Basic Weather Station BWS-200
C-2
Check the following:
1.
Ensure that the value is one that should be returned by the attached sensors.
2.
Ensure that the battery voltage is between greater that 11.5V DC. The logger
will opertate between 7V and 16V DC.
3.
Check that the Wind Sentry, CS215 (and the ARG100 raingauge, if fitted) is
wired to the correct datalogger channel as shown in the sensor wiring table.
See Appendix A of this manual.
4.
If you have modified the original datalogger program in any way, ensure that
the correct range code parameters have been used –
see the Sensor and
Datalogger manuals for details.
5.
Check the appropriate sensor for damage and/or contamination.
If you have modified the original datalogger program you should
connect the sensors as described in Appendix A and download the
original program to eliminate program errors etc. before seeking
advice.
NOTE