Connections

 

Clamping Yoke Connector Specifications 

 

Input / Output connections 

Optional Signal connections plugs 

Tightening torque min. – max. 

1,2 – 2,2Nm (blade 1,0x5,5 DIN5264 ) 

0,4 – 0,5Nm (blade 0,6x3,5 PH1 PZ1) 

Touch-safe protection acc. to DIN VDE 0470 

IP20 plugged/ IP10 unplugged 

Not applicable 

Clamping range, min. – max. 

0,5 – 16mm² / AWG26 – AWG6 

0,2 – 4,0mm² / AWG26 – AWG12 

Solid, H05(07) V-U min. – max. 

0,5 – 16mm² 

0,2 – 4,0mm² 

Stranded, H05(07) V-U min. – max. 

6 – 16mm² 

Not applicable 

Flexible, H05(07) V-U min. – max. 

0,5 – 16mm² 

0,2 – 4,0mm² 

w. plastic collar ferrule, DIN 46228 pt 4 min. – max. 

2,5 – 10mm² 

0,2 – 2,5mm² 

w. wire end ferrule, DIN 46228 pt 1, min. – max. 

2,5 – 10mm² 

0,2 – 4,0mm² 

Plug gauge in accordance with EN 60999 a x b; ø 

5,4 x 5,1mm; 5,3mm 

2,8 x 2,4mm; 2,5mm 

Pitch (P) 

10,16mm 

5,08mm 

Wire Stripping Length (fine wired) 

Nominal Cross Section 

Wire End Ferrule 

Stripping Length 

Wire End Ferrule 

Stripping Length 

0,25mm² 

H0,25/5 

5mm 

H0,25/10 HBL 

8mm 

0,5mm² 

H0,5/6 

6mm 

H0,5/12 OR 

8mm 

1,0mm² 

H1,0/6 

6mm 

H1,0/12 GE 

8mm 

2,5mm² 

H2,5/12  

12mm 

H2,5/19D BL  

14mm 

4,0mm² 

H4,0/12 

12mm 

H4,0/20 GDR 

14mm 

6,0mm² 

H6,0/20 

12mm 

H6,0/20 SW 

14mm 

10,0mm² 

H10,0/12 

12mm 

H10,0/22 EB 

15mm 

The length of ferrules is to be chosen depending on the rated voltage. The outside diameter of the plastic collar should not be larger than 
the pitch (P) 

 
 

Ordering Information 

Ordering Codes 

Product Code 

Information 

Article Number 

HSEUREG07201.015(R2) 

0-18Vdc 

3041052001CA 

HSEUREG07201.030(R2) 

0-30Vdc 

3041052002CA

 

HSEUREG07201.050(R2) 

0-50Vdc 

3041052003CA

 

HSEUREG07201.090(R2) 

0-90Vdc 

3041052004CA

 

HSEUREG07201.130(R2) 

0-130Vdc 

3041052005CA

 

HSEUREG07201.180(R2)

 

0-180Vdc 

3041052006CA

 

Certificate Calibration 

Separate works certificate manufacturer calibration of the power supply 

Back Plate Kit 

Hart mount plate kit including screws 

2201002001CA 

Optional Interface Connectors 

Optional 2poles Clamping Yoke Connector 180° cabling (10pcs per pack) 

3520037 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

Содержание HSEUREG07201.015

Страница 1: ...IN Rail Specification Voltage programming from 0V Multi interface 0 10V 0 20mA Sense Shutdown remote ON OFF N 1 parallel operation Natural convection Precise dynamic response on load change Designed for long life under full stress Strong input filters High reliability shock vibration proof Over Voltage and continuous short circuit protection EMI EMS EN61000 6 2 3 EN55032 class B EN61010 1 EN61010 ...

Страница 2: ...atural convection The 1kW models use a forced air cooling system with a fan In selecting the fan as with all our power supplies in our opinion we use with the German manufacturer EBM Papst the highest quality and most reliable devices in the world market Design Conception The HSEUREG power supply series realizes high programmable power in a space saving housing Latest generation electrical devices...

Страница 3: ...n protective electrical separation 60Vdc Analogue Interface see table protective electrical separation 60Vdc working impedance 500Ω Accuracy 1 5 Interface Latency Interface 15ms including signal latency for 0 Umax programming Start up Delay Typ 250ms Softstart Typ 100ms Start up from Shutdown Typ 250ms Response Load Change 1ms 10 100 100 10 Base Load None Efficiency 230Vac 90 typical Short Circuit...

Страница 4: ...unctional interface 500 Ω working resistance with voltage programming 2 Ureg Input 3 Sense Input Sense Control none Compensation max 2V per load line 4 Sense Input 5 Remote Input External Shutdown Remote ON OFF Open Collector or Switch Voltage drop 1V with typical 2 3mA 6 Remote Input Programming Interface Ureg The standard programming of the HSEUREG Series is an analogue interface The output volt...

Страница 5: ...o allow proper operation Remote Sensing Schematics Although the HSEUREG sense block is simpler it applies to the shown schematics Please note that the HSEUREG has no AUX connection feature and that the sense block has only connections We recommend twisted sense lines Local Sensing Remote Sensing Compensation of Load Line Drop Voltage Sense battery charger operation mode Remote Sensing as a battery...

Страница 6: ... sections of all power supplies to the busbar or to the star point are identical Allow proper connection for low contact resistance If you want to use the sensing function connect it also to the star point or busbar To avoid measurement errors select the line length from the neutral point or from the busbar to the load as short as possible and use the maximum possible conductor cross section The H...

Страница 7: ...rein a failure or malfunction could result in injury or death Mechanics ST HD Baseplate Cooling Temperature Management The temperature management of the HSEUREG series provides a direct dissipation of the main energy losses The internal coolers of the output diodes and the power FETs connect to the back plate cooler It is possible to dissipate about 40 50 of the energy losses out of a system while...

Страница 8: ...a free air space of 50mm top bottom and 10mm sidewalls is required and for active devices 15mm space from the sidewalls One can use the DIN Rail installation equipped standard with our patented 35mm DIN Rail bracket according to EN60715 It is easy to mount dismount while snaping it onto the 35mm DIN Rail no tools necessary It is not allowed to install the HSEUREG in other mounting direction then b...

Страница 9: ... accordance with EN 60999 a x b ø 5 4 x 5 1mm 5 3mm 2 8 x 2 4mm 2 5mm Pitch P 10 16mm 5 08mm Wire Stripping Length fine wired Nominal Cross Section Wire End Ferrule Stripping Length Wire End Ferrule Stripping Length 0 25mm H0 25 5 5mm H0 25 10 HBL 8mm 0 5mm H0 5 6 6mm H0 5 12 OR 8mm 1 0mm H1 0 6 6mm H1 0 12 GE 8mm 2 5mm H2 5 12 12mm H2 5 19D BL 14mm 4 0mm H4 0 12 12mm H4 0 20 GDR 14mm 6 0mm H6 0 2...

Страница 10: ...bolts or operation outside the specified herein specification or in an unsuitable environment has the immediate loss of warranty to follow We disclaim any responsibility for any resulting damage to persons or things 4 Note The device must not be operated without an upstream circuit breaker CB We recommend the use of C Type 16A for 230Vac or 25A for 115Vac It is prohibited to use the unit without P...

Отзывы: