TITLE
12
SAFETY options
FUNCTIONS > CX Input, CY Input
SAFETY INPUTS
If during the reverse motion a diff erent safety is triggered the automation will perform the appropriate action for the new triggered
safety, should multiple safeties be triggered at the same time the automation will be halted at its current position.
SENSITIVE EDGES
C7
REOPENING DURING CLOSING
• When the automation is in its closing cycle and the safety circuit is triggered the automation will reverse its motion until it reaches its fully open
position again.
• If the auto closing option is enabled and the safety is no longer triggered the auto closing countdown will commence, once completed the
automation will start the closing cycle again.
• If the auto closing option is not enabled the automation will return to the fully open position awaiting another activation from a command device.
C8
RECLOSING DURING OPENING
• When the automation is in its opening cycle and the safety circuit is triggered the automation will reverse its motion until it reaches its fully
closed position again.
• Once the automation has reached the fully closed position it will require another activation from a command device to restart.
The above sequence will be attempted 3 times before the automation is halted, the automation will then
require activation from a command device to restart.
C1
REOPENING DURING CLOSING
• When the automation is in its closing cycle and the safety circuit is triggered the automation will stop and reverse its motion until it reaches its
fully open position again.
• If the auto closing option is enabled and the safety is no longer triggered the auto closing countdown will commence, once completed the
automation will start the closing cycle again.
• If the auto closing option is not enabled the automation will return to the fully open position awaiting another activation from a command device.
C2
RECLOSING DURING OPENING
• When the automation is in its opening cycle and the safety circuit is triggered the automation will stop and reverse its motion until it reaches its
fully closed position again.
• Once the automation has reached the fully closed position it will require another activation from a command device to restart.
C3
PARTIAL STOP
• When the automation is in its opening cycle and the safety circuit is triggered the automation will stop.
• If the auto closing option is enabled and the safety is no longer triggered the auto closing countdown will commence, once completed the
automation will start closing the device.
C4
OBSTRUCTION WAIT
• When the automation is in either its opening or closing cycle and the safety circuit is triggered the automation will stop.
• Once the safety is no longer triggered the automation will carry on the cycle it was performing at the time it was interrupted.
Содержание 8K01MB-0560
Страница 30: ...TITLE notes...
Страница 31: ...TITLE notes...