background image

Page 1 of 2

Delayed Egress Lock Maintenance Manual 

INSTRUCTIONS

Electrified Locks, Relays and Timers

These systems are meant to delay the egress in certain but not all cases. The delayed egress device should be automatically 
unlocked in case of a fire, earthquake etc. The door should be unlocked at once when the sprinkler or fire detection system goes off 
or during a power outage. In other words, it’s a matter of public safety if an emergency evacuation is required.
FOR SPECIAL LOCKING ARRANGEMENT: The delayed egress lock must be wired to a fire alarm system per NFPA code or other 
regulations to bypass the time delay in the event of a fire. Contact your local code authority to verify compliance with fire and 
building codes. 

RECOMMENDATIONS FOR INSPECTION AND MAINTENANCE:

1. 

It is the responsibility of the installer to ensure that the Dip Switch 8-1 setting complies with local Fire, Building and Life 
Safety Codes. All installations must be approved by the local Authority Having Jurisdiction (AHJ).

2. 

This product and all related accessories or parts must be inspected and maintained on a quarterly basis. 

3. 

Contacting surfaces of the electromagnetic lock and armature plate must be kept free of contaminating materials. 
Surfaces must be cleaned periodically with a non-abrasive cleaner.

4. 

All mounting fasteners must be inspected on a quarterly basis. When properly installed, the ends of the armature 
plate allow a slight movement, but the plate will feel secure when grasped at the bolt. There should be no movement 
to the mounting bracket or housing of the electromagnetic lock. For added safety, thread locking compound should 
be applied for the armature plate bolt and the four captive electromagnetic lock mounting screws to reduce chance of 
screws loosening over extended time. 

5. 

The door frame must be inspected and deemed structurally sound for the installation of the electromagnetic lock. 
The structural integrity of the mounting surfaces must be strong enough to meet or exceed the holding force of the 
product.

6. 

The lock must be protected from potential damage due to intruders or tampering. Wire the built-in tamper switch to an 
annunciator device to be alerted when the cover is removed by someone tampering with the lock.

7. 

The components, hardware, installation instructions and mounting template included are intended for use on out 
swinging doors.

8. 

Do not install this product on the exterior of buildings.

9. 

Check the door starts countdown when continuously pressed to exit. Adjust both the proxy sensor and proxy trigger to 
ensure the countdown is triggered when the door is pressed to open.

a. 

To increase the height of the proxy sensor from the front cover surface, turn the proxy holder clockwise.

b. 

To decrease the height of the proxy sensor from the front cover surface, turn the proxy holder 
counterclockwise increasing the gap between the sensor and the proxy trigger.

c. 

Using the M5 Allen key, screw in or out the proxy trigger that is spring loaded to increase or decrease the gap. 
Note: The proxy sensor and the proxy trigger does not need to touch to operate correctly.

10. 

Separate mounting accessories not included with this product must be used in the following applications: 

a. 

Narrow head jamb situations or center-hung doors. 

b. 

Wherever there is insufficient space on the door frame header to mount the lock 

c. 

Hollow metal or wood frames where the doorstop is not thick enough to allow the product to be installed

d. 

Wherever an obstruction in the door prevents installation of the armature plate at a proper height

e. 

Doors that do not permit the armature plate to be mounted low enough to meet the magnet surface. 

11. 

A mechanical latching device is recommended in conjunction with the Delayed Egress lock.

12. 

Do not leave problems unresolved. If a satisfactory solution cannot be achieved after troubleshooting a problem, 
please call Camden. If you must wait for the following workday to call for assistance, leave the door inoperable until 
satisfactory repairs can be made. Never sacrifice the safe operation of the automatic maglock for an incomplete 
solution.

WARNING: Improper installation, maintenance, inspection or usage of the product or any related accessories or parts may 

cause the electromagnetic lock, armature plate and associated hardware to disengage and fall, causing serious bodily injury and 
property damage.
The fire marshal will fine you for it during an inspection.

Отзывы: