A2X SERIES

 

 

SPUN ALUMINUM EXHAUSTERS

M-A2X_05_13_22

Page 2 of 5

1.

A qualified electrician in accordance with all local and National Electrical Codes should do all wiring.  

2.

Ensure power supply is disconnected and locked out prior to making electrical connections.   

3.

Wire the motor according to the wiring diagram on motor label or on the sticker inside the motor wrap. All motors should be wired to 

the same rotation as indicated on the sticker on the top plate.  

4.

Leave enough slack in the wiring to allow for motor movement when adjusting the belt tension.   

5.

Excess wire must be restrained in order to prevent it from entering the pulley, shaft or wheel rotating area.   

6.

Disconnect switches are recommended and should be located near the fan in order to, swiftly cut off power in case of an emergency 

and maintain complete control of the power source.

Some single phase direct drive motor’s running RPM can be adjustable with a variable speed control (please contact factory for more  

information). The speed control knob starts at off position, then high to low adjust range. At high speed, the speed control would allow the 

motor running at its maximum RPM. Dial the knob to the low side would let the speed control regulate the voltage on the motor to reduce 

the RPM. 
A minimum speed adjustment is needed to limit the motor RPM range. Follow this procedure to set the minimum speed. 

1.

Motor must be in servicing status to allow the minimum speed setting. Motor would not slow down unless proper load is applied.   
Motor RPM would be changed under different system (static pressure). 

2.

Turn the main control knob to the lowest speed position. 

3.

Locate and adjust the minimum speed setting, it can be found on the control box itself. 

4.

Motor RPM range would be from full RPM to the RPM just set.  

 

The lowest minimum voltage that may be applied to the motors is 65VAC. Running at lower voltage can cause premature failure 

to the motor.

 

For 3 phase motors, a variable frequency drive (VFD) is required to adjust motor speed.

VARIABLE SPEED CONTROL – SINGLE PHASE

VARIABLE FREQUENCY DRIVE – THREE PHASE

INSTALLATION

RECOMMENDED
ROOF OPENING

WIRED TO POWER

BY OTHERS

ROOF

DECK

OPTIONAL DISCONNECT CAN 

BE MOUNTED INSIDE THE 

HOUSING OR OUTSIDE

MINIMUM 12”

RECOMMENDED
ROOF OPENING

ROOF

DECK

MINIMUM 12”

WIRE OPTION 2:

WIRE THROUGH

THE VENT TUBE

WIRE OPTION 1:

THROUGH CONDUIT

GENERAL CLEAN AIR APPLICATION (UPBLAST)

GENERAL CLEAN AIR APPLICATION, DOWNBLAST

Note: A2X105 and A2X120 has only wiring option 1, A2X210 and larger has 

only wiring option 2 available. 

STANDARD WIRING INSTRUCTIONS

1.

Install roof curb, caulk and flash to ensure the water tightness. 

2.

Rotate the blower wheel by hand. Wheel should not be rubbing against the housing inlet. If rubbing occurs, loosen the set screws on 

the wheel hub and shift the wheel to obtain clearance. Then re-tighten all set screws. 

3.

Complete all subsequent duct connections. 

4.

Secure the fan to the curb cap. Do not lift the unit by the hood or motor. Lift the unit by horizontal supports on direct drive or by motor 

mounting plate for belt drive unit. 

5.

Use at least 8 proper fasteners to connect the blower base to the roof curb. 

6.

Verify if the power supply is compatible with the equipment.  

7.

Make sure the power line is shut down before wiring the motor to power line. 

8.

Remove top cap, connect power line to the motor/disconnect switch as indicated. 

9.

For all upblast units, the electrical supply enters the motor compartment through the vent tube. 

10.

Ensure all fasteners and set screws are tightened. 

11.

Place the top cap back on the hood. 

12.

Caulk and flash the fan base including the fan base corners and roof curb to ensure good water tightness. 

Содержание A2X Series

Страница 1: ...provincial and local codes all of them will supersede this manual 9 Failure to follow the safety instructions in this manual may cause serious injury or death due to electrical shock or high speed ro...

Страница 2: ...RPM range would be from full RPM to the RPM just set The lowest minimum voltage that may be applied to the motors is 65VAC Running at lower voltage can cause premature failure to the motor For 3 phase...

Страница 3: ...del The control module features a 4 digit LED display that indicates demand of full speed and motor speed in rpm The display also indicates an error code message for minor diagnostics if required Moto...

Страница 4: ...itches are available for purchase as accessories No dampers can be used in the system RESTAURANT EXHAUST APPLICATION 1 Lock out all power sources 2 Inspect all fasteners and set screws and tighten as...

Страница 5: ...accident abuse neglect and operation not in accordance with instructions NOTICE No warranty claims will be honored by CANARM Ltd unless prior authorization is obtained Disconnect and secure to the OF...

Страница 6: ...concernant l usage de cet appareil car ils supplantent de manuel 9 Ne pas suivre les instructions de ce manuel peut causer de s rieuses blessures ou la mort due un choque lectrique ou aux pi ces en ro...

Страница 7: ...de ce niveau peut causer un d faillance pr matur e du moteur Pour un moteur 3 phases un entra nement fr quence variable VFD est requis pour ajuster la vitesse du moteur CONTR LE DE VITESSE VARIABLE U...

Страница 8: ...si n cessaire La vitesse du moteur peut tre chang e en ajustant le pot de contr le de la vitesse situ sur le module de contr le Un petit tournevis peut tre utilis pour faire cet ajustement M A2X FR_05...

Страница 9: ...OUVERTURE DU TOIT RECOMMAND E CONDUIT SOUD PAR AUTRUI CONDUIT SOUD PAR AUTRUI REBORD VENTIL MINIMUM DE 20 DE LA CIME DU TOIT C BL POUR TRE ALIMENT PAR D AUTRES MUR SURFACE DU TOIT INTERRUPTEUR DE FER...

Страница 10: ...ration excessif D bit d air r duit Mettre l appareil hors tension et fermer le disjoncteur avant de faire l inspection ou l entretien Un manque cette directive pourrait causer de s rieuses blessures o...

Отзывы: