact  3a

Direct, Reversing, Y-D, Reactor, Inverter starter

Signal contact  3a

Local, Auto, W/L condition

Timer contact 

2a

ON Delay, OFF Delay

Trip contact 

1a

Fault output

Output Contact (9Nos) Operation input

Local, Auto, Water level, Flow switch

MC condition signal input

Monitoring of sequence (LED)

External trip 

2a

Emergency, Sequence

ZCT

Ratings

200mA/0. 1mA

Specification

25Æ, 40Æ, 80Æ

Indication

7-segment

3-phase current, Trip analysis, setting indication

LED

Operation, Trip, System fail, Communication, Remote control 
Condition

Self supervision

System Fail LED, Error indication

Communication

MODBUS/RS-485

Installation

Panel inside installation/Door mounting

Wlthdrawable cable

Basic cable 2m

Weight

0.6kg (MCT 0.35kg)

Dimension

Main unit

148(W) x 100(H) x 74(D) mm

MCT

151(W) x 55(H) x 33(D) m

13

Characteristics Curve - CSMPA & CSMPM Series

1000

100

10

1

0.1

100

600

1000

Hot

Cold

10000

1000

100

10

1

100

600

1000

Hot

Cold

20

30

Time(sec)

9

100

Current (%)

150

200

300

400

500

600

1

3

5

7

Analog Relay: CSMPA 22/40/80

Digital Relay: CSMPM 6/60

Class 10 (10 Sec.)

10000

1000

100

10

1

100

600

1000

Hot

Cold

30

10000

1000

100

10

1

100

1000

30
20

60

Definite time characteristics-CSMPA-60T/TE

Class 20/30 (20/30sec.)

Definite time characteristics

Содержание CSMPA22-2S

Страница 1: ...TM 40 26 Electronic Motor Protection Relays ...

Страница 2: ...ry l l l Reverse phase l 3SR l 3SR l 3SR Current setting range A 0 3 1 5 1 5 4 4 22 Operating time characteristics Inverse time characteristics Inverse time characteristics CSMPA22 2PD Definite time Characteristics Time setting Inverse time 0 30 sec Sec Reset time Manual Reset Prompt Reset after 1min optional Tolerance Current 5 Time 5 or 0 5sec Control Voltage AC 100 260V Power Frequency 50 60Hz ...

Страница 3: ...ent of a motor to protect from the over current Check if the rated current of a motor is within the current setting range of relay Set the RC A Rated current knob to the maximum value and then start a motor Under normal motor operation rotate the RC knob to the counterclockwise until the O L LED turned ON OFF The current at this point in the 100 current rating under real load At this point rotate ...

Страница 4: ...ring which the relay tripped by the over current The relay is tripped after the selected operating time Set the operation time by the O TIME knob In special case such as for mechanical shock relay if you set the O TIME to the min value the relay is tripped at once Generally set it to 4 6 seconds 3 Set the operating current Similar to that of the screw type Set the operation current to protect from...

Страница 5: ...LED External trip 2a Emergency Sequence ZCT Ratings 200mA 0 1mA Specification 25Æ 40Æ 80Æ Indication 7 segment 3 phase current Trip analysis setting indication LED Operation Trip System fail Communication Remote control Condition Self supervision System Fail LED Error indication Communication MODBUS RS 485 Installation Panel inside installation Door mounting Wlthdrawable cable Basic cable 2m Weigh...

Страница 6: ...S 3SR With External Current Transformers CSMPA 22 40 80 2S 3S 3SR For Y D Wiring R S T MCCB MCD relay A1 95 97 A2 96 98 Relay FUSE TR MCM MCS 19T MCD 19X OFF RESET ON 19X MCD 19T 19X MCS MC MCM U V W M X Y Z MCS Note When you use the relay inside of the line apply the 1 3 value of the rated current MCM MCD MCS 19T 19X Magnetic Contactors for Power use Magnetic Contactors for motor operation use Ma...

Страница 7: ...le 17 48 5 5 53 6 54 2 72 5 M3 5 8 52 63 50 5 44 23 7 48 7 2 012 u u u u u u u u u u u u u u u u u u u u 55 69 u u u u 47 u u u u 9 5 R2 5 05 62 5 1 5 22 u u u u u u u u u u u u 44 7 4 5 CSMPA 60T CSMPA 60TA CSMPA 22 2S CSMPA 80 2S CSMPA 22 3S CSMPA 80 3S CSMPA 22 3SR CSMPA 80 3SR 3 CT 100 400 500 600 CSMPA 40 2S CSMPA 40 3S CSMPA 40 3SR 8 INSERT M4 118 74 22 45 8 Ø5 5 62 5 141 51 141 118 74 14 5 ...

Страница 8: ... 40 A 100 260 V 1a1b CSMPA80 2S 16 80 A 100 260 V 1a1b CSMPA80 3S 16 80 A 100 260 V 1a1b CSMPA80 3SR 16 80 A 100 260 V 1a1b CSMAP60 T 0 5 6 A 110 220 415 V 1c CSMPA60 T 5 60 A 110 220 415 V 1c CSMPA60 TE 0 5 6 A 110 220 V 1c CSMPA60 TE 5 60 A 110 220 V 1c Intellegent Motor Controller with communication Communication through Models RS 485 RS 422 Inverse Definite Time Characteristics Comprehensive D...

Страница 9: ...We touch your everyday electricity 36 37 Sai Dham Commercial Center Landewadi Bhosari PUNE 411039 Email marketing genuineatuomation com Website www genuineautomation net GENUINE AUTOMATION ...

Отзывы: