Input to output isolation

Not isolated

Input voltage

20 to 35 VDC

Output voltage

13.8 VDC ± 0.1 V

Output voltage regulation

< 3%

Input current at no load

Approx. 25 mA

Output current

Continuous

20 A

Current limit *

21A

*Note:

  In current limit condition, the output voltage will drop if the current drawn increases beyond the current 

limit value of 21 A

Output ripple and noise

less than 50 mV    RMS

Efficiency

Approx. 92%

Operating ambient temperature

-20 to +30

o

(derate linearly to 0 at 70º C) 

Humidity

Max. 95%, non condensing

Protections:

- Overload

By current limiting

- Over heating

Drop in output voltage

- Reverse polarity

Fuse protection, 20 A

- Over voltage

Varistor

 

(also protects against load dump)

Input side fuse

20 A (inside the unit)

Safety and EMC Standards:
- Emission

EN50081-1

- Immunity

EN50082-1

- Automotive directive

95/45/EC

Input / output connections

Terminal Block –

 

(6.3   mm   male   flat   tab, 

quick connect)

Weight

0.48 lbs / .21 Kg

Dimensions (H x W x D)

1.9” x 3.5” x 5.0”(49 x 88 x 126mm)

Warranty

5 years

NOTE: 

Specifications are subject to change without notice 

CAUTION!

  : THERE IS NO ISOLATION BETWEEN THE INPUT AND THE OUTPUT. INPUT 

AND OUTPUT HAVE A COMMON NEGATIVE 

Содержание CPC-20

Страница 1: ...Owner s Manual Product DC DC Step Down Converter Model CPC 20 Thank you for purchasing a Canadian Power Conversion product Please read this manual before operating this converter INSTRUCTION MANUAL ...

Страница 2: ...The unit may be installed on the top of or the bottom of a horizontal surface It can also be installed horizontally on a vertical surface Input and output connections The CPC 20 has a terminal block with 4 male flat tabs 6 3 mm for quick connection One is for positive 24 VDC input marked 24 V two are common negative for input and output marked 0 V and one is for positive 12 VDC output marked 13 8 ...

Страница 3: ...V To limit voltage drop to 2 use 10 AWG for distance up to 6 ft and 8 AWG for up to 10 ft The cables on the 12 VDC output side must be able to carry the full 21 A current under current limit conditions To limit the drop in voltage to 2 use 10 AWG multi stranded cables to connect to the load for a distance of up to 6 ft and 8 AWG for a distance of up to 10 ft Use female quick connect terminals tab ...

Страница 4: ... 0 at 70º C Humidity Max 95 non condensing Protections Overload By current limiting Over heating Drop in output voltage Reverse polarity Fuse protection 20 A Over voltage Varistor also protects against load dump Input side fuse 20 A inside the unit Safety and EMC Standards Emission EN50081 1 Immunity EN50082 1 Automotive directive 95 45 EC Input output connections Terminal Block 6 3 mm male flat t...

Страница 5: ...Contact Information Corporate Address 10673 240A Street Maple Ridge B C Canada V2W 2B1 e cpc canadianpowerconversion com w www canadianpowerconversion com ...

Отзывы: