Campbell CS506 Скачать руководство пользователя страница 11

CS506 Fuel Moisture Sensor 

5.  Datalogger Programming 

This section is for users who write their own datalogger programs.  A 
datalogger program to measure this sensor can be created using Campbell 
Scientific’s Short Cut Program Builder software.  You do not need to read this 
section to use Short Cut. 

The CS506 has a built in enable circuit.  When voltage on the enable lead is 
less than 1 VDC, the sensor is off.  When a voltage greater than 4 VDC, 
commonly 5 VDC, is applied to the enable lead, the sensor is on.  The output 
signal is a 

±

0.7 volt square wave.  The CRBasic instruction PeriodAvg is used 

with the CR800-series, CR1000, and CR3000 dataloggers to measure the 
period of the output signal in microseconds on a single-ended analog input 
channel.  For Edlog dataloggers, instruction P27 Period Average may be used 
with the CR500, CR510, CR10, CR10X, and CR23X dataloggers.  The CS506 
is not compatible with 21X, CR7, or CR200-series dataloggers. 

Since fuel moisture does not change very rapidly, the sensor is typically 
measured only once per hour. 

After the period of the output signal in microseconds is measured it is 
converted to percent water content using one of two equations: 

θ(τ 

≤ 

17.7)

 = 7.6298

τ

 -130.0904 

θ(τ > 17.7)

 = 0.0406

τ

2

 + 3.7685

τ

 - 73.7974 

where 

θ

 is the percent of water by weight in the fuel moisture stick and 

τ 

is 

period average in microseconds. 

There is a slight disconnect in the two equations at 17.7 

μ

s where the linear 

equation gives a water content of 4.98% while the quadratic equation gives 
5.68%.  A sudden small increase or decrease in the measured water content 
near 5% is to be expected as the datalogger changes from one equation to the 
other. 

TABLE 5-1.  Wiring for Example Programs 

Color CR1000 CR10X 

Red 

12 V 

12 V 

Black G 

Green SE1 

SE1 

Orange C1 

C1 

Clear 

 

 

Содержание CS506

Страница 1: ...CS506 Fuel Moisture Sensor Revision 3 12 C o p y r i g h t 1 9 9 8 2 0 1 2 C a m p b e l l S c i e n t i f i c I n c...

Страница 2: ......

Страница 3: ...emoving reinstalling and shipping defective products to Campbell Campbell will return such products by surface carrier prepaid within the continental United States of America To all other locations Ca...

Страница 4: ...g container Campbell Scientific s shipping address is CAMPBELL SCIENTIFIC INC RMA _____ 815 West 1800 North Logan Utah 84321 1784 For all returns the customer must fill out a Statement of Product Clea...

Страница 5: ...ion 1 2 Specifications 1 3 Installation 2 4 Wiring 4 5 Datalogger Programming 5 5 1 CR1000 Programming 6 5 2 CR10X Programming 7 6 Maintenance 8 Figures 3 1 Back view of the 26817 fuel moisture temper...

Страница 6: ......

Страница 7: ...lity and to allow probe interchangeability without individual calibration two additional sorts are performed on the dowels before they are selected to be used as a sensor First the dowels are sorted d...

Страница 8: ...ions Dowel 1 3 cm 1 2 in diameter 50 8 cm 20 in long Electronics 10 2 x 6 4 x 1 9 cm 4 x 2 5 x 0 75 in The above accuracy is a static accuracy derived at slow changing conditions with experimental dat...

Страница 9: ...t resistant cable ties One cable tie passes through the two slots where the fuel moisture stick attaches to the CS506 sensor in order to loosely secure the cable of the CS205 107 The other two cable t...

Страница 10: ...ataloggers are given in Table 4 1 When Short Cut for Windows software is used to create the datalogger program the sensor should be wired to the channels shown on the wiring diagram created by Short C...

Страница 11: ...n P27 Period Average may be used with the CR500 CR510 CR10 CR10X and CR23X dataloggers The CS506 is not compatible with 21X CR7 or CR200 series dataloggers Since fuel moisture does not change very rap...

Страница 12: ...ts FuelM Units PA_uS uSec Define Data Tables DataTable Table1 True 1 DataInterval 0 60 Min 10 Sample 1 FuelM FP2 Sample 1 PA_uS FP2 EndTable Main Program BeginProg Scan 10 Sec 1 0 CS506 Fuel Moisture...

Страница 13: ...2 1 0 Minutes Seconds into a 2 60 Interval same units as above 3 30 Then Do 2 Do P86 1 41 Set Port 1 High 3 Period Average SE P27 1 1 Reps 2 4 200 kHz Max Freq 2 V Peak to Peak Period Output 3 1 SE Ch...

Страница 14: ...ea P80 18555 1 1 Final Storage Area 1 2 60 Array ID 13 Real Time P77 12334 1 1220 Year Day Hour Minute midnight 2400 14 Sample P70 15015 1 2 Reps 2 1 Loc PA_uS 6 Maintenance The sensor dowel rod shoul...

Страница 15: ......

Страница 16: ...ntific Canada Corp CSC 11564 149th Street NW Edmonton Alberta T5M 1W7 CANADA www campbellsci ca dataloggers campbellsci ca Campbell Scientific Centro Caribe S A CSCC 300 N Cementerio Edificio Breller...

Отзывы: