Section 6.  Troubleshooting

6-10

9.

If you don't see characters echoed on the screen then the problem could be with
the RAD modem or the computer's serial port.  Unplug the RAD modem from
the back of the computer.  The COM port will have either 9 or 25-pins.  The
pins are in two rows, with one row having one more pin then the other.

Call the row with the most pins as the top row.

Pin 1 is on the top row on the far left side.  Pins are counted from left to right
across the top row.

Get into TERM and go into terminal emulations.  Briefly touch the outer metal
shield around the pins to discharge any static electricity in your body.  Take a
small screwdriver and short pin 2 to pin 3 on COM port 1.  Be very careful not
to accidentally short any of the other pins, or short to the outer metal shield
around the connector.

Start typing.  You should see the key presses echoed on the screen.  If you don't
then you probably have a bad COM port and will need to replace it.

If you do see characters being typed then the modem could be bad.  

Call

Campbell Scientific

.

10. Remove the paper clips from the back of the RAD modem.  Reattach all the

wires to the RAD modem according to your wiring diagram.  Plug it back into
the computer's COM 1 port.

11. Take your paper, pen, and screwdrivers with you and go out to the weather

station.  Disconnect the SC932C from the datalogger and the RAD modem.
Verify the RAD modem is wired as shown in Figure 3.3-3 in this manual.

Keep in mind that the wires should ultimately be attached as follows:

TABLE 6-1.  RAD At Computer [Goes To] RAD At Datalogger

+RCV

+XMT

-RCV

-XMT

+XMT

+RCV

-XMT

-RCV

12. Disconnect the wires from the RAD modem.  Carefully twist the conductors of

the following wires together:

a. Twist the "-RCV" and "-XMT" wires together.

b. Twist the "+RCV" and "+XMT" wires together.

Make sure these wires don't touch anything else.

13. Take the RAD modem out of the enclosure and back to the computer

Test the RAD modem as explained in steps 2 - 11 in this section.

If the modem is bad, 

call Campbell Scientific

.

If the modem checks out then continue.

Содержание T. Weather 106

Страница 1: ...INSTRUCTION MANUAL T Weather 106 Weather Station Revision 9 02 C o p y r i g h t c 1 9 9 3 2 0 0 2 C a m p b e l l S c i e n t i f i c I n c...

Страница 2: ...other warranties expressed or implied including warranties of merchantability or fitness for a particular purpose CAMPBELL SCIENTIFIC INC is not liable for special indirect incidental or consequentia...

Страница 3: ...Enclosure Datalogger Power Supply 3 2 3 2 Sensor Connection 3 4 3 3 Communication and Data Storage Peripherals 3 5 3 4 Sealing and Desiccating the Enclosure 3 9 4 T Weather 106 Sensor Arm Installatio...

Страница 4: ...the T Weather 106 Enclosure 3 4 3 2 1 Position of Sensor Bulkhead Connectors 3 5 3 2 2 Default Sensor Switch Settings 3 5 3 3 1 Phone Modem Mounting and Connections 3 6 3 3 2 Short Haul Modem Mounting...

Страница 5: ...e tower assembling as much as possible Section 2 Repackage equipment for transport to the field site 1 1 2 Outdoors Locate suitable site Section 1 Prepare tower Section 2 T Weather 106 Stations Place...

Страница 6: ...rs small medium Small diagonal side cuts Needle nose pliers Wire strippers Pocket knife Calculator Volt Ohm Meter Electrical Tape Step ladder 6 Datalogger prompt sheet Section 6 Station manuals Statio...

Страница 7: ...988 1 WMO 1983 2 and AASC 1985 3 publications 1 3 1 Wind Speed and Direction Wind sensors should be located over open level terrain and at a distance of at least ten times EPA the height of any nearby...

Страница 8: ...USFA map local airport or through a computer service offered by the USFS called GEOMAG Section 1 4 1 A general map showing magnetic declination for the contiguous United States is shown in Figure 1 4...

Страница 9: ...agnetic declination and annual change The following information menu and prompts are from GEOMAG GEOMAG is a user friendly program that provides estimates of the geomagnetic field elements including d...

Страница 10: ...AG Model USCON90 Latitude 42 2 N Date 7 27 93 Longitude 111 51 2 W Elevation 4454 0 ft D deg min 15 59 6 Annual change 0 6 1 Exiting Press Cntrl Z to exit GEOMAG When the main menu reappears either se...

Страница 11: ...n 1 Preparation and Siting 1 7 FIGURE 1 4 2 Declination Angles East of True North Are Subtracted From 0 to Get True North FIGURE 1 4 3 Declination Angles West of True North Are Added to 0 to Get True...

Страница 12: ...Section 1 Preparation and Siting 1 8 This is a blank page...

Страница 13: ...ime Once attached they cannot be detached The T Weather 106 Tower provides a support structure for mounting the T Weather 106 weather station components Figure 2 1 1 shows a typical T Weather 106 Towe...

Страница 14: ...ld be about 4 inches deep and just large enough in diameter to insert one end of the conduit Make certain the cavity points in the direction from which power and communications cables will come 6 Cent...

Страница 15: ...ble Refer to Section 1 for components supplied by installer 2 2 2 Installation Attach the tower to the base as shown in Figure 2 2 1 1 Dig a hole close to the concrete base to access the lower conduit...

Страница 16: ...lower it onto the conduit and mounting bolts Install a washer and nut on each bolt and hand tighten Check plumb of the tower by placing a level on the north and east sides of the lower tower section A...

Страница 17: ...to the foundation using a fence post driver or sledge hammer Drive the rod at an angle if an impenetrable hardpan layer exists Soften hard clay soils with water if necessary 3 Strip 1 inch of insulat...

Страница 18: ...Section 2 T Weather 106 Tower Installation 2 6 This is a blank page...

Страница 19: ...e T Weather 106 enclosure at the locations shown in Figure 3 1 Components include 1 T Weather 106 Enclosure 1 4 unit Desiccant Pack 1 Flat Point Screw Driver 1 Phillips Screwdriver 1 Power Supply Opti...

Страница 20: ...to 24 VAC must be used with the rechargeable battery at all times In either case power is routed through the Heyco fitting on the enclosure back and connected to the CHG ports by depressing connector...

Страница 21: ...ng wire ties Make electrical connections as described in 3 1 1a above 3 1 3 AC Power Installation a The AC power option includes a 120 VAC to 16 VAC The transformer should be mounted inside a user sup...

Страница 22: ...uld be taken not to scratch the enclosure or sensor assembly Strip 1 inch of insulation from the top end of the 12 AWG green tower ground wire curl the end and place the curled end under the head of o...

Страница 23: ...s are installed Ensure that all cables and connector caps are under the cover before tightening the screws 4 Configure sensor switch settings as shown in Figure 3 2 2 if necessary Open 604 Ohm 100 Ohm...

Страница 24: ...3 3 1 1 Internal Installation For installation inside the T Weather 106 Enclosure the following components are provided in the phone modem kit 1 COM200 or COM300 Phone Modem 1 12 inch RJ 11 Patch Cor...

Страница 25: ...splice kit when splices are in a valve box or buried 3 3 2 Short Haul Modem Short haul modems enable communication between a datalogger and computer over two twisted pairs of wires The maximum distanc...

Страница 26: ...At the T Weather 106 Enclosure 1 20 foot 4 Wire Patch Cable 2 2 Direct Burial Splice Kits 1 Length of User Supplied Wire Supplier Anixter p n F 02P22BPN Phone 847 677 2600 At the PC 1 Rad Modem 1 5 fo...

Страница 27: ...3 4 Sealing and Desiccating the Enclosure The T Weather 106 Enclosure is supplied with a desiccant pack The desiccant maintains a low humidity in the enclosure to minimize the chance of condensation o...

Страница 28: ...OURS AT 250 F DESICCANT ACTIVATED BAGGED FOR CONTENTS 4 UNITS PACKAGE USE AND STATIC DEHUMIDIFICATION DO NOT EAT UNITED DESICCANTS GATES 101CHRISTINE BELEN NEW MEXICO 87002 DESI PAK SPECIFICATION MIL...

Страница 29: ...or arm as shown in Figure 4 2 1 without the wind sensor attached Screws 4 FIGURE 4 2 1 T Weather 106 Sensor Arm Mounting 1 Remove the cover from the Enclosure 2 Place the sensor arm on top of the encl...

Страница 30: ...R10KD Keyboard Display or a laptop PC FIGURE 4 4 1 Wind and RH Temperature Sensor Installation 1 Place the 034A in the 034A Mounting Shaft pointing the vane due south Tighten the alignment screw 2 Att...

Страница 31: ...the red cap from the pyranometer FIGURE 4 6 1 Pyranometer Leveling Check the measurements of all sensors after the datalogger is programmed Display measurements using the 6 Mode with the CR10KD Input...

Страница 32: ...Pin Datalogger Relative Humidity 0 1VDC Air Temperature 0 1VDC 12V Switched Supply Not Used Analog Ground Shield 1 2 3 4 5 6 1 H 1 L 12VDC Switched Supply AG G FIGURE 4 7 1 Schematic of HMP45C LC RH a...

Страница 33: ...ot Used 3 H 3 L G Shield 4 5 6 1 2 3 4 5 6 FIGURE 4 7 3 Schematic of LI200X LC Solar Radiation Sensor and Connector 3 1 Not Used Connector Pin Magnetically Activated Reed Switch Tipping Rain Bucket No...

Страница 34: ...Section 4 T Weather 106 Sensor Arm Installation 4 6 This is a blank page...

Страница 35: ...weather station that includes serial numbers dates that the site was visited and maintenance that was performed 5 1 1 Instrumentation Maintenance The instrumentation requires a minimum of routine main...

Страница 36: ...r contamination General Maintenance An occasional cleaning of the glass on the solar panel will improve its efficiency Check sensor leads and cables for cracking deterioration proper routing and strai...

Страница 37: ...ng the Keypad Check keypad response after each of the following steps A Make sure the battery has been installed and the power switch if any is ON Section 6 5 B Use a voltmeter to measure the voltage...

Страница 38: ...modem end 2 3 3 2 4 20 5 7 F Make sure the modem is properly configured and cabled Section 6 6 G If still no response call Campbell Scientific 5 2 3 99999 Displayed in an Input Location A Make sure th...

Страница 39: ...re at the Weather Station The inside of the enclosure can be broken up into three basic areas see Figure 6 2 1 1 The communication option short haul or phone modem which mounts towards the top 2 The a...

Страница 40: ...1 Short Haul Modem Mounting and Connection LA ALK CHG PHONE MODEM Vo GND RH 604 OHM OPEN 100 OHM 5V CHG XMT XMT RCV RCV GND EXT 12V GND 12V 12VSW 6L 10 1 6H BATTERY CS I O 1K OPEN MADE IN USA OPEN SW...

Страница 41: ...plugs directly into the RJ 11 jack inside the enclosure for phone line access A ribbon cable runs between the COM200 and the 9 pin plug marked CS I O The COM200 requires two power supplies to operate...

Страница 42: ...s been lost if the voltage measured is 12 5 VDC or less The datalogger needs a minimum of 9 6 VDC to operate The battery cannot be deep discharged Once voltages get below 11 0 VDC the battery is damag...

Страница 43: ...should be identical to the battery voltage If these voltages are not present or incorrect then unplug the ribbon cable from the CS I O plug and repeat the measurements at the plug If the measurements...

Страница 44: ...troubleshooting tools is the CR10KD from Campbell Scientific The keypad can quickly verify whether the 5 VDC supply is operational if the program in the weather station is running battery voltage lev...

Страница 45: ...o that parameter then use the Tab key to change it After completing changes or to exit the station file window press Enter until you see the save options area Press s to save the file and return to th...

Страница 46: ...lowatts per meter2 4 TEMP C air temperature in degrees Celsius 5 RH percentage relative humidity 6 WS wind speed in miles per hour 7 RAIN rainfall for the past minute in inches 8 WD wind direction in...

Страница 47: ...same colored wires then wrap a piece of tape around one of them or mark it with a pen It is crucial that the wiring is put back in the correct order 5 Disconnect all the wires from the RAD modem Make...

Страница 48: ...OM port and will need to replace it If you do see characters being typed then the modem could be bad Call Campbell Scientific 10 Remove the paper clips from the back of the RAD modem Reattach all the...

Страница 49: ...ad low ohms Untwist the wires that were connected in step 12 of this section Measure across all the wires in any order you want The meter should read infinite resistance across any set of wires If the...

Страница 50: ...mal movement The older buckets did not have the drain plug on the bottom of the bucket that blocks entry of pests The newer buckets do have this plug but it won t stop the spiders The bucket needs to...

Страница 51: ...This is a blank page...

Страница 52: ...campbellsci com br suporte campbellsci com br Campbell Scientific Canada Corp CSC 11564 149th Street NW Edmonton Alberta T5M 1W7 CANADA www campbellsci ca dataloggers campbellsci ca Campbell Scientifi...

Отзывы: