background image

HVAC  PRODUC S

HVAC PRODUC S

 

HVAC PRODUC S

ALX SERIES

SPUN ALUMINUM EXHAUSTERS

ALX-M-07_31_14

Page 4 of 5

WARNING

MAKE SURE THE UNIT IS NOT CAPABLE OF OPERATION DURING REPARATION.

FAN TROUBLESHOOTING

WARRANTY

CANARM Ltd.

warrants every new fan to be free of defects in material and workmanship to the extent that, within a period of one year

from the date of purchase 

CANARM Ltd.

shall either repair or replace at 

CANARM

’s option, any unit or part thereof, returned freight

prepaid, and found to be defective.

This warranty does not include any labour or transportation costs incidental to the removal and reinstallation of the unit at the user’s 
premises.

Components repaired or replaced are warranted through the remainder of the original warranty period only; it is null and void in case of 
alteration, accident, abuse, neglect, and operation not in accordance with instructions.

NOTICE: 

No warranty claims will be honored by 

CANARM Ltd.

unless prior authorization is obtained.

P

ROBLEM

P

O

SS

IBLE I

SS

U

E

S

OL

U

TION

Wheel rubbing inlet

Adjust wheel, loosen set screw(s) and move the wheel, acquiring 
clearance between inlet and wheel, then re-tighten set screw(s)

Wheel unbalance

Check wheels for debris or dirt build up and clean when necessary

Object in rotation area or housing

Remove object

Motor compartment loose

Re-tighten the fasteners

Malfunction of electrical supply

Check supply voltage, fuse and switch

Malfunction of motor

Check wiring and overload protector

Motor overload/overheat

Wrong wheel rotation

Re-wire the motor to change direction of rotation

Damper Malfunction

Check opening side of back draft damper, check operation status of 
controlled damper

Wrong wheel rotation

Re-wire the motor to change direction of rotation

Improper Duct System

Check obstruction of duct in the duct or dirty filter

Fan does not operate

Redu

c

ed airflow

Ex

c

essive noise/vibration

Disconnect and secure to the OFF position all electrical power to the fan prior to inspection or servicing. Failure to comply with this safety
precaution could result in serious injury or death.

1.

Ventilator should be checked at least once a year. For critical or severe applications a routine check every two to three months is 
suggested.

2.

When moving or installing a belt, don’t force the belt over the sheave. Loosen the motor mount so that the belt can be easily slipped
over the sheave.

3.

The belt, on belt driven units, should be removed and carefully checked for cracks, ply separation or irregular wear. A small
irregularity in the contact surface of the belt will result in noisy operation. If any of these defects are apparent the belt should 
be replaced. At the same time check the sheaves for chips, dents or rough surfaces that could damage the belt.

4

. The correct belt tension is important. Too tight a belt will result in excess bearing pressure, which can cause premature bearing failure

and may cause the motor to overload.  Too loose a belt will result in slippage, which will burn out belts. Proper belt deflection should
be 1/64” (half way between sheave centers) for each inch of belt span when a force of approximately 5 lbs. is applied.

5.

The belt alignment should be checked to be sure that the belt is running perpendicular to the rotating shafts. Motor and drive shafts
must be parallel.

6.

A periodic inspection of all fasteners should be carried out to ensure they have not loosened due to vibration. Particular attention
should be paid to fasteners attaching the wheel to the shaft and those attaching the shaft to the bearing.

MAINTENANCE 

Содержание ALX SERIES

Страница 1: ...CEIVER MUST NOTE ANY DAMAGE ON THE CARRIER S BILL OF LADING AND FILE A CLAIM IMMEDIATELY WITH THE FREIGHT COMPANY DO NOT LIFT THE UNIT BY THE HOOD OR MOTOR PLEASE LIFT THE UNIT BY HORIZONTAL SUPPORTS...

Страница 2: ...nd on the control box itself 4 Motor RPM range would be from full RPM to the RPM just set The lowest minimum voltage that may be applied to the motors is 65VAC Running at lower voltage can cause prema...

Страница 3: ...sconnect switches are available for purchase as accessories No dampers can be used in the system UL762 RESTAURANT EXHAUST APPLICATION 1 Lock out all power sources 2 Inspect all fasteners and set screw...

Страница 4: ...ong wheel rotation Re wire the motor to change direction of rotation Improper Duct System Check obstruction of duct in the duct or dirty filter Fan does not operate Reduced airflow Excessive noise vib...

Страница 5: ...IBRATION ELIMINATOR 4 5 TOP PLATE 1 6 UPBLAST APRON 1 7 VENT 1 8 VERTICAL BRACKET 4 9 INLET BAFFLE 4 10 DRAIN 4 11 MOTOR SUPPORT RAIL 2 12 HORIZONTAL BRACKET 4 13 BASE 1 14 BLOWER WHEEL 1 5 6 7 3 2 8...

Страница 6: ...a aucun dommage SI VOUS CONSTATEZ DES DOMMAGES VOUS DEVEZ LES NOTER SUR LE CONNAISSEMENT DU TRANSPORTEUR ET FAIRE UNE R CLAMATION AU TRANSPORTEUR IMM DIATEMENT NE SOULEVEZ PAS L QUIPEMENT PAR LE CAPOT...

Страница 7: ...est 65VAC Un voltage en de de ce niveau peut causer un d faillance pr matur e du moteur Pour un moteur 3 phases un entra nement fr quence varaible VFD est requis pour ajuster la vitesse du moteur CON...

Страница 8: ...alignement et la tension si applicable 4 Con rmer que le voltage utilis est identique celui du moteur et que le tout est bien c bl 5 Faire la rotation de la roue pour s assurer que ni la pale ni la c...

Страница 9: ...et v rifier l op ration du volet contr l Mauvaise rotation de la roue Refaire le c blage pour changer la direction de la rotation Syst me de conduit inad quat Redimensionner le conduit Bruit vibration...

Страница 10: ...D BIT VERS LE HAUT 1 7 VENT 1 8 FERRURE VERTICALE 4 9 D FLECTEUR D ENTR E 4 10 DRAIN 4 11 RAIL DE SOUTIEN DU MOTEUR 2 12 FERRURE HORIZONTALE 4 13 BASE 1 14 ROUE DE VENTILATEUR 1 5 6 7 3 2 8 9 4 14 11...

Отзывы: