9. Troubleshooting
NOTE
If the inverter displays any alarm message as listed in Table 9.1, please
turn off the inverter (refer to Section 6.2 to stop your inverter) and wait for 15
minutes before restarting it (refer to Section 6.1 to start your inverter). If the
failure persists, please contact your local distributor or the service center.
Please keep ready with you the following information before contacting us.
1. Serial number of Canadian Solar Three Phase Inverter;
2. The distributor/dealer of Canadian Solar Three Phase Inverter (if available);
3. Installation date.
4. The description of problem (i.e. the alarm message displayed on the LCD and the status
of the LED status indicator lights. Other readings obtained from the Information submenu
(refer to Section 6.2) will also be helpful.);
5. The PV array configuration (e.g. number of panels, capacity of panels,
number of strings, etc.);
6. Your contact details.
10. Specifications
.60.
.61.
Dimensions (W*H*D)
Weight
1065*567*344.5mm
84kg
Max. DC input voltage (Volts)
MPPT voltage range (Volts)
Max. input current (Amps)
MPPT number/Max input strings number
Rated grid voltage (Volts)
Rated grid output current (Amps)
Power Factor (at rated output power)
Max.efficiency
EU efficiency
Model
Topology
Self consumption (night)
Operating ambient temperature range
Relative humidity
Ingress protection
Cooling concept
Max.operation altitude
1100
10*26
10*40
10/20
50/60
98.7%
98.3%
Transformerless
<
2W
-25
℃...
+60
℃
0~100%
IP66
Intelligent redundant cooling
4000m
Rated output power (Watts)
Max. output power (Watts)
Max. apparent output power (VA)
600
100000
110000
110000
152.0/144.3
167.1
THDi (at rated output power)
<3%
Start-up voltage (Volts)
Max short circuit input current (Amps)
Rated DC voltage (Volts)
Rated grid frequency (Hertz)
180...1000
195
Max. output current (Amps)
AC connection
DC connection
Display
Communication connections
MC4 connector
OT Terminal (max 185 mm²)
LCD, 2×20 Z
RS485, Optional: Wifi, GPRS , PLC
3/N/PE, 220/380, 230/400
Operating frequency range (Hertz)
45...55 or 55...65
>
0.99 (0.8 leading - 0.8 lagging)
Noise emission (typical)
≤
65 dBA
CSI-100K-T400GL02-E