background image

SECTION 1.  WEATHER STATION DESCRIPTION AND INSTALLATION

1-6

1.4.  MAST INSTALLATION

INSTRUCTIONS

The tower mounts on a cement foundation as
shown in figure 1.4-1. Provided with the tower is
a tilt base (figure 1.4-2), anchor bolts, and nuts.
The tilt base will also be used as a template.

Step 1 

 Dig a 24" square hole that is 24"

deep. These estimates are for heavy soils only;
light, shifting, or sandy soils require a deeper
base (and more cement).

Step 2 

 Approximately 0.3 cubic yards of

cement is required to fill the hole. While the
cement is setting, assemble the template (tilt
base) and anchor bolts (figure 1.4-1). Set the
anchor bolts in the cement leaving the threaded
end of the bolts a minimum of 2" above the
cement (Figure 1.4-1).  This will allow the tower
base to rest on the double nuts about 1 1/4"
above the cement surface. Be sure to level the
base!
  Allow time for the cement to setup
before mounting the tower.

NOTE: For light, sandy, or shifting soils, the
size of the concrete block should be
increased.

1.4.1  WEATHER STATION ASSEMBLY

To complete the installation of the weather
station, the following tools will be needed.

• 

screw drivers (regular and Phillips)

• 

open end wrenches (7/16, 1/2, 9/16)

• 

level

• 

pipe wrench

• 

tape measure

• 

step ladder (the crossarm is over 10 feet
high requiring a ladder to level sensors)

• 

compass (recommended for orienting wind
direction sensor)

Step 1 

 Remove the crossarm cover and

assemble the sensors on the ends of the
crossarm (Figure 1.3-2).  Note:  For proper
crossarm orientation refer to (Figure 1.4-3).

Step 2 

 Place the crossarm in front of you

with the 1 5/8" hole on the left (Channel up).

Step 3 

 Mount the wind set on the left side.

Mount the wind set so that the wind speed is on
the side closest to you.

Step 4 

 Mount the solar radiation and rain

gage sensors on the opposite side of the
crossarm.  Note: Insert the sensor cables
through the grommet slots to the center of the
crossarm and out the 1 1/2" center hole before
mounting the sensors.

Step 5 

 Mount the radiation shield into the 1

5/8" diameter hole on the underside of the
crossarm. Insert the temperature and Relative
Humidity (RH) sensor into the radiation shield.
Make sure that the temperature and RH sensor
is properly seated into the radiation shield.

Step 6 

 Apply Teflon pipe dope to the 54" X 1

1/2" mast pipe.  Thread the sensor cable
through the mast.  Screw the pipe onto the
crossarm and allow pipe to rotate around
sensor cables.

Step 7 

 Place mast into the tower and secure

the mast with the set screw.  Replace the
crossarm cover using the six screws.

Step 8 

 After the cement has setup, mount

the tower onto the base.

NOTE:  align the crossarm on the ground
east-west.  The radiation shield and the
wind set should be mounted on the west
side. The wind direction sensor mounts on
the north side and the wind speed on the
south (figures 1.3-2 and 1.4-3).  Use a
compass for accurate alignment.

Step 9 

 Vertical plumb the mast using the

adjustment nuts on the tilt base and the level.
Getting the bottom tower section plumb is very
important.  As concrete is poured into the hole,
periodically check the tower for plumb using a
carpenters level and make adjustments as
necessary (Figure 1.4-4).

Step 10 

 Level the solar radiation and rain

gage sensors. Attach the lightning rod to the 1
1/2" pipe just below the crossarm.

Step 11 

 Mount the enclosure on the tower

approximately 36 inches below the crossarm
(Figure 1.3-2).

Содержание NW8002

Страница 1: ...NW8002 WEATHER STATION INSTALLATION INSTRUCTION MANUAL REVISION 3 97 COPYRIGHT c 1991 1997 CAMPBELL SCIENTIFIC INC...

Страница 2: ...antability or fitness for a particular purpose CAMPBELL SCIENTIFIC INC is not liable for special indirect incidental or consequential damages Products may not be returned without prior authorization T...

Страница 3: ...HOOTING 3 1 3 1 Communication Testing 3 1 3 2 Sensors 3 3 3 3 Datalogger 3 5 FIGURES 1 2 1 Effect of Structure on Wind Flow 1 2 1 3 1 NW8002 Enclosure with RAD Connection 1 3 1 3 2 NW8002AC SP Weather...

Страница 4: ...Probe Assembly 2 3 3 1 1 RAD Testing Computer End 3 1 3 1 2 RAD Testing Datalogger End 3 2 3 2 1 4831 Temperature Relative Humidity Probe Assembly 3 5 TABLES 1 2 1 Approximate Range Miles 1 1 1 5 1 P...

Страница 5: ...0 C Operating relative humidity range 0 to 100 non condensing SENSOR SPECIFICATIONS Temperature Range 35 C to 48 C Accuracy 4 C typically better than 2 C Relative Humidity Range 12 97 RH Accuracy 5 Wi...

Страница 6: ...anted earth This allows the temperature and humidity readings to closely correspond with that of the turf the ET value is to represent 3 The radiation shield that covers the probe provides protection...

Страница 7: ...ne modem for use with Mir 5000 systems only Figure 1 9 1 PS12 LA 12 V Rechargeable Battery Sensors Figure 1 3 2 4776 Li Cor Solar Radiation Sensor 6575 HMP35C Temperature and RH Probe 4830 Texas Elect...

Страница 8: ...SECTION 1 WEATHER STATION DESCRIPTION AND INSTALLATION 1 3 FIGURE 1 3 1 NW8002 Enclosure with RAD Connection...

Страница 9: ...SECTION 1 WEATHER STATION DESCRIPTION AND INSTALLATION 1 4 FIGURE 1 3 2 NW8002AC SP Weather Station Cross Arm Detail...

Страница 10: ...SECTION 1 WEATHER STATION DESCRIPTION AND INSTALLATION 1 5 FIGURE 1 3 3 NW8002AC Weather Station...

Страница 11: ...ft Channel up Step 3 Mount the wind set on the left side Mount the wind set so that the wind speed is on the side closest to you Step 4 Mount the solar radiation and rain gage sensors on the opposite...

Страница 12: ...1 7 FIGURE 1 4 1 NW8002 Cement Base FIGURE 1 4 2 NW8002 Tower with Tilt Base...

Страница 13: ...SECTION 1 WEATHER STATION DESCRIPTION AND INSTALLATION 1 8 FIGURE 1 4 3 NW8002AC SP Weather Station Top View FIGURE 1 4 4 Plumbing NW8002 Tower...

Страница 14: ...mits current from the battery and provides circuitry to connect an external 12 volt battery The terminals on the PS12 are exposed by unscrewing the two set screws as shown in Figure 1 5 1 The two 12 v...

Страница 15: ...gas may be generated at a rate sufficient to create a hazard Campbell Scientific makes the following recommendations 1 A CR10 equipped with standard lead acid batteries should NEVER be used in applic...

Страница 16: ...SECTION 1 WEATHER STATION DESCRIPTION AND INSTALLATION 1 11 FIGURE 1 6 1 NW8002SP Weather Station...

Страница 17: ...SECTION 1 WEATHER STATION DESCRIPTION AND INSTALLATION 1 12 FIGURE 1 6 2 NW8002 Weather Station Sensor Connection...

Страница 18: ...modems Installation is as follows 1 Select a direct burial cable with two twisted pairs Two recommended types of cable are Two Cables Toro shielded armored cable P 7162 D A 1 or Anixter F 02P22BPN Rod...

Страница 19: ...SECTION 1 WEATHER STATION DESCRIPTION AND INSTALLATION 1 14 FIGURE 1 8 1 RAD Modem Connection and Grounding...

Страница 20: ...the computer site to communicate with the weather station The DC112 comes from the factory connected to the datalogger inside the enclosure Figure 1 9 1 The burial phone cable is routed through the b...

Страница 21: ...SECTION 1 WEATHER STATION DESCRIPTION AND INSTALLATION 1 16 FIGURE 1 9 1 NW8002 Enclosure with DC112 Phone Modem Option Use with MIR 5000 Systems Only...

Страница 22: ...2 1 Look for possible cable damage on any sensors and record all inspection findings in log section 2 4 2 2 MONTHLY 2 2 1 RAIN GAGE Check the rain gage funnel and tip mechanism Be sure screen inside f...

Страница 23: ...pes of Temperature Relative Humidity Sensors which you may have Refer to the cleaning procedures for your particular system below 2 3 2 TEMPERATURE RELATIVE HUMIDITY SYSTEMS SHIPPED AFTER JANUARY 1 19...

Страница 24: ...screen off and thoroughly clean the screen DO NOT TOUCH THE RELATIVE HUMIDITY CHIP Remember that while the sensor is rugged the function of it is to sense water vapor in the air therefore careful han...

Страница 25: ..._ _____ ____________________________ _____ ____________________________ _____ ____________________________ _____ ____________________________ _____ ____________________________ _____ _________________...

Страница 26: ...____________________ _____ ____________________________ _____ ____________________________ _____ ____________________________ 2 TO 3 MONTH Rain Gage Inspect and clean if necessary Date OK Comments ___...

Страница 27: ...spect and spin each sensor Date OK Comments _____ ____________________________ _____ ____________________________ _____ ____________________________ _____ ____________________________ _____ __________...

Страница 28: ...sor leads for damage or corrosion Also check leads at terminal strip of datalogger to be sure that leads are securely fastened b Use circuit diagrams in Appendix and Section 2 3 to ohm out defective s...

Страница 29: ...ill has not been established go to Sections 3 1 thru 3 3 to test the datalogger If the datalogger test passes then the SC932 is suspect and will need to be repaired or replaced 3 1 2 TESTING THE SC95C...

Страница 30: ...circuits Section 3 2 1 or the CR10KD Keyboard Display can be connected to the CR10 to check sensor reading values Section 3 3 1 Table 2 1 3 2 1 OHM METER TESTS OF SENSORS All sensors that are to be c...

Страница 31: ...f you are suspecting improper readings and if facilities exist the temperature and relative humidity probe should be placed in a sealed container over deionized water for two hours After two hours it...

Страница 32: ...OTE Contact your Toro distributer for RH chip replacement 3 3 DATALOGGER CR10 The CR10 is the heart of the weather station it measures the sensors outputs and converts the measurements to engineering...

Страница 33: ...CR10 Temperature and 10 Battery Voltage If the datalogger is not operating properly the CR10 Temperature will not record a reasonable value The battery voltage should read no less than 11 76 volts If...

Страница 34: ...A 1 APPENDIX A SENSOR SCHEMATICS...

Страница 35: ...APPENDIX A SENSOR SCHEMATICS A 2...

Страница 36: ...APPENDIX A SENSOR SCHEMATICS A 3...

Страница 37: ...APPENDIX A SENSOR SCHEMATICS A 4...

Страница 38: ...APPENDIX A SENSOR SCHEMATICS A 5...

Страница 39: ...APPENDIX A SENSOR SCHEMATICS A 6...

Отзывы: