9 Commissioning Inverter
18 / 32
If required, you can adjust the parameter values in the allowed range.
Notice: The parameters can be adjusted under the “Volt-Watt enable” mode only.
The allowed range for Australia Region A, B, C.
Region
Default value
Vw1
Vw2
Australia A
Voltage
253 V
260 V
Inverter maximum active power output level (P)% of S
rated
100%
20%
Australia B
Voltage
250 V
260 V
Inverter maximum active power output level (P)% of S
rated
100%
20%
Australia C
Voltage
242 V
250 V
Inverter maximum active power output level (P)% of S
rated
100%
20%
Allowed range
Voltage
235 to 255 V 240 to 265 V
Inverter maximum active power output level (P) % of S
rated
100%
0% to 20%
NOTE Australia C parameter set is intended for application in isolated or remote power systems.
b) Reactive power regulation for voltage variation (Volt-Var mode), as per FIG. 9.8
FIG. 9-8 Reactive Power Regulation for Voltage Variation (Volt-Var mode)
If required, you can adjust the parameter values in the allowed range.
Notice: The parameters can be adjusted under the “Volt-Var enable” mode only.
Parameters modification steps:
1. In the Parameters page, modify the “Volt-Var” to Enable mode.
2. Adjust the parameter values according to the local requirement.