Use low capacitance, low resistance, screened cable (as fitted by Campbell Scientific) to
reach distances of several hundred meters.
l
Ensure that the power ground cable has low resistance and is connected to the same
ground reference as the data logger control terminals.
l
Be aware that daisy-chaining sensors reduces the maximum cable length roughly in
proportion to the number of sensors connected in parallel.
8.3 Modbus register map
(p. 18) provides the input register map (function code 4) and
(p. 19) provides
the holding register map (functions 3, 6, and 16).
Table 8-1: Input register map
Input register
Value
Modbus
data type
Description
30001
Serial number
Float
1
Specifies the sensor serial number
assigned by the factory
30003
Temperature
Float
1
The CS240DM measures temperature
by using a 4-wire configuration. The
stored value is in degrees Celsius.
30005
Counter
Float
1
The counter provides an indicator
that the sensor is actively taking
measurements. This value will
increment once per measurement,
rolling over at 10,000.
30007
Sensor status
Float
1
0 = good
1 = open/short
30009
Temperature
range check
Float
1
0 = good/in range
1 = out of range
1
Modbus float is a 32-bit integer.
CS240 and CS240DM PT-1000 Class A, Back-of-Module Temperature Sensors
18