(Subject to alterations. This product is not designed to be used in applications such as life support systems wherein a failure or malfunction could result in injury or death)
Mechanics
IP20 housing, UL94V-0 ABS with RTI 85°C, housing for DIN/VDE0603 cutout box and wall mount. DIN 43880 with IEC
standardized ventilation slots. Save fix on DIN-Rail TS35mm (7.5/15) DIN/EN60715. It is designed for building cabinets
DIN/VDE0603. Easy to wall mount by multifunctional housing; remove the DIN-Rail latch and access the two mounting
holes to screw the ESB303 to any flat surface.
Mounting Instructions
Follow the mounting restrictions to allow maximum lifetime of the product and to prevent from tripping the internal
temperature protection fuse. The ESB303 is an active device. The distance between an ESB303 and the next active or
temperature sensitive device shall be 17,5mm. To a non-active device, the distance can be 0mm. The power
consumption of the device is 3.3W (3x1.1W per phase conductor) constant at 230Vac continuous operation. Make
sure that the ventilation holes below and above the unit are not blocked to allow free air convection. The neutral
must be connected to the device. If the neutral is not connected the ESB303 remains in the limiting mode. If so, the
device will overheat, and the internal temperature protection will irreversible blow.
Operation
Temperature
Ambient
Temperature
ESB303.LED.200/400
AC 16A current
ANSI / UL 508
-40°C … +55°C
CAN / CSA C22.2
-40°C … +55°C
IEC 61010-1
-40°C … +60°C
The distance between an ESB303 and the next active or temperature sensitive device shall be 17,5mm. To a non-active
device, the distance can be 0mm.
Table of the standards
Model
Camtec Article No.
EN 60950-1
EN 61010-1
EN 61004-1
VDE approval
ESB303.LED.200/400 3041114001CA
Yes
Yes
applicable
In preparation
Verkoopadres:
Advantec Electronics
, Industrieweg 10 G, 4731 SC Oudenbosch, Nederland, Tel: (31) 085 87 688 37