CDM-A100 Series
12
6.1 Voltage Measurements – Specifications
Voltage measurements use a 24-bit Analog-to-Digital (A-to-D) converter. One
channel at a time is measured in numeric succession. Differential and single-
ended channels can be mixed.
Terminals
Differential Configuration
CDM-A108:
DIFF 1H/1L – 8H/8L
CDM-A116:
DIFF 1H/1L – 16H/16L
Single-Ended Configuration
CDM-A108:
SE 1 – 16
CDM-A116:
SE 1 – 32
Range:
Measurement Range and Resolution
(p. D-1)
Accuracy
1
0 to 40 °C:
±(0.04% of R Offset
2
)
–40 to 70 °C:
±(0.06% of R Offset
2
)
–55 to 85 °C:
±(0.08% of R Offset
2
)
Resolution:
Measurement Range and Resolution
(p. D-1)
Speed:
, Analog Voltage
Measurement Speed
(p. 13)
(p. 25)
Input Resistance:
>20 G
Ω
Input Limits:
±5 Vdc
Maximum Input Voltage:
±20 Vdc
DC Common-Mode Rejection: >120 dB with input reversal
≥
86 dB without input reversal
Normal-Mode Rejection:
>70 dB at 60 Hz
Input Current:
±3 nA typical at 25 °C
±12 nA maximum at 50 °C
±100 nA maximum at 85 °C
1
Accuracy specification does not include sensor error or measurement noise.
2