Manual und Technical Details 

 

Analogue Interface CON1 (Connector Model Weidmueller 1277320000 = included) 

Pin 

Name 

Type 

Function 

Signal 

Remarks 

AC OK-1 

Output 

Closers, Signal AC OK 

Relay 

Potential-free 

DC OK-1 

Output

 

Closers, Signal DC OK

 

Relay

 

Potential-free

 

AC OK-2 

Output

 

Center, Signal AC OK

 

Relay

 

Potential-free

 

DC OK-2 

Output

 

Center, Signal DC OK

 

Relay

 

Potential-free

 

AC OK-3 

Output

 

Break, Signal AC OK

 

Relay

 

Potential-free

 

DC OK-3 

Output

 

Break, Signal DC OK

 

Relay

 

Potential-free

 

SB 

Input 

Control Signal Standby

 

Switch / Open Collector 

 

SD 

Input 

Control Signal Shutdown 

Switch / Open Collector 

 

DGND 

Digital Ground 

 

10 

+12V AUX 

Output 

Auxiliary Voltage 

12Vdc/0,5A ±0,5V 30mVpp 

1000uF, O-Ring Diode 

11 

DGND 

Digital Ground 

 

12 

INH 

Input 

Control Signal Inhibit (Interlock) 

Switch 

 

Analogue Interface CON2 (Connector Model Weidmueller 1277330000 = included) 

Pin 

Name 

Type 

Function 

Signal 

Remarks 

DGND 

Digital Ground 

 

TEMP 

Output 

Temperature Control

 

Voltage 10mV/°C 

 

DGND 

Digital Ground

 

 

PSOT 

Output

 

Signal PowerSink Over Temperature

 

Open Collector 

 

DCF 

Output

 

Signal DC Failure

 

Open Collector 

 

ACF 

Output

 

Signal AC Failure

 

Open Collector 

 

FF 

Output

 

Signal Fan Failure

 

Open Collector 

 

INH 

Output

 

Signal Inhibit Active 

Open Collector 

 

OT 

Output

 

Signal Over Temperature 

Open Collector 

 

10 

TA 

Output

 

Signal Temperature Alarm 

Open Collector 

Early warning 

11 

OCP 

Output

 

Signal Over Current Protection 

Open Collector

 

 

12 

CC 

Output

 

Signal Constant Current Mode 

Open Collector

 

 

13 

OVP 

Output

 

Signal Over Voltage 

Open Collector

 

 

14 

CV 

Output

 

Signal Constant Voltage Mode 

Open Collector 

 

Analogue Interface CON3 (Connector Model Weidmueller 1277340000 = included) 

Pin 

Name 

Type 

Function 

Signal 

Remarks 

AGND 

Analog Ground 

 

Imon 

Output

 

Current Monitor

 

0-5Vdc / 5mA, 0-10Vdc / 5mA 

 

PS 

Output

 

Control Signal External PowerSink

 

Prepared Control Output 

 

Umon 

Output

 

Voltage Monitor

 

0-5Vdc / 5mA, 0-10Vdc / 5mA 

 

CS 

I/O

 

Current Share Bus (CSB)

 

Parallel Operation 

Bidirectional 

Ireg-OUT 

Output

 

Current Programming Slave

 

0-5V / 5mA 

 

AGND 

-

 

Analog Ground

 

 

Ureg-OUT 

Output

 

Voltage Programming Slave 

0-5V / 5mA 

 

AGND 

-

 

Analog Ground

 

 

10*

 

Iadj 

Output

 

Potentiometer Connection Current 

 

With external poti 

11 

Uref 

Output

 

Reference Voltage 

5,2Vdc / 5mA, 10,4Vdc / 5mA 

 

12*

 

Uadj 

Output

 

Potentiometer Connection Voltage 

 

With external poti 

13 

CS 

I/O

 

Current Share Bus (CSB) 

Parallel Operation 

Bidirectional

 

14 

Ireg-IN 

Input

 

Current Programming 

0-5V, 0-10V, 0-20mA, 4-20mA 

 

15 

AGND 

-

 

Analog Ground 

 

16 

Ureg-IN 

Input 

Voltage Programming 

0-5V, 0-10V, 0-20mA, 4-20mA 

 

Analogue Interface CON4 (Connector Model Weidmueller 1277290000 = included) 

Pin 

Name 

Type 

Function 

Signal 

Remarks 

Sense - 

Input 

Sense Connection 

2V / load line 
 

Sense - 

Input 

Sense Connection

 

-

 

3, 4 

 

 

NC 

Must not be connected

 

5, 6 

 

 

NC 

Sense + 

Input

 

Sense Connection

 

-

 

2V / load line 
 

Sense + 

Input

 

Sense Connection

 

-

 

PIN10/12*

 

when

 

no external control signal shall be used the device can be set with internal potentiometers. Please connect 

Pin10 with Pin14 and Pin12 with Pin16 to operate this mode. 

 

Содержание 3041107001CA

Страница 1: ...rogramming Real time I V monitoring Reference voltage f autonomous programming CSB Current Share Bus Inhibit for safe interlocking Remote Shutdown Remote Shutdown Power Good Relay AC ok and DC ok Precise dynamics on load change Series parallel operation up to 100kW EMC conducted class B radiated class A Efficiency 92 94 PFC Powerfactor 0 99 Variable controlled fans from Papst Long lifetime under h...

Страница 2: ...ign specifications call for the highest standards of safety and interference suppression The device was developed in accordance with the requirements of EN61010 1 EN61010 2 201 EN62368 1 and the EMC standards EN55032 conducted Class B radiated Class A The mechanical design of the CPS i3000 device series is unique It is the first power supply line in the world market which can be flexibly adapted t...

Страница 3: ... no ticker operation Master Slave Mode Ureg OUT Ireg OUT The master slave mode can be defined in the parallel operation One device can be set as the master the other involved network units act as a slave and the setting signals follow current voltage which are commanded by the Master This ensures that all devices are operated synchronously Current Share Bus CS In parallel operation the involved ne...

Страница 4: ...measuring point distance 10mm Hold Up Time 20ms 230Vac mains buffering at full load Inrush Current 14 6Aeff 20 7Apeak 230Vac active electronic inrush protection no simple NTC Startup Delay typ 1s Softstart typ 100ms Ambient Temperature 20 C 60 C operating derating 2 5 C 50 C Storage Temperature 40 C 85 C Ambient Conditions Humidity 95 non condensing 25 C climate class 3K3 pollution degree 2 ROHS 2...

Страница 5: ...Inhibit Active Open Collector 9 OT Output Signal Over Temperature Open Collector 10 TA Output Signal Temperature Alarm Open Collector Early warning 11 OCP Output Signal Over Current Protection Open Collector 12 CC Output Signal Constant Current Mode Open Collector 13 OVP Output Signal Over Voltage Open Collector 14 CV Output Signal Constant Voltage Mode Open Collector Analogue Interface CON3 Conne...

Страница 6: ...Tel 49 721 46596 0 Fax 49 721 46596 77 www camtec gmbh com info camtec gmbh com Subject to alterations This product is not designed to be used in applications such as life support systems wherein a failure or malfunction could result in injury or death Schematic of the internal circuits analogue interface CON1 4 ...

Страница 7: ...0 C 250Vac 20A Neutrik PowerCon 3x2 5 mm Neutrik NAC3FCA Copy of the original instruction http www neutrik com de powercon powercon 20 a nac3fca Interface pluggable Push Pull Connectors from Weidmueller included Input Power Connector Neutrik NAC3FCA included Output Power Connection M8 Powerbars Lock Pins snap into the 2U 3U 19 subrack WARNING OUTPUT CONNECTION INSTRUCTION Mount the cable lugs dire...

Страница 8: ...eries is an analog interface The output voltage is linearly proportional to the adjusted analog control signal If the control signal 0V and or 0A applies the power supply delivers 0V at the output The power supply is already working from 0V output voltage and low load with high precision The monitor signal is analog linear to the output voltage The monitor signal for current and voltage is the rea...

Страница 9: ...current to the output This special behaviour is a protection for the power supply and for the connected load Compensation of Load Line Drop Voltage Sense standard operation mode The CPS i power supply has a Sense Mode to compensate for the voltage drop over long load lines The compensation amounts to a maximum of 2V per load line Under certain circumstances it can be expected to apply more complic...

Страница 10: ...ribution in parallel operation of several identical CPS i units Define the power supply as the master which you want to address with your control A coding of the power modules as the master or the slave is required see below table The signals of the interface are looped together Connect Ureg OUT and Ireg OUT of the master to Ureg IN and Ireg IN from to slave Connect the corresponding Ureg OUT Ireg...

Страница 11: ...lternatively a voltage of 10 to 30V typ 12V 1 5mA 24V 5 5mA can be applied If the standby repeals the power supply starts with a delay of 500ms Using the soft start the current and the voltage rises within 100ms continuously to the default set values Between control input SB and power output is a reinforced isolation of max 400Vdc and a basic isolation of max 600Vdc working voltage Inhibit Interlo...

Страница 12: ...ay contacts changeover The contacts of CON1 Pin1 and CON1 Pin3 are closed relay coil is energized when the input voltage is higher than typ 175Vac or 210Vdc switch on The contacts of CON1 Pin5 and CON1 Pin3 are closed relay coil is not energized when the input voltage is lower than typical 165Vac or 145Vdc turn off Contact load resistive load 30Vdc 1A 60Vdc 0 3A 30Vac 0 5A Between the relay contac...

Страница 13: ...etween the TEMP signal and power output is a reinforced isolation of max 400Vdc and a basic isolation of max 600Vdc working voltage Temperature Control Signal PSOT of the PowerSink Fast Down Programming Option The PowerSink option has a temperature monitor The alarm signal PSOT is high when the internal PowerSink module is overheated Output Open Collector IMAX 10mA VLOW 0 6V VMAX 30V If PSOT is ac...

Страница 14: ...00A 24Vdc 125A 3000 3000W CPS i3000 060 60Vdc 50A 48Vdc 62 5A 3000 3000W CPS i3000 090 90Vdc 33 3A 72Vdc 41 5A 2997 2988W CPS i3000 150 150Vdc 20A 120Vdc 25A 3000 3000W CPS i3000 300 300Vdc 10A 240Vdc 12 5A 3000 3000W Inrush Current Limiter electronic The power supply unit has an electronic current limiter 230Vac 14 6Arms 20 7Apeak It is a precisely working circuit instead of a usual simple NTC so...

Страница 15: ...ther power supplies are not approved for series operation above 60Vdc If the units are remotely controlled via the analog interface it is compulsory to use a potential free control voltage Paralleling N 1 Decoupling To increase the overall power of the power supply two or more devices of the same model with the same output voltage may be operated in parallel When using the Current Share Bus the nu...

Страница 16: ...l Germany P 16 22 04 2016 01 5 Tel 49 721 46596 0 Fax 49 721 46596 77 www camtec gmbh com info camtec gmbh com Subject to alterations This product is not designed to be used in applications such as life support systems wherein a failure or malfunction could result in injury or death ...

Страница 17: ...al Safety Factory Test Field Test Owner 60Vdc 2800Vdc Type and factory test are the manufacturer While repating damage can happen to the power supply unit For the field test owner follow the below instruction a Use suitable test equipment raising the voltage slowly b Short circuit L1 and N and all the DC output terminals c Use only test voltages of 50 60Hz The outputs are unearthed and therefore t...

Страница 18: ...esult in injury or death Mechanics Aluminium housing IP20 Cooling is achieved via front to rear fans To ensure adequate heat dissipation 50mm to the front and 150mm blockade free distance from the device back wall must be guaranteed The harnesses are to be designed and installed to that the air outlet of the unit is not being blocked In a rack mounting of multiple subracks the rear distance of the...

Страница 19: ...electronic current sink is used the output voltage remains constant at the set value The current sink provides fast dynamic response Fig 1 Fig 2 Fig 3 A Power Sink see Fig 1 enables fast down programming at low load conditions or without a load For comparison see Figure 2 without and Figure 3 with PS option When paralleling the power supplies the SD SB and INH need to be connected in parallel to a...

Страница 20: ...www camtec gmbh com info camtec gmbh com Subject to alterations This product is not designed to be used in applications such as life support systems wherein a failure or malfunction could result in injury or death 19 Subrack 2U 3U 2U Subrack for 1 3 CPS i3000 with up to 9kW continuous power 3U Subrack for 1 5 CPS i3000 with up to 15kW continuous power ...

Страница 21: ... to custom design power supplies Steplessly hard mount of the CPS i2000 3000 power supply modules in a 3D room In practice that means that one can mount the modules into every angle imaginable Our 3D Heat Dissipation 3D HD ensures optimal cooling in each mounting position you may consider All you may consider is to make sure that at least a distance of 5cm 2 Inch to the front cooling slots and 15c...

Страница 22: ... 3U 5 Modules mountable only in conjunction with front panel 3U orderable 2201005001CA 19 Rack Rail 2x Support Rails for rack mount mounting kit included 2201008001CA Cable Management Rail Cable support for rack mount mounting kit included In preparation Hard Mount Holder narrow 2x Holder for strait wall mount mounting kit included 2201011001CA Hard Mount Holder flat 2x Holder for flat wall mount ...

Отзывы: