CAMDEN CX-33 Скачать руководство пользователя страница 4

Page 4 of 28

CX-33 Advanced Logic Relay Installation Instructions

Section 3B

2 Door Timed Airlock  
(Mode 2)

Utilizing door position switches (Camden CX-MDC or 
equivalent), this mode ensures that only one door in an 
airlock will be open at a time. Each output hold time is 
adjustable from 1 – 50 seconds. 3 outputs allow for one 
of the doors to have an electric lock and a door operator. 
(Alternatively, the doors could have locks only and no 
operators.)

Refer to 

Diagram 2

, (Page 12) for the following connections.

Wire the activating device(s) for Door #1 to DRY 1 terminals. 
Wire the activating device(s) for Door #2 to DRY 2 terminals. 
Wire the respective door contact switches to Inputs 3 & 4. 
(The contact circuit must be closed when the door is closed).

Wire the outputs as shown.. If a lock is not used, set H1 & D1 
timers to zero (0.0), and Relay 1 will be ignored.

Once input and output connections are made, program the 
unit according to the General Programming Instructions on 
page 1, and walk-test the installation. Timing adjustments 
may need to be made.

It is NOT recommended to add the “Delay-on-activate”  
(or nuisance delay) feature in this mode!

Once the desired operation is achieved, proceed to  
Section 4, Pg 9 for

 System Inspection Instructions

.

Section 3C

2 Door Latching Airlock  
(Mode 3)

Utilizing door position switches, (Camden CX-MDC, or 
equivalent) this mode ensures that only one door in an airlock 
will be open at a time.  Providing the opposite door is closed, 
one switch activation will latch open (unlock) the door, and 
the second activation on the same input will allow the door 
to close (lock). 3 outputs allow for one of the doors to have 
an electric lock and a door operator. (Alternatively, the doors 
could have locks only and no operators.)

The CX-33 is unique in the industry because it also provides 
the ability to add an adjustable “Walk-away” time. If the door 
input has been activated but the door has not been opened, 
the relay will reset (re-lock). Both doors have their own 
respective adjustable timers. (If the time is set to zero, then 
this feature is disabled).

Refer to 

Diagram 3

, (Page 13) for the following connections.

Wire the activating device(s) for Door #1 to DRY 1 terminals. 
Wire the activating device(s) for Door #2 to DRY 2 terminals. 
Wire the respective door contact switches to Inputs 3 & 4. 
(The contact circuit must be closed when the door is closed).

Wire the outputs as shown. If a lock is not used, set H1 & D1 
timers to zero (0.0), and Relay 1 will be ignored.

Once input and output connections are made, program the 
unit according to the General Programming Instructions on 
page 1, and walk-test the installation. Timing adjustments 
may need to be made.

It is NOT recommended to add the “Delay-on-activate”  
(or nuisance delay) feature in this mode!

Once the desired operation is achieved, proceed to  
Section 4, Pg 9 for 

System Inspection Instructions

.

Section 3D

Bi-Directional Door Sequencer  
(Mode 4)

This mode sequences all 3 relays in both directions, also 
known as bi-directional door sequencing.

A basic 2-door sequencer with just two inputs and two 
outputs is shown in 

Diagram 4a

 (Page 14). A more complex 

sequencer utilizing 4 switch inputs, and allowing for one door 
with an electric lock is shown in 

Diagram 4b 

(Page 15).

DRY 1 or WET 1 inputs sequence Relay 1 to Relay 2 to Relay 3. 
DRY 2 input sequences Relay 3 to Relay 1 to Relay 2.

Input 3 only sequences Relay 1 to Relay 2, and Input 4 only 
activates Relay 3.

If a relay (Relay 1 for example) operation is not desired it 
can be turned off by setting the time delays to zero (in this 
example H1 & D1).

Once input and output connections are made, program the 
unit according to the General Programming Instructions on 
page 1, and walk-test the installation. Timing adjustments 
may need to be made.

In addition, you can add a “Delay-on-activate” (or nuisance 
delay) to this mode by setting time via Step 8 of the Program 
Mode. If this feature is used, any input will have to be held  
for at least the time indicated on the display 

before

 the  

CX-33 will activate. If this feature is not wanted, set the time 
to zero (0.0)

Once the desired operation is achieved, proceed to Section 4, 
Pg 9 for 

System Inspection Instructions

.

Содержание CX-33

Страница 1: ...read the instructions fully and made the required adjustments Mounting The CX 33 should be mounted in a clean dry location out of direct contact with the elements Suitable locations include inside a m...

Страница 2: ...contact N O or N C 3 Set Dry Input 3 to activate on normally open or normally closed contact N O or N C 4 Set Dry Input 4 to activate on normally open or normally closed contact N O or N C 5 Set Wet...

Страница 3: ...ergy S A M w switching network Mode 10 Proceed to section 3K on Page 7 Mag lock with N O Fire Alarm input Mode 11 Proceed to section 3L on Page 7 Mag lock with N C Fire Alarm input Mode 12 Proceed to...

Страница 4: ...tive adjustable timers If the time is set to zero then this feature is disabled Refer to Diagram 3 Page 13 for the following connections Wire the activating device s for Door 1 to DRY 1 terminals Wire...

Страница 5: ...nlock and open the door Refer to Diagram 6 Page 17 for the following connections The CX 33 allows for dry and or powered maintained connections to the Access System time clock DRY 1 and or WET inputs...

Страница 6: ...s are made program the unit according to the General Programming Instructions on page 1 and walk test the installation Timing adjustments may need to be made It is NOT recommended to add the Delay on...

Страница 7: ...1 2 Input 2 sequences Relays 2 3 Input 3 sequences Relays Section 3K Low Energy SAM Plus Mode 10 This mode combines a Low Energy Secondary Activation Module SAM with a switching network aka make break...

Страница 8: ...am 7a page 26 for connections The all active switches and Lock down Switch are all normally open switches The RESET switch is normally closed Connect as shown A fail safe electric strike or mag lock s...

Страница 9: ...y 320 mA max Inputs 4 x dry contacts and 1 x wet contact 4 5 120 V AC DC Optically isolated non polarity sensitive Response time 0 5 seconds Relay Output 3 x Form C SPDT Relay contact rating 3 amps 24...

Страница 10: ...Page 10 of 28...

Страница 11: ...Page 11 of 28...

Страница 12: ...Page 12 of 28...

Страница 13: ...Page 13 of 28...

Страница 14: ...Page 14 of 28...

Страница 15: ...Activating Switch Door 1 sequences relays 1 to 2 to 3 LED 1 LED 2 LED 3 DISPLAY Relay 1 Relay 2 Relay 3 N C N O COM N C N O COM N C N O COM POWER 12 24V AC DC DRY 1 DRY 2 DRY 3 DRY 4 WET INPUT INPUT I...

Страница 16: ...ut 4 fires relay s 2 3 and holds both until input is released 6 Relay 3 can be used for a status indicator 7 Wet I P activates on 4 5V AC DC Older interphone panels may produce a stray voltage when in...

Страница 17: ...relay or if available Dry 1 Input LED 1 CX 33 LED 2 LED 3 DISPLAY Relay 1 Relay 2 Relay 3 N C N C N O N O N O N C COM COM COM POWER 12 24V AC DC DRY 1 DRY 2 DRY 3 DRY 4 WET INPUT INPUT INPUT INPUT IN...

Страница 18: ...Page 18 of 28...

Страница 19: ...Page 19 of 28...

Страница 20: ...Page 20 of 28...

Страница 21: ...Page 21 of 28...

Страница 22: ...Page 22 of 28...

Страница 23: ...Page 23 of 28...

Страница 24: ...ea Blvd Mississauga Ontario L4W 2T7 Door 3 Operator Door 2 Operator Door 1 Operator LED 1 CX 33 LED 2 LED 3 Relay 1 Relay 2 Relay 3 N C N C N O N O N O N C COM COM COM POWER 12 24V AC DC DRY 1 DRY 2 D...

Страница 25: ...UL Approval or certification for this mode 2 Timer H1 sets the length of time the Push Panic switch must be pressed held before the door unlocks 3 Timer H2 sets the minimum ON time for the electric lo...

Страница 26: ...2 24V AC DC DRY 1 DRY 2 DRY 3 DRY 4 WET INPUT INPUT INPUT INPUT INPUT MENU UP DOWN 1 2 3 4 5 6 7 8 9 Lock Down PUSH TO LOCK DOWN PUSH TO RESET Lock Down Indicator Can be part of Lock Down Switch Fail...

Страница 27: ...DC DRY 1 DRY 2 DRY 3 DRY 4 WET INPUT INPUT INPUT INPUT INPUT MENU UP DOWN Electric Lock Door 1 Power for Strike Activating Switch Door 2 sequences relays 3 to 1 to 2 Door 1 Operator Door 2 Operator S...

Страница 28: ...ric Lock Door 1 Power for Strike Activating Switch Door 2 sequences relays 3 to 1 to 2 Door 1 Operator Door 2 Operator Switch Sequences Relays 1 2 only Switch activates Relay 3 only Optional Switches...

Отзывы: