SDM-CD16AC 16 Channel AC/DC Controller
9: Else (P94)
Else, If the heater is off,
10: Z=F (P30)
1: 0
F
Enter a "0" into heater
2: 0
Exponent of 10
control location
3: 10--
Z Loc :
11: End (P95)
End Then Do/Else/End
END HEATER CONTROL LOGIC
START COOLER CONTROL LOGIC
12: If X<=>F (P89)
If "Cooler" on
1: 1--
X
Loc
threshold is
2: 3
>=
exceeded
3: 27.5
F
4: 30
Then
Do
Then
13: Z=F (P30)
Put a "1" into cooler
1: 1
F
Control Location
2: 0
Exponent of 10
3: 15--
Z Loc :
14: End (P95)
End Then Do/End
15: If X<=>F (P89)
If cooler is on
1: 15--
X
Loc
(Cooler control
2: 2
<>
Location <>0)
3: 0
F
4: 30
Then
Do
Then
16: If X<=>F (P89)
Check lower threshold to
1: 1--
X
Loc
see if cooler should be
2: 4
<
turned off
3: 24.5
F
4: 30
Then
Do
17: Z=F (P30)
If cooler should be turned
1: 0
F
off, put a "0" into cooler
2: 0
Exponent of 10
control location
3: 15--
Z Loc :
18: End (P95)
End Then Do/End
19: Else (P94)
Else if cooler is off
20: Z=F (P30)
1: 0
F
Put a "0" into cooler
2: 0
Exponent of 10
control location
0: 15--
Z Loc :
13