24
Modulation: Boiler Inlet, Outdoor Reset Operation (Standalone)
Description
Electrical Connection(s)
Programming Instructions
•
Boiler operates with variable
setpoint determind by
outdoor reset curve
•
Modulates on inlet sensor
(default)
•
Heat demand is generated
when Remote Operator is
closed.
1)
Place both toggle switches to
LOCAL
2)
Press
and select Login
3)
Select Advanced Setup
4)
Select
CH Config
5)
Select
Outdoor Reset Config
6)
Select
Outdoor
Reset and Press
and select
Enable
7)
Set
Max outdoor temp
(Warm weather shutdown, WWSD)
8)
Set
Min outdoor temp
(Outdoor Design)
9)
Set
Low Water temp
(Min. Water Temp.)
10)
Set
Outdoor boost max off point
(Design Max.)
11)
Select
Sensor Configuration
12)
Select
Outdoor temp src
and Press
13)
Select
S5
and Press
14)
Place right hand toggle switch to
REMOTE
for remote operation (if
required)