The interface is electrically insulated
from all other circuits.

9

5

6

1

CTS
RTS
DSR

GND
DTR
TXD
RXD

Ambient conditions

Nominal range of use
for temperature:

0…15…30…45 

°

C (usage group II)

Storage temperature:

–40 to + 85 

°

C

Annual mean
relative humidity:

 75%

Power supply 

AC/DC power pack (DC or 50 - 60 Hz)

Rated voltage

Tolerance

24 -   60 V DC / AC

85 - 230 V DC / AC

Power consumption:

 9 W resp. 

 10 VA

Option (not allowed for CSA)

Power supply from
measuring input
(self powered):

 24 - 60 V AC or 85 - 230 V AC

 Please note the max. and min. measuring input voltage!

Type label

Input voltage

Tolerance Power

inscription

range

supply

(* acc. to appli- = internal power

connec-

cation N or U2) supply range

tion

Self powered
by U1/*

24 - 60 V AC

(int. 24-60 V)

Self powered
by U1/*

85 - 230 V AC

(int. 85-230 V)

Programming connector on transducer

Interface:

RS 232 C

DSUB socket:

9-pin

DC – 15 to + 33%
AC 

±

 10%

±

 10%

Internal
measuring
input

7.2 PC software for the SINEAX DME 401

SINEAX DME 401 transducer is equipped as standard with
both an RS 232C interface and an RS 485 MODBUS interface.
The latter permits up to 32 devices to be connected including
a master (PC).

Accordingly, two program packages are available for
the SINEAX DME 440/401, “PC Software DME 4” (Order
No. 146 557) and “METRAwin10 Software” (Order
No. 128 373).

PC Software DME 4”

 provides functions for both interfaces.

For example, the existing configuration of a transducer can
be simply adapted to changed measurement requirements,

measurements and counter readings can be uploaded and
other functions for specific devices executed.

The PC is connected to the RS 232 interface by the
programming cable (Order No. 980 179). In the case of an
RS 485 interface, a converter RS 232C 

 RS 485 is needed

which can be either a board in the PC or an external unit.

The software has an easy-to-operate, clear menu structure
which allows for the following functions to be performed:

• Uploading and display of the programmed configuration

of the transducer or, in the case of the RS 485, the
addressed device

• Easy change of input and bus parameters

Fig. 10. Overview of the parameters.

• Downloading of a modified or new configuration to the

(addressed) transducer

• Archiving of configuration files

• Configurable password access to those functions that

permit transducer data to be changed

• Configuration of all the usual methods of connection

(types of power system)

Fig. 11. Programmation of the input parameters.

Содержание Gossen MetraWatt SINEAX DME 401

Страница 1: ...instruments com http www gmc instruments com Betriebsanleitung Programmierbarer Multi Messumformer SINEAX DME 401 Mode d emploi Convertisseur de mesure multiple programmable SINEAX DME 401 Operating I...

Страница 2: ...des symboles ci contre dans le pr sent mode d emploi ThefollowingsymbolsintheOperatingInstructions indicate safety precautions which must be strictly observed Betriebsanleitung Programmierbarer Multi...

Страница 3: ...programmierten internen Energiez hler maxi mal 4 abfragen Die Programmierung des SINEAX DME 401 ber den Bus ist ebenfalls m glich Der Betrieb ber eine Standardschnittstelle EIA 485 ist gew hrleistet D...

Страница 4: ...squerschnitt Unbedingt sicher stellen dass die Leitungen beim Anschliessen spannungsfrei sind Anschlussleitungen nach Tabelle anschliessen 1 2 3 2 4 1 1 1 5 165 Messeing nge Netzformen Anwendung Klemm...

Страница 5: ...3 5 1 8 2 3 L1 L2 L3 k l K L 5 1 8 2 3 L1 L2 L3 u U v V v V u U k l K L 5 1 8 2 3 Dreileiter Drehstromnetz gleichbelastet I L1 Bei Strommessung ber L2 bzw L3 Spannungsanschluss nach folgender Tabelle...

Страница 6: ...1 3 1 L1 v V u U k l K L 2 11 3 1 2 L2 L3 L2 L3 N L2 L3 Vierleiter Drehstromnetz gleichbelastet I L1 L1 8 3 1 L1 k l K L 5 8 3 1 L1 v V u U k l K L 5 8 3 1 5 L2 L3 L2 L3 L2 L3 Dreileiter Drehstromnetz...

Страница 7: ...Einkopplung von St rungen vermin dert Der Schirm ist zu erden An den Bus lassen sich bis zu 32 Teilnehmer inklusive Master anschliessen Grunds tzlich ist der Anschluss von Ger ten aller Hersteller erl...

Страница 8: ...in Data Out A Dout Data Out B Data In A Data in B Handshake Out A Handshake Out B Handshake In A Handshake In B PC 5 1 6 2 7 3 8 4 9 GND TxD RxD DTR DSR RTS CTS 5 3 2 4 6 7 8 Interface 86201 von W T B...

Страница 9: ...Messung des Effektivwertes IB BST Einstellzeit f r BS Phasenverschiebungswinkel zwischen Strom und Spannung F Frequenz der Eingangsgr sse Fn Nennwert der Frequenz P Wirkleistung des Netzes P P1 P2 P3...

Страница 10: ...PF1 LF2 Leistungsfaktor Strang 2 sgnQ2 1 PF2 LF3 Leistungsfaktor Strang 3 sgnQ3 1 PF3 H Hilfsenergie Hn Nennwert der Hilfsenergie CT Stromwandler bersetzungsverh ltnis VT Spannungswandler bersetzungs...

Страница 11: ...te zur Verf gung Die PC Software DME 4 Bestell Nr 146 557 und die METRAwin10 Software f r den SINEAX DME 440 401 Bestell Nr 128 373 Die PC Software DME 4 stellt Funktionen f r beide Schnitt stellen zu...

Страница 12: ...biszu10Messwertengleichzeitig erfassbar von ausw hlbaren Messumformern mit Uhrzeit und Datum Zus tzliche Protokollierung von Minima und Maxima m glich Fortlaufende Aufzeichnung von bis zu 4 Messwerten...

Страница 13: ...r Fehlersuche Instandsetzung und einer abschlies senden berpr fungderKalibrierungundderSpannungs festigkeit in unserem Werk oder durch eine unserer Servicestellen zugelassen Beim ffnen der Abdeckung k...

Страница 14: ...s programm s au maximum 4 peuvent tre s lectionn s La programmation du SINEAX DME 401 est aussi possible travers les bus Le fonctionnement est galement assur par une interface standard EIA 485 L inter...

Страница 15: ...ples de 2 2 5 mm2 de section Lors du raccordement des c bles se rassurer imp rativement que toutes les lignes soient hors tension Raccorder les fils de connexion selon les indications du tableau 1 2 3...

Страница 16: ...1 I L1 L1 L2 L3 5 1 8 2 3 L1 L2 L3 k l K L 5 1 8 2 3 L1 L2 L3 u U v V v V u U k l K L 5 1 8 2 3 Courant triphas 3 fils charges quilibr es I L1 Pour la mesure du courant en L2 resp L3 connecter les ten...

Страница 17: ...u U k l K L 2 11 3 1 2 L2 L3 L2 L3 N L2 L3 Courant triphas 4 fils charges quilibr es I L1 L1 8 3 1 L1 k l K L 5 8 3 1 L1 v V u U k l K L 5 8 3 1 5 L2 L3 L2 L3 L2 L3 Courant triphas 3 fils charges qui...

Страница 18: ...blindage doit tre mis terre Le bus permet le raccordement de jusqu 32 appareils y compris le PC pilote Master Il est possible de raccorder tous les appareils de fabricants qui respectent le protocole...

Страница 19: ...ignal GND Sortie de donn es A Sortie de donn es B Entr e de donn es A Entr e de donn es B Message de colloque sortie A Message de colloque sortie B Message de colloque entr e A Message de colloque ent...

Страница 20: ...de IB BS Fonction d aiguille entra n e pour la mesure de la valeur effective IB BST Temps de r ponse de BS Angle de d phasage entre courant et tension F Fr quence de la grandeur d entr e Fn Valeur nom...

Страница 21: ...Q1 S1 QF2 Facteur r actif branche 2 Q2 S2 QF3 Facteur r actif branche 3 Q3 S3 LF Facteur de puissance du r seau LF sgnQ 1 PF LF1 Facteur de puissance branche 1 sgnQ1 1 PF1 LF2 Facteur de puissance bra...

Страница 22: ...tive en moyenne annuelle 75 Alimentation auxiliaire Bloc d alimentation CC CA CC ou 50 60 Hz Tensions nominales Tol rances 24 60 V CC CA 85 230 V CC CA Consommation 9 W resp 10 VA Option pas admissibl...

Страница 23: ...les de ce logiciel sont Captage simultan de jusqu 10 valeurs de mesure fournies par des convertisseur de mesure s lectionn s avec indication de la date et de l heure Possibilit d tablir un protocole d...

Страница 24: ...nnect de toute source de tension les condensateurs de cet appareil peuvent encore tre charg s Apr s avoir r par ou remis en tat et referm l appareil v rifier que l isolement haute tension soit bien co...

Страница 25: ...al counters that have been configured max 4 can also viewed Provision is made for programming the SINEAX DME 401 via the bus A standard EIA 485 interface can be used The transducers are also equipped...

Страница 26: ...ls They are suited for single wire leads of 4 mm2 or multiple wire leads of 2 2 5 mm2 cross section Make sure that the cables are not live when making the connections Connect the leads according to th...

Страница 27: ...K L 5 1 8 2 3 L1 L2 L3 u U v V v V u U k l K L 5 1 8 2 3 3 wire 3 phase symmetric load I L1 Connect the voltage according to the following table for current measurement in L2 or L3 Current transf Ter...

Страница 28: ...L1 v V u U k l K L 2 11 3 1 2 L2 L3 L2 L3 N L2 L3 4 wire 3 phase symmetric load I L1 L1 8 3 1 L1 k l K L 5 8 3 1 L1 v V u U k l K L 5 8 3 1 5 L2 L3 L2 L3 L2 L3 3 wire 3 phase symmetric load Phase shif...

Страница 29: ...nal noise to the bus and limits emissions from the bus The shield must be connected to solid ground You can connect up to 32 members to the bus including master Basically devices of different manufact...

Страница 30: ...ke Out A Handshake Out B Handshake In A Handshake In B PC 5 1 6 2 7 3 8 4 9 GND TxD RxD DTR DSR RTS CTS 5 3 2 4 6 7 8 Interface 86201 of W T Fig 8 Fig 8 shows the connection of transducer DME 401 to t...

Страница 31: ...Q1 Reactive power phase 1 phase to neutral L1 N Q2 Reactive power phase 2 phase to neutral L2 N Q3 Reactive power phase 3 phase to neutral L3 N S Apparent power of the system S I1 2 I2 2 I3 2 U1 2 U2...

Страница 32: ...eider Automation Inc Input Waveform Sinuso dal Rated frequency 50 60 or 16 2 3 Hz Own consumption VA with external power supply Voltage circuit U2 400 k Current circuit I2 0 01 QF Reactive power facto...

Страница 33: ...uding a master PC Accordingly two program packages are available for the SINEAX DME 440 401 PC Software DME 4 Order No 146 557 and METRAwin10 Software Order No 128 373 PCSoftwareDME4 providesfunctions...

Страница 34: ...analogue display Adjustable measurement scanning interval Printing of measurements in tables or as curves Transfer of measurements to other Windows programs Simple setting of parameters Provision for...

Страница 35: ...be charged even though the device has been disconnected from all voltage sources Afterrepaironmaintenanceandclosingofthedevice the insulation must be tested with high voltage with the values listed in...

Страница 36: ...36...

Отзывы: