Appendix A. Making Concurrent Measurements with the SR50
A-
2
Place measurement in Loc X.
If measurement is > -1000 then use measurement
Else
Add 1 to a counter
If the counter = 3 (means there were 3 bad readings in a row) then do:
Use bad reading for measurement.
Reset counter.
Example Program:
In this example, an SR50 is mounted 2 meters above the ground. Snow depth
and measurement quality numbers are the desired output. This program uses
Instruction 105 (refer to Section 9 in the CR10X manual for details on P105
SDI-Recorder Instruction) to obtain a distance measurement from the SR50.
The SR50’s address is 0. It is assumed that a Campbell Scientific 107
Temperature Probe is being used and that the SR50 SDI-12/DATA Bus line
(green wire) is wired to control port 1(see Figure 2, page 6 for wiring
diagram).
;{CR10X}
;
*Table 1 Program
01: 5
Execution
Interval
(seconds)
1: Temp (107) (P11)
; Measure air temperature
1: 1
Reps
2: 1
SE
Channel
3: 1
Excite all reps w/E1
4: 1
Loc [ AIR_TEMP ]
5: 1
Mult
6: 0
Offset
2: Z=X+F (P34)
; Convert Celsius reading to Kelvin
1: 1
X Loc [ AIR_TEMP ]
2: 273.15 F
3: 2
Z Loc [ T_KELVIN ]
; Measure the SR50 using Concurrent Measurement ability...
3: SDI-12 Recorder (P105)
1: 0
SDI-12
Address
2: 1 --
Start Measurement (aM1!)
; <<<< Configured to provide distance with
3: 1
Port
; echo quality numbers and do concurrent measurement
4: 3
Loc [ Raw_Dist ]
5: -1.0
Mult
6: 0.0
Offset
; Check to see if a valid measurement has been returned, and if it has, move
; the measurement to another Input Location to be used as data and reset the
; failure counter.