28
Domestic Hot Water Setup Programming Instructions
Adjust lightoff rate
Description
Programming Instructions
•
Adjust ignition speed on
lightoff
•
This may need to be adjusted
to achieve smooth lightoffs
cannot be achieved through
combustion settings
•
All Tank Heater’s leave the
factory with an ignition fan
speed of 3000 RPM
1)
Place both toggle switches in
LOCAL
2)
Press
and select Login
3)
Select Advanced Setup
4)
Select
Burner Control Ignition
5)
Select
Adjustable lightoff rate,
and enter desired lightoff rate using 5-way control and press
Adjust stack limit
Description
Programming Instructions
•
Adjust stack limit based on
vent material used
•
PVC: 149
o
F
•
CPVC: 194
0
F
•
PP, AL29-4C, Stainless steel:
230
o
F
1)
Place both toggle switches in
LOCAL
2)
Press
and select Login
3)
Select Quick Start
4)
Select
Stack Limit
5)
Select
Preferred
Stack limit
, and enter desired stack limit rate using 5-way control and press