CX-ED1410 ‘Universal’ Fire Electric Strike
Page 3 of 3
Black
Red
Blue
Green
Red
Green
Black
Blue
12V
24V
Black
Red
Blue
Green
(+12V)
(-)
Varistor
Varistor
(+24V)
(-)
5. Connections
6. Operation
POWER
12V AC/DC
Red/Black: +12V
Blue/Green: Ground
A varistor is provided to protect/prevent strike from spikes.
Connect varistor between input wires.
Note: The door strikes are to be powered via a class 2 power
limit output from a control panel or power supply that is UL
listed to UL Burglar Alarm/Access control standards.
How to modify fail-safe to fail-secure or vice versa.
(1). Loosen the screw as per the product diagram below.
(2). Rotate the set plate 180° and slide the plate until it is
properly seated.
(3). Tighten the screw.
Fail Safe Mode
Fail Secure Mode
24V AC/DC
Red:
+24V
Black/Blue: -
Green:
Ground