Overtemperature Thermal Shutdown, Over Voltage Protection & Derating 

OT  Over  Temperature

  The  maximum  ambient  temperature  is  +70°C.  If  the 

power  Supply  exceeds  this  value  (over  temperature  protection)  it  completely 
shuts  down  (metering  point  50mm  from  outside  device).  The  device  restarts 
automatically into operation when the temperature drops to a normal value.  
 

OVP  Over  Voltage  Protection 

Exceeding  the  OVP  results  into  ticker  mode. 

Resuming  the failure causes automatic restart  into normal operation. For the 
values please read the Technical Table on page 2.

 

 

Baseplate Cooling & Temperature Management 

The temperature management of the CPS-EC series provides a direct dissipation of the main energy losses. 
The internal coolers of the output diodes and the power FETs connect to the back-plate cooler. It is possible to 
dissipate about 40 – 50% of the energy losses out of a system while using the Baseplate cooling bundle 
2201002001 to hard mount the unit to a plane and heat conductive surface.  

 

Series Operation 

Two or more units of the same model and output voltage can be operated up to a total voltage of 600Vdc in 
series (not applicable with EN62368-1). The CPS-EC1500 models are to be operated with floating output when 
connected in series. Such the output terminals must not be connected to earth (GND/PE). Due to the dielectric 
strength of the internal components used, only the models with an output voltage of 90Vdc and later are 
approved for series operation. Other power supplies are not approved for series operation above 60Vdc. 
If the units are remotely controlled via the analog interface it is compulsory to use a potential-free control 
voltage!

 

 

Parallel Operation & Decoupling 

To increase the overall power of the power supply, two or more 
devices of the same model with the same output voltage may be 
operated in parallel. We recommend using a busbar for the DC power 
connector. Make sure that the cable lengths and cable cross-sections 
of all power supplies to the busbar or to the star point are identical. If 
you want to use the sensing function, connect it also to the star point 
or busbar. To avoid measurement errors, select the line length from 
the neutral point or from the busbar to the load as short as possible 
and use the maximum possible conductor cross-section 
 
The CPS-EC models have no internal O-ring diode, to operate the 
devices redundant N+1. 
 
 
 
 
 
 
 

 

Coating Option 

We offer the CPS-EC series with an optional coating. It is to be used in e.g. dusty, dirty, high humidity area or in 
awaiting quick temperature changes. Short circuit and corrosion at print board lines and at solder points can be 
prevented. The coat itself is a transparent acrylic resin.  
Peters SL 1306 N-FLZ (transparent) IEC60216-1 2001, IPC-CC-830B, UL listed as permanent coating  
File No.: E80315 , UL94V-0 
Ordering Information: add extension 

C

 to the model name (example): CPS-EC1500.048

C

(R2)

 

 

Содержание CPS-EC1500

Страница 1: ... 2V per load line Electronic inrush current limiter 20 7Apeak Inhibit function Interlock External shutdown Boost Charge Mode Precise dynamic response to load change Designed for long life under full stress Strong input filters Hold up time 20ms High reliability shock vibration proof Overload and short circuit protection Efficiency up to 94 EMI EMS EN61000 6 2 3 EN55032 EN61010 1 EN61010 2 201 EN62...

Страница 2: ...per margin is 0 5 The tolerance of the lower margin is 5 0 Output Current Monitoring The CPS EC power supply features a 0 5Vdc signal output It is a real time linear signal and indicates the current consumption of the load The measuring point is directly at the output connection of the device Boost Charge Mode The CPS EC1500 offers a boost charge mode The defined current limiting can be triggered ...

Страница 3: ...0Vac Inhibit Function Interlock Yes protective forced isolation to the inputs and the output 3000Vac Derating 60 C 70 C 2 5 C Accuracy 1 5 interface Load Regulation 0 05 0 100 Start up from Shutdown Typ 420ms Start up from Inhibit Typ 420ms Response to Load Change 1ms 10 100 100 10 Base Load None required open circuit proof Efficiency 230Vac 92 94 at 90 load Short Circuit Protection Continuous Ope...

Страница 4: ...ne AWG22 AWG6 0 25 1 5mm Sense Aux 3000Vac to input Boost Charge Open Collector AWG22 AWG6 0 25 1 5mm BC 3000Vac to input output Power Good Relay b contact AWG22 AWG6 0 25 1 5mm DC OK 3000Vac to input output can also be used with a simple passive switch All potentiometers and all the inputs and the outputs of the analogue interface provide a forced isolation It is to ensure a protective isolation ...

Страница 5: ...cause damages to the power supply unit To basically prevent from interferences enable to twist sense compensation lines To reduce inductive influences make sure that the load wires are installed close to each other Driving a pulsative load requires a large electrolytic and a ceramic capacitor Make sure that C1 C2 are not oscillating with load wires It would cause ripple voltage into the load lines...

Страница 6: ...ment range of the CPS EC series up to 400Vdc If the DC voltage is ok the relay is closed if the power supply unit is in false operation in the shutdown or in the inhibit mode the relay is open Considering the lower and the upper margin of the AC voltage detection it is to say that the CPS EC series starts at 150Vac The unit starts with 210Vdc when a DC voltage applies to the input The below table ...

Страница 7: ...argin the output voltage drops down and the unit delivers constant current Similar is when the upper margin of the voltage allows the current to be dropped by the power reduction behavior of the CPS EC series The C V setting must meet the Pmax 1500W Model Value UA1 V Value IA1 A Value UA2 V Value IA2 A Pmax CPS EC1500 024 30 50 0 24 62 5 1500 1500W CPS EC1500 036 45 33 3 36 41 7 1500 1501W CPS EC1...

Страница 8: ...8 1 The CPS EC1500 models are to be operated with floating output when connected in series Such the output terminals must not be connected to earth GND PE Due to the dielectric strength of the internal components used only the models with an output voltage of 90Vdc and later are approved for series operation Other power supplies are not approved for series operation above 60Vdc If the units are re...

Страница 9: ...test equipment raising the voltage slowly b Short circuit L1 and N and all the DC output terminals c Use only test voltages of 50 60Hz The outputs are unearthed and therefore they have no resistance to GND PE d If the residual voltage is 60Vdc observe the safety standards Use only specially insulated screwdriver to trim the Ua Ia Connections AC Main Input PE wire N wire L wire DC Mains DC voltage ...

Страница 10: ...t in injury or death Mechanics Mechanics Stable metal aluminum housing IP20 To allow adequate convection a free air space of 50mm top bottom and 5mm sidewalls is required for active devices 15mm space from the sidewalls For free air convection it is necessary to install the unit horizontal Use the DIN Rail installation equipped standard with the patented 35mm DIN Rail brackets according to EN60275...

Страница 11: ...and for active devices 15mm space from the sidewalls For proper air convection it is necessary to install the CPS EC1500 One can use the DIN Rail installation equipped standard with our patented 35mm DIN Rail bracket according to EN60275 It is easy to mount dismount while snaping it onto the 35mm DIN Rail no tools necessary A wall mount back plate option is available too It is not allowed to insta...

Страница 12: ... 46228 pt 1 min max 2 5 10mm 0 2 1 5mm Plug gauge in accordance with EN 60999 a x b ø 5 4 x 5 1mm 5 3mm 2 4 x 1 5mm 2 3mm Pitch P 10 16mm 3 5mm Wire Stripping Length fine wired Nominal Cross Section Wire End Ferrule Stripping Length Wire End Ferrule Stripping Length 0 25mm H0 25 5 5mm H0 25 10 HBL 8mm 0 5mm H0 5 6 6mm H0 5 12 OR 8mm 1 0mm H1 0 6 6mm H1 0 12 GE 8mm 2 5mm H2 5 12 12mm H2 5 19D BL 14...

Страница 13: ...ication loosening bolts or operation outside the specified herein specification or in an unsuitable environment has the immediate loss of warranty to follow We disclaim any responsibility for any resulting damage to persons or things 4 Note The device must not be operated without an upstream circuit breaker CB We recommend the use of B Type 16A It is prohibited to use the unit without PE It may be...

Отзывы: