background image

 

 

   

CPS-EC1000(R2) MANUAL

                 

Camtec Power Supplies GmbH  -  Gewerbestrasse 30  -  76327 Pfinztal  -  Germany      

P.7/12 (03.2022.00.0)

 

Phone +49(721)46596-0  -   Fax +49(721)46596-77  -   

www.camtec-gmbh.com

 - 

[email protected]

 

(Subject to alterations. This product is not designed to be used in applications such as life support systems wherein a failure or malfunction could result in injury or death) 

 

C/V Current Voltage Behaviour 

The CPS-EC series provides a perfect current voltage chart. It has no 
foldback or other abnormalities. The output voltage can drop down to zero 
volts when the power supply is overloaded. The unit delivers a stable and 
constant current to the outputs. The device can be used either in the CV or 
in the CC mode (automatic switch over). When the output voltage is set to 
the maximum demanded value and the current limit reaches its desired 
margin, the output voltage drops linear down to zero and the unit delivers 
constant current. Similar is when the upper margin of the voltage allows the 
current to be dropped by the power reduction behaviour of the CPS-EC 
series. The C/V setting must meet the Pmax = 1000W! 

Model 

Value UA1 (V) 

Value IA1 (A) 

Value UA2 (V) 

Value IA2 (A) 

Pmax 

CPS-EC1000.024 

30 

33,3 

24 

42,0 

1008W 

CPS-EC1000.036 

45 

22,2 

36 

28,0 

1008W

 

CPS-EC1000.048 

58 

17,2 

48 

21,0 

1008W

 

CPS-EC1000.060 

75 

13,3 

60 

16,7 

1008W

 

CPS-EC1000.072 

90 

11,1 

72 

13,9 

1008W

 

CPS-EC1000.110 

137,5 

7,3 

110 

9,1 

1008W

 

CPS-EC1000.150 

180 

5,6 

150 

6,7 

1008W

 

CPS-EC1000.220 

264 

3,8 

220 

4,5 

1008W

 

CPS-EC1000.300 

360 

2,8 

300 

3,33 

1008W

 

 

Inrush Current Limiter 

The unit is featured with an electronic inrush current limiter (ex. 230Vac = 9,8Arms / 13,8Apeak). The built-in 
circuit is a very precise limiter and no simple NTC thermistor solution. The circuit works with an accuracy of 
±10%. The accuracy is independent from the ambient temperature and from the number of switch-on 
sequences. The quickest recommended MCB is B-type 10A (230Vac) / 20A (115Vac). The smallest power 
relay or a contactor in front of the CPS-EC480 must cope 13,8A peak current (note 18,4A nominal 115Vac). 
The inrush duration is 400ms and the overall power up time of the unit is 500ms. See the below drawings for 
technical information. 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 

Overtemperature Thermal Shutdown, Over Voltage Protection & Derating 

OT  Over  Temperature

  The  maximum  ambient  temperature  is  +70°C.  If  the 

power  Supply  exceeds  this  value  (over  temperature  protection)  it  completely 
shuts  down  (metering  point  10mm  from  outside  device).  The  device  restarts 
automatically into operation when the temperature drops to a normal value.  
 

OVP  Over  Voltage  Protection 

Exceeding  the  OVP  results  in  a  locked 

shutdown  mode.  Resuming  the  failure  causes  automatic  restart  into  normal 
operation. For the values please read the Technical Table on page 2.

 

Содержание CPS-EC1000

Страница 1: ...1V per load line Electronic inrush current limiter 13 8Apeak Inhibit function Interlock External shutdown Efficiency up to 92 Precise dynamic response to load change Designed for long life under full...

Страница 2: ...with a 15 turns high precision potentiometer The listed values are guaranteed by the factory The tolerance of the upper margin is 0 5 The tolerance of the lower margin is 5 0 Output Current Monitorin...

Страница 3: ...to the inputs and the output 3000Vac Sense Function Compensation 1V per load line Remote Shutdown Yes protective forced isolation to the inputs and the output 3000Vac Inhibit Function Interlock Yes pr...

Страница 4: ...put Sense Compensation 1V per load line AWG22 AWG6 0 25 2 5mm Sense Aux 3000Vac to input Power Good Relay b contact AWG22 AWG6 0 25 2 5mm DC OK 3000Vac to input output All potentiometers and all the i...

Страница 5: ...ARNING Reverse polarity of the sense lines can cause damages to the power supply unit To basically prevent from interferences enable to twist sense compensation lines To reduce inductive influences ma...

Страница 6: ...setting for DC input supply The below table of values shows the hysteresis of the lower and upper threshold margins where the DC OK Relay indicates a low voltage The nominal voltage of the cell voltag...

Страница 7: ...48 21 0 1008W CPS EC1000 060 75 13 3 60 16 7 1008W CPS EC1000 072 90 11 1 72 13 9 1008W CPS EC1000 110 137 5 7 3 110 9 1 1008W CPS EC1000 150 180 5 6 150 6 7 1008W CPS EC1000 220 264 3 8 220 4 5 1008W...

Страница 8: ...lies from each other To increase the power capability RED models can be connected in parallel For higher voltages an external decoupling diode shall be installed from the system engineer Coating Optio...

Страница 9: ...in injury or death Mechanics Mechanics Stable metal aluminium housing IP20 To allow adequate convection a free air space of 50mm top bottom and 5mm sidewalls is required for active devices 15mm space...

Страница 10: ...and for active devices 15mm space from the sidewalls For proper air convection it is necessary to install the CPS EC1000 One can use the DIN Rail installation equipped standard with our patented 35mm...

Страница 11: ...46228 pt 1 min max 2 5 10mm 0 2 1 5mm Plug gauge in accordance with EN 60999 a x b 5 4 x 5 1mm 5 3mm 2 4 x 1 5mm 2 3mm Pitch P 10 16mm 3 5mm Wire Stripping Length fine wired Nominal Cross Section Wir...

Страница 12: ...g bolts or operation outside the specified herein specification or in an unsuitable environment has the immediate loss of warranty to follow We disclaim any responsibility for any resulting damage to...

Отзывы: