Section 7. Installation
160
7.6.3.12 Execution and Task Priority
Execution of program instructions is divided among the following three tasks:
•
Measurement task — rigidly timed measurement of sensors connected
directly to the CR3000
•
CDM task — rigidly timed measurement and control of CDM/CPI
(p. 532)
peripheral devices
•
Digital task (a.k.a, SDM task) — rigidly timed measurement and control
of SDM
(p. 554)
peripheral devices, pulse measurements, and RS-232
measurements.
•
Processing task — converts measurements to numbers represented by
engineering units, performs calculations, stores data, makes decisions to
actuate controls, and performs serial I/O communication.
Instructions or commands that are handled by each task are listed in table
Program Tasks
(p. 160).
These tasks are executed in either pipeline or sequential mode. When in pipeline
mode, tasks run more or less in parallel. When in sequential mode, tasks run
more or less in sequence. When a program is compiled, the CR3000 evaluates
the program and automatically determines which mode to use. Using the
PipelineMode or SequentialMode instruction at the beginning of the program
will force the program into one mode or the other. Mode information is included
in a message returned by the datalogger, which is displayed by the datalogger
support software
(p. 90).
The CRBasic Editor pre-compiler returns a similar
message.
Note A program can be forced to run in sequential or pipeline mode by
placing the SequentialMode or PipelineMode instruction in the
declarations section of the program.
Some tasks in a program may have higher priorities than others. Measurement
tasks generally take precedence over all others. Task priorities are different for
pipeline mode and sequential mode.
Содержание CR3000 Micrologger
Страница 2: ......
Страница 3: ......
Страница 4: ......
Страница 6: ......
Страница 30: ......
Страница 34: ......
Страница 36: ......
Страница 96: ......
Страница 200: ...Section 7 Installation 200 FIGURE 42 Running Average Frequency Response FIGURE 43 Running Average Signal Attenuation ...
Страница 485: ...Section 8 Operation 485 8 11 2 Data Display FIGURE 110 Keyboard and Display Displaying Data ...
Страница 487: ...Section 8 Operation 487 FIGURE 112 CR1000KD Real Time Custom ...
Страница 488: ...Section 8 Operation 488 8 11 2 3 Final Storage Data FIGURE 113 Keyboard and Display Final Storage Data ...
Страница 489: ...Section 8 Operation 489 8 11 3 Run Stop Program FIGURE 114 Keyboard and Display Run Stop Program ...
Страница 491: ...Section 8 Operation 491 FIGURE 116 Keyboard and Display File Edit ...
Страница 495: ...Section 8 Operation 495 Low power standby whenever possible Low power bus sets bus and modules to low power ...
Страница 496: ......
Страница 502: ......
Страница 564: ...Section 11 Glossary 564 FIGURE 126 Relationships of Accuracy Precision and Resolution ...
Страница 566: ......
Страница 594: ......
Страница 598: ......
Страница 600: ......
Страница 602: ......
Страница 624: ......
Страница 642: ......
Страница 643: ......