Appendix C. EasyFlux
®
DL CR6KH20
C-11
TABLE C-12. Default Wiring for Non-Calibrating Soil Heat Flux Plates
Sensor
Quantity
Wire Description
Color
VOLT116 Terminal
HFP01 #2
1
Signal
White
Diff 6H
Signal Reference
Green
Diff 6L
Shield
Clear
⏚
HFP01 #3
1
Signal
White
Diff 7H
Signal Reference
Green
Diff 7L
Shield
Clear
⏚
TABLE C-13. Default Wiring for Soil Heat Flux Plates (Self Calibrating)
Sensor
Quantity
Wire Description
Color
VOLT116 Terminal
HFP01SC #1
1
Signal
White
Diff 5H
Signal Reference
Green
Diff 5L
Shield
Clear
⏚
Heater Signal
Yellow
Diff 13H
Heater Reference
Purple
Diff 13L
Shield
Clear
⏚
Heater Power
Red
SW12-1
1/
Power Reference
Black
G
HFP01SC #2
1
Signal
White
Diff 6H
Signal Reference
Green
Diff 6L
Shield
Clear
⏚
Heater Signal
Yellow
Diff 14H
Heater Reference
Purple
Diff 14L
Shield
Clear
⏚
Heater Power
Red
SW12-1
1/
Power Reference
Black
G
HFP01SC #3
1
Signal
White
Diff 7H
Signal Reference
Green
Diff 7L
Shield
Clear
⏚
Heater Signal
Yellow
Diff 16H
Heater Reference
Purple
Diff 16L
Shield
Clear
⏚
Heater Power
Red
SW12-2
1/
Power Reference
Black
G
1/
The SW12 terminals on the VOLT116 are limited to 200mA output. Accordingly, no more than two
HFP01SC sensors may be connected to each terminal. Connect heater power wires from HFP01SC #1 and #2
to SW12-1, and connect heater wires from HFP01SC #3 to SW12-2.