4. RS-485 default configuration
The default RS-485 settings are: 19200 baud rate, 8 data bits, even parity, one stop bit. This
configuration is used for most Modbus networks.
5. SR20-D2 register map
(p. 4) provides the register map for the most commonly used values. A comprehensive
register map is available in the Hukseflux manual.
Table 5-1: RS-485 register map
Starting
Register
Number
Register
Count
Data Format
Units
Description
1
1
Signed 16 bit integer
Modbus address
3
2
Signed 32 bit integer
mW/m
2
Irradiance (temperature
compensated signal)
5
2
Signed 32 bit integer
mW/m
2
Irradiance (temperature
uncompensated signal)
7
1
Signed 16 bit integer
0.01 °C
Sensor body temperature
8
1
Signed 16 bit integer
x 0.1 Ω
Sensor electrical resistance
9
1
Signed 16 bit integer
Scaling factor irradiance
10
1
Signed 16 bit integer
Scaling factor temperature
11
2
Signed 32 bit integer
nV
Sensor voltage output
41
1
Signed 16 bit integer
Serial number
42
2
Float
µV/W/m
2
Sensor sensitivity
47
2
Signed 32 bit integer
Calibration date
99
1
Signed 16 bit integer
x 0.01 %
Humidity
SR20-D2 ISO Spectrally Flat Class A (Secondary Standard) Pyranometer
4