32
This flow of electrons is the flame current. The flame current
is measured by the control as ionization in uA.
When the flame current is above
1.5uA
, the Valiant FT will
register
a flame.
When the flame current is below
1,0uA
,
the flame will be
registered as extinguished.
PART 7 ERROR TABLE
There are three different type of error-groups:
Locking Errors
(Manually reset via the reset button)
Blocking Errors
(Automatically reset when the error is
resolved)
Warnings
(will disappear when the warning is resolved; not
stored in history)
Table 14: Lockout Codes
#
Description
1
Unconfigured safety data
2
Waiting for safety data verification
3-46, 58-60, 97-99,
143-148, 172-178
Internal Fault. Replace SOLA
Controller
47
Flame rod to ground leakage
48
Static Flame
49
24VAC low/high
50
Modulation Fault
64
Fan speed not proved, ignition
failure
67
Interlock Off, safety circuit is open
79
Heater Outlet high limit tripped
82
Stack limit tripped (PVC: 149
°
F,
CPVC: 194
°
F, 250
°
F)
105
Flame detected out of sequence
106
Flame lost if Main Flame
Establishing Period (MFEP)
107
Flame lost early in run
108
Flame lost in run
109, 110
Ignition failed
112
Pilot test flame timeout
113
Flame circuit timeout
137
Interlock failed to close; safety
circuit is open
149
Flame detected
Figure 38: Lockout Condition (Home screen)
Figure 39: Lockout Condition (lockout screen)
To eliminate the lockout error,
1. Press the red bar, as circled above
2. Press the [Lockouts] button
3. Press [Clear Lockout]
Table 15: Alert Codes
#
Description
29
Burner switch turned OFF
30
Burner switch turned ON
61
Anti-short Cycle
62
Fan speed not proved
63
LCI off, safety circuit is open
68
Setpoint was overridden due to sensor fault
69
Modulation was overridden due to sensor fault
81
Delta-T limit exceeded (70
°
F)
110
Ignition failure occurred
123
Modulation rate was limited due to outlet limit
124
Modulation rate was limited due to Delta-T limit
215
No Lead Lag slaves available to service demand
219
Using backup Lead Lag header sensor due to
sensor failure
229
Lead lag slave communication timeout.
275-281
LCI off, safety circuit is open
283
Demand off during measured purge time
291
Abnormal Recycle: Flame was not on at end of
Ignition period
292
Abnormal Recycle: Flame was lost during Main
Flame Establishing Period
293
Abnormal Recycle: Flame was lost early in Run
294
Abnormal Recycle: Flame was lost during Run
303-310
+
Interlock Off, safety circuit is open
324, 374-
379
Hardware flame bias. Flame sensor wire needs to
be re-routed.
352
+
Stack sensor fault
355
+
Outlet sensor fault
357
+
DHW sensor fault
359
+
Inlet sensor fault
460
LCI lost in run
550
Delta T inlet/outlet limit was exceeded
614
Lead boiler was rotated due to measured run time
* If an internal hardware fault is detected, contact Camus Technical
Support for troubleshooting procedure.
+
The alarm LED and alarm contacts closed and remain closed until
the ‘RESET’ button is pressed.
Содержание Valiant-FT II Series
Страница 2: ...99 0419 Rev 00...
Страница 40: ...36 PART 9 PIPING DIAGRAMS Figure 40 Single Boiler Hydronic Heating Zoned Piping...
Страница 41: ...37 Figure 41 Multiple Boiler Hydronic Heating Zoned Piping...
Страница 42: ...38 Figure 42 Single Boiler with DHW Tank Hydronic Heating Zoned Piping...
Страница 43: ...39 PART 10 PARTS LIST...
Страница 44: ...40...
Страница 45: ...41...
Страница 46: ...42...
Страница 47: ...43...
Страница 48: ...44...
Страница 49: ...45...
Страница 50: ...46...
Страница 51: ...47...
Страница 52: ...48...
Страница 53: ...49...
Страница 54: ...50...
Страница 60: ...56 PART 11 TUBING DIAGRAM...
Страница 61: ...57 PART 12 WIRING DIAGRAM...
Страница 62: ...58...
Страница 63: ...59...