CDM-A100 Series
31
TABLE 10-1. CPIStatus Activity
Response
Meaning
Active
The module is connected to the
(p. 32)
bus and is making
measurements according to the datalogger program.
Offline
The module was present after startup but is no longer
responding.
Unused
The module is or was connected and powered but is not
included in the datalogger program.
Wait Config
The module has not yet responded to a datalogger’s attempts
to configure it.
Config Fail
The module could not be configured. A configuration error
message is appended to this response.
10.3 COMM status LED
(p. 32)
indicates the current operation of the CDM-
A100, as shown in TABLE
TABLE 10-2. COMM Status LED Activity
Green
Flashing
Module has been configured by datalogger
and is receiving sync signals
Orange
Flashing
Device has not been configured by
datalogger
Red
Single-Flash
Device has been configured but is not
receiving sync signals
Double-Flash
Device has encountered a scan timeout
Solid
Error
10.4 CPI Port LEDs
(p. 32)
bus indicate the current operation of
the CPI bus as shown in TABLE
TABLE 10-3. CPI Port LED Activity
Green
Flashing
Frame Sync
Orange
Flashing
CPI activity
Solid
CPI bus fault
10.5 Replacing a CDM-A108 or CDM-A116
An existing CDM-A100 can be replaced with a new module using the same
CPI address without requiring a change to the program.
Содержание CDM-A100 Series
Страница 2: ......
Страница 3: ......
Страница 7: ......
Страница 11: ...Table of Contents iv ...
Страница 45: ...CDM A100 Series 34 ...
Страница 47: ......
Страница 53: ...Appendix B Example Programs B 6 ...
Страница 57: ...Appendix C Calculating Network Restrictions C 4 ...
Страница 60: ......